Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L1 | Accepted-AOC AOC | |
| 2 | L2₹1.1 Cr+₹5.9 L (5.58%)Rejected-Finance TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L2 | Rejected-Finance Highest | |
| 3 | Rejected-Technical | - | Rejected-Technical Rejected | |
| 4 | Rejected-Technical 5 B 2 1ST FLOOR OPP METRO PILLOR 484 TILAK NAGAR DELHI 110018 | WEST | DELHI | 110018 | - | Rejected-Technical Rejected |
Tender Value
₹98.9 L
EMD Value
₹2.0 L
Closing Date
31 May 2022, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Divn. PWD B and R Br. Ambala Cantt.
Const. of MCH Block and Service Block in the campus of Civil Hospital, Sec.-6, Panchkula (Pdg. Fire Alarm and Public Address System).
2022_HRY_221994_1
PWD/Elect-KNL/Elect-AMB/110264
Open Tender
Construction Works
Works
90 days
Ambala Cantt.
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
₹2.0 L
Yes
5 Aug 2022
19 May 2022
1 Jun 2022
19 May 2022
31 May 2022
19 May 2022
Amount
Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. HSR NO. 23.7.6.2
SITC of Microprocessor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of required loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 2 Serial Ports. The panel shall have a built in power supply, battery charger maintenance free battery capable of running for a minimum 24 hours operation complete as required. The panel should also have IP30 or better protection. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. Make: Morley ZX5SE,Bosch Avenar 2000, Siemens Cereberus EN. NS-1
SITC of Analog Addressable type Active Repeater Fire Alarm Panel with Backlit LCD display, having controlls for reset, mute, accept, silence alarms and self test conforming to BS5839 standards with all labour and materials required to complete the job in all respect up to the entire satisfaction fo engineer-in-charge of work. Make : (Morley ZX R-A, Bosch FMR, Siemens FT201). NS-2
SITC of addressable multisensor smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make: Morley HM/PTSE/I + MI/B501AP/IV ,Bosch FAP-425-OT+ MS400B,Siemens OH720 + DB721 NS-3
SITC of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector). (Make: Morley HM/RHSE/I +MI/B501AP/IV, Bosch FAH-425-T + MS400B, Siemens HI720+ DB 721). NS-4
Supply, installation, testing & commissioning of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make : Morley HM/MCP/Glass, Bosch FMC-210- DM-G-R, Siemens FDM22. NS-5
Supply, installation, testing & commissioning of Addressable Control Relay Module with flexible network structures with a maximum switching current of 1A @ 30V DC. Shall be EN54/UL/VDS Certification Make : Morley MI/DCMO,Bosch FLM-420-RLV1-E, Siemens FDCIO221 NS-6
Supply, installation, testing & commissioning of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment). Make : (Morley MI DMMI, Bosch FLM-420-O1I1-E,Siemens FDCI221 NS-7
Supply, installation, testing & commissioning of Addressable Loop powered sounder with strobe/flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer - in Charge of work. Make: Morley WSO-PR-N05,Bosch FNM-420, Siemens FDS224R NS-8
Supply Installation, Testing & Commissioning of Glow Type Exit Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class - I material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour and material required to complete the job in all respect up to entire satisfaction of Engineer-in-Charge of work. Make Pearl/Giolite/OMEX. NS-9
SITC of minimum 1000 Mtr. Range Siren generatorprovided at the roof of the building with separate power suppl, relay etc. with all accessories required to complete the job in all respect up to the entire satisfaction of engineer incharge. Make: National/Kheraj NS-10
SITC of battery backup for controllers ( 5 KVA UPS on line with 2 hours backup ) Make Libert, Microtek, Eton. NS-11
SITC of PVC unsheathed s/c stranded ( ISI marked ) copper contuvtor cable 1100v grade in existing pipe excluding cost and erection of pipe but including connection etc. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer – in charge of work MAKE FINOLEX/POLYCAB/Plaza. PVC unsheathed copper size 1.5 sq mm single core NS-12
SITC of EN-54 Certified IP based EVAC PA controller capable of adding 12 zones in the system and expandable upto 400 zones with 14x 4 Audio matrix with full DSP functionality. 8 audio inputs, 4 audio outputs, 4 channel output matrix. Shall support the following: single line switching or redundant group A/B switching, amplifier redundany, 4 x 100V audio inputs and 12 speaker line outputs. 8000 fault, warning and event conditions log. Built in message manager for 100 emergency/business calls up to 85 minutes. 10 control inputs and 13 control outputs. Impedance measurement and Pilot Tone supervision for speaker line monitoring. Frequency response (ref. 1 kHz) 20 Hz to 20 kHz (-0.5 dB), Signal-to-noise ratio (A-weighted): Line in to line out: 106 dB typical, THD+N < 0.05%, Crosstalk (line level) Line in to line out (0 dB gain): < 100 dB at 1 kHz, Sample rate 48 kHz, DSP processing resolution 24-bit linear A/D and D/A conversion, 48-bit processing. The omneo interface unit is able to send and receive Dante audio to and from other PA Controllers with the transmission of up to 16 digital audio input signals and 16 digital audio output channels with low latency shall be possible.Ethernet connectors (Primary /Secondary)100/1000 Mbit/s, RJ-45,integrated transformer isolationSampling rate 48 kHz. Data format 24 Bit. Audio channels Up to 16 ✕ 16 at 48 kHz, Audio flows Up to 16 ✕ 16 simultaneous audio streams,Latency across network 5 ms (typically) Make /BOSCH/ Siemens/Honeywell NS-13
SITC of Booster amplifier 480 watts Frequency response: 60 Hz to 15 khz (+1/3db), Inputs :XLR & phone jack , Input 1, Input 2-4, Impendence :20kΩ, Sensitivity : 1 V balanced , S/N >: >85 dB complete in all respect Make /BOSCH/ Siemens/Honeywell NS-14
SITC of Horn Loudspeaker 15 watts . Max power 22.5 W, Rated power (PHC) 15 W ( 15,7.5,3.75 W) ,Sound pressure Level rated power 103dB ( At 1kHz,Iw,Im), Effective frequency range (-10dB) 500Hz to 5KHz ,Opening angle (at 1 kHz/4kHz,-6 dB), Rated voltage 100V . Rated impedance 667ohm. Ambient temperature range -25 to +55 C .Connection 4 wire cable, 50 cm long complete in all respect Make /BOSCH/ Siemens/Honeywell NS-16
SITC of Cabinet and Ceiling Speaker Max Power - 9 W ,Rated power (PHC) - 6 W(6-3-1.5), Sound pressure level at rate power /1 w ,(at1kHz,1m) (at 1 kHz, 1 m) - 96dB/ 90dB,Effective frequency range (-10 dB) - 200-15000 Hz,Opening angle (at 1 kHz/4 kHz, - 6 dB),In degrees - 150/70,Rated voltage - 100 V,Rated impedance - 1667 Make /BOSCH/ Siemens/Honeywell NS-17
Supply, installation, testing & commissioning of 32 U Standard rack to place all Av equipment Make Valrack, Comrack,Hive Networks. NS-18
Wiring for PA system with the following sizes of FRLS insulated copper conductor single core 1100 volts grade cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Finolex/Havel/Plaza. 2 x 1.5 sq.mm NS-19
Supply & erection of FIRE EXTINGUISHERS duly hang on wall with necessary hook complete in all respect (Make: Safex/Minimax/ Ceasefire). ABC Dry power type fire Extinguishers of 5 kg. capacity NS-20
Co2 type fire extinguishers of 4 Kg capacity NS-20 i
Prime Computers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .