| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹52.2 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹60.2 L+₹7.8 L (14.9%)Rejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | L2 | Rejected-Finance L2 | |
| 3 | L3₹60.2 L+₹7.9 L (15.1%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹61.5 L+₹9.1 L (17.4%)Rejected-Finance 33 CHANDASI HOUSE LANE NO 11 S K PURAM ARYA SAMAJ MANDIR ROAD RPS MORE BAILEY ROAD DANAPUR PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | L4 | Rejected-Finance L4 | |
| 5 | L5₹67.7 L+₹15.4 L (29.4%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | L5 | Rejected-Finance L5 |
Tender Value
₹84 L
EMD Value
₹1.7 L
Closing Date
12 Oct 2024, 6:00 pmClosed
CWE Jaipur
Military Engineer Services, HQ Commander Works Engineer, Kalyan Marg, Banipark, Jaipur-06
SPECIAL REPAIR/REPLACEMENT OF DISTRIBUTION TRANSFORMERS AGAINST BER AT GE KOTA MIL STN
2024_MES_673933_1
CWE/KOTA/82364/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Kota
As per NIT
7 documents required · 7 mandatory
₹1,000
Yes
GE Kota
₹1.7 L
3 Mar 2025
11 Sept 2024
14 Oct 2024
11 Sept 2024
12 Oct 2024
28 Sept 2024
11 Sept 2024 - 26 Sept 2024
Amount
Material and labour for disconnecting unserviceable transformer of any size and taking down from 2/4 pole/platform etc.using suitable crane or lifting machine and other accessories. Also placing the same at suitable position or storage yard complete all as specified and directed by Engr-in-charge.
Supply, installation, testing and commisioning of Transformer 200KVA, EEL - 3,11/0.433KV, 50 Hz, step down, outdoor type, ONAN Cooled oil immersed copper wound, transformer, complete with first filling of IS-335 ISI marked filtered & dehyrated tranformer oil and other standard fittings/acceesories and 7 position OFF ciricuit tap changer (Tapping range + 7.5% in steps of 2.5% Each) with vector group Dyn-11, with provision of HV and LV cable box (with cable glands) suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180 and complete with and including following accessories for installation of transformer all as specified and directed. 01. Name, rating & diagram plate -1 no. 02. Off circuit tap changing switch -1 no. 03. Earthing terminals -2 nos. 04. Lifting lugs -2 nos. 05. Oil level indicator (flush tube) -1no. 06. Oil drain valve with plug -1 no. 07. Oil filter valve with plug -1 no. 08. Conservator with oil filling hole with cap -1 no. 09. Thermometer pocket -1 no. 10. 4” dial type thermometer stem type -1 no. 11. Air release plug -1 no. 12. Silicagel breather -1 no. 13. Removable inspection opening on top cover -1 no. 14. Explosion vent -1 no. 15. Unidirectional c.i. rollers -4 nos.
Supply, installation, testing and commisioning of Transformer 250KVA, EEL - 3 ,, 11/0.433KV, 50 Hz, step down, outdoor type, ONAN Cooled oil immersed copper wound, transformer, complete with first filling of IS-335 ISI marked filtered & dehyrated tranformer oil and other standard fittings/acceesories and 7 position OFF ciricuit tap changer (Tapping range + 7.5% in steps of 2.5% Each) with vector group Dyn-11, with provision of HV and LV cable box (without cable glands) suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180 and complete with and including following accessories for installation of transformer all as specified and directed. 01. Name, rating & diagram plate -1 no. 02. Off circuit tap changing switch -1 no. 03. Earthing terminals -2 nos. 04. Lifting lugs -2 nos. 05. Oil level indicator (flush tube) -1no. 06. Oil drain valve with plug -1 no. 07. Oil filter valve with plug -1 no. 08. Conservator with oil filling hole with cap -1 no. 09. Thermometer pocket -1 no. 10. 4” dial type thermometer stem type & with mrp -1 no. 11. Air release plug -1 no. 12. Silicagel breather -1 no. 13. Removable inspection opening on top cover -1 no. 14. Explosion vent -1 no. 15. Unidirectional c.i. rollers -4 nos.
Supply, installation, testing and commisioning of Transformer 315 KVA, EEL - 3, 11/0.433KV, 50 Hz, step down, outdoor type, ONAN Cooled oil immersed copper wound, transformer, complete with first filling of IS-335 ISI marked filtered & dehyrated tranformer oil and other standard fittings/acceesories and 7 position OFF ciricuit tap changer (Tapping range + 7.5% in steps of 2.5% Each) with vector group Dyn-11, with provision of HV and LV cable box (without cable glands) suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180 and complete with and including following accessories for installation of transformer all as specified and directed. 01. Name, rating & diagram plate -1 no. 02. Off circuit tap changing switch -1 no. 03. Earthing terminals -2 nos. 04. Lifting lugs -2 nos. 05. Oil level indicator (flush tube) -1no. 06. Oil drain valve with plug -1 no. 07. Oil filter valve with plug -1 no. 08. Conservator with oil filling hole with cap -1 no. 09. Thermometer pocket -1 no. 10. 4” dial type thermometer stem type -1 no. 11. Air release plug -1 no. 12. Silicagel breather -1 no. 13. Removable inspection opening on top cover -1 no. 14. Explosion vent -1 no. 15. Unidirectional c.i. rollers -4 nos.
Supply, installation, testing and commisioning of Transformer 500 KVA, EEL-3, 11/0.433KV, 50 Hz, step down, indoor type, ONAN Cooled oil immersed copper wound, transformer, complete with first filling of IS-335 ISI marked filtered & dehyrated tranformer oil and other standard fittings/acceesories and 7 position OFF ciricuit tap changer (Tapping range + 7.5% in steps of 2.5% Each) with vector group Dyn-11, with provision of HV and LV cable box (without cable glands) suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180 and complete with and including following accessories for installation of transformer all as specified and directed. 01. Name, rating & diagram plate -1 no. 02. Off circuit tap changing switch -1 no. 03. Earthing terminals -2 nos. 04. Lifting lugs -2 nos. 05. Oil level indicator -1no. 06. Oil drain valve with plug -1 no. 07. Oil filter valve with plug -1 no. 08. Conservator with oil filling hole with cap -1 no. 09. Thermometer pocket -1 no. 10. 4” dial type thermometer stem type -1 no. 11. Air release plug -1 no. 12. Silicagel breather -1 no. 13. Removable inspection opening on top cover -1 no. 14. Explosion vent -1 no. 15. Unidirectional c.i. rollers -4 nos.
M & L in replacement and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed
M & L in replacement and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed
M & L in replacement and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed
M & L in replacement and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3.5 core complete all as specified and directed
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed
Returning & filling in including spearing, leveling watering and well ramming in layers not exc 25cm thick complete all as specified and directed
Removing of surplus soil not exc 50m and depositing where directed at a level not exc 1.5m above the starting point
Supply and Spread dry river sand for cable cushioning in trenches all as specified and directed. Note : Punned down thickness shall be considered for measurement .
Supply and lay burnt bricks sub class ‘B’ old size laid dry in trenches across the cable protection all as specified and as directed
Supply and lay GI tubing, light grade, 80 mm bore dia as cable protection fixed on walls/poles/laid in trenches complete including dismantling of old unserviceable pipe all as specified and directed
Supply and lay GI tubing, light grade, 50 mm bore dia as cable protection fixed on walls/poles/laid in trenches complete all as specified and as directed.
M&L in replacement of Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32 x 6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length, etc complete all as specified.
Sant Construction Co. (BID ID -3129277)
M/S Anil Enterprises (BID ID -3125888)
Roy and Sons Infrastructures (BID ID -3129939)
Vijaypower Generators Limited (BID ID -3128449)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .