Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.4 LAccepted-AOC | L1 | Accepted-AOC Work Awarded Being L1 | |
| 2 | L2₹37.7 L+₹1.4 L (3.77%)Rejected-Finance | L2 | Rejected-Finance Rejected being L2. | |
| 3 | L3₹38.8 L+₹2.5 L (6.79%)Rejected-Finance NOT AVAILABLE | NA | NA | 121004 | L3 | Rejected-Finance Rejected being L3. |
Tender Value
Refer Docs
EMD Value
₹76,100
Closing Date
28 Dec 2020, 5:00 pmClosed
EE JSV GHUMARWIN
EE JSV GHUMARWIN
SH Laying jointing and testing of rising main 50 mm dia GMS pipe MC Markota Phase ic dismentalling of existing main 40 mm dia 40 mm dia GMS pipe MC 1st stage kangri, Dismentallingrelaying of existing booster stage 200 mm dia MSERW pipe 125 mm dia
2020_HPIPH_43290_1
GMR-BLP-02(10388-437)
Open Tender
Civil Works
Item Rate
180 days
KOT DEHRA HATWAR NEAR BHARARI
Please refer Tender documents.
7 documents required · 7 mandatory
₹800
Yes
EE JSV GHUMARWIN
₹76,100
Yes
13 Apr 2021
17 Dec 2020
29 Dec 2020
17 Dec 2020
28 Dec 2020
17 Dec 2020
17 Dec 2020 - 28 Dec 2020
Amount
Excavation infoundation and trenches etc.(including pipes and pits upto all depths) in all kinds of soil such as pick work, jumper work, blasting and chiselling soft or hard rock where blasting is prohibited in all leads and lifts including trimming and dressing of sides, levelling of bed to correct grade stacking the excavated soil clear from the edge of excavation and returning the excavated soil after laying, jointing and testing of GI pipes in trenches in 15cm layers including consolidating each deposited layers by ramming and watering and then disposing of all surplus excavated soil as directed in all leads and lifts and soring strutting and trimming and dressing where ever required including restoration of un-metalled/metalled/paved surface to its original condition including cost of diversion for traffic night signals fixing caution board, crossing over trenches for access to houses and fencing etc. complete in all respect. Pick Jumper work
Pick /jumper work
Pick Work
Laying jointing in trenches and testing ( to be leveled to grade) GMS pipe jointed with 5% of total joints flanged conforming to IS: 6392-1971 (lates upto date amendements) and remaining joints provided with circumferential butt welded joints and welding of flanges with pipes as per IS: 816-1965 with electrod as per IS: 814-2004 including required number and size of nuts and bolts as per 1369-1967 and compressed asbestos fiber jointing gaskets not less than 3mm in thickness as per IS: 2712-1965. The welding of flnages to be done on both faces in two layers on outer face & one layer on inner face to make the joints leak proof and to the entire satisfaction of the Engineer-in-charge. The laying of pipe shall confirm to IS: 5822-1994 and as per CPHEEO manual. The laying will include all operations such as cutting welding and jointing including flushing cleaning and hydroulic testing complete in all respect to the entire satisfaction of the Engineer-in-charge including entire carriage of materials. Pipe will be measured for straight length only. (Earth work in trenches, MS flanges and butt welding joints to be measured and paid for spearartely).
Markota Phase GMS pipe (Medium Class) 50 mm dia. with wall thickness of 3.60, outer dia 60.80 mm from RD 0/0 to 1500 M.S Table-17
GMS pipe (Medium Class) 50 mm dia. with wall thickness of 3.60, outer dia 60.80 mm from RD 1500to 2500 M.S Table-5
Dismentalling of existing Rising Main 40mm dia ( Markota Phase ) i/c stacking properly as per direction of Engineer- in- charge
GMS Tubes 40mm dia (Medium class) from RD 0/0 to 2500 with flange table- 5
Kangri Phase GMS Tubes 40 mm dia (Medium class) from RD 0 to 900 with flange table - 17
GMS Tubes 40 mm dia (Medium class) from RD 900 to 1800 with flange table- 5
Booster stage ( Kot Dehra Hatwar ) GMS pipe (Medium Class) 125 mm dia. with wall thickness of 4.50, outer dia 140.80 mm from RD 0/0 to 50 M.S Table-5
Booster Stage ( Existing ) Dismentaling of existing rising main 200 mm dia MSERW PIPE i/c stacking properly at site
Relaying,jointing and testing MSERW flanged/Butt welded pipes including cost of bends complete as per IS/ISO:3183-2007, Grade L210 or A, as per dimensions, weights and test pressures mentioned below in a random length of 4 to 7 meters. The Butt welded joints & MS flanges are to be provided on each joint as per table given below conforming to IS:6392-1971 and welding of flanges with electrodes as per relevants codes including required number & size of nuts and bolts as per relevants codes and asbestos fibre jointing gasket sheet not less than 3 mm thickness as per relevant codes. The welding of flanges to be done on both faces in two layers to make the joints leak proof and to entire satisfaction of the Engineer-in-Charge . The laying of pipe should be conformed to IS:5822-1994 (Earth work in trenches, Flanged joints & Butt welded joints to be measured and paid for seperately). The pipe shall have zinc coating inside as well as out side as per latest IS code.
MSERW pipe 200 mm dia with wall thickness 4.80 mm and outer dia. 219.10 mm having wt.25.368 Kg/Rmt from RD 0/0 to RD 30.
Providing and fixing of manual Chain pully block of INDEF/AVON/ BHARAT or any reputed make 3.00 Tonne along with 3.00 mtrs lift chain dia 8mm grade 80 alloy steel and its accessories including making arrangement complete in all respect in all leads and lifts.
Dismenntaling/ relaying of common header complete in all respect as per direction of Engineer In charge
Providing circumferencial Butt welded joints by electrical arc welding to GMS/MSERW pipe, welded in requisite number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS: 816-1969 specifications, by using welding electrodes conforming to IS:814-1991, at site of work complete in all respects, including manual/mechanical handling of pipes in all leads and lifts to the entire satisfaction of Engineer-in-Charge.
200 mm Dia MSERW Pipe as per IS/ISO: 3183-2007 of Grade L 210 or A (WT 4.80 mm ) R.D 0/0 to RD 30
Providing and fixing double flanged Cast Steel Reflux valve of Leader/ Kirloskar/ KSB make for rising main and capable of with standing 21 Kg/cm2 normal seat pressure conforming to BS:1868/API-600 or latest ammendments.
50 mm dia Class ASA 150 Flange Table 17 , 21 kg/cm2 nominal seat pressure ( Markota Phase)
40 mm dia Class ASA 150 Flange Table 17 , 21 kg/cm2 nominal seat pressure (Kangri Phase )
125 mm dia Class ASA 150 Flange Table 17 , 21 kg/cm2 nominal seat pressure ( Booster Stage Kot Dehra Hatwar )
Providing and fixing cast steel air valve (Isolating type) Double orifice with rubber ball 25 mm dia of KSB/ Leader/ Kirlosker make confirming to BIS:14845 with upto date amendments as per class PN 10 to with stand a seat pressure of 11.22 kg/cm2 in rising mains as per direction and to the entire satisfaction of Engineer-in-Charge.
Thrust Block Providing and laying cement concrete 1:4:8 ( 1 cement:4 sand: 8 stone aggregate 40 mm nominal size ) and curing complete excluding cost of form work in foundation and plinth within all leads and lifts complete in all respect and as direction by the Engineer-in-charge.
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm so as to give a rough finish including centering, shuttering, strutting and propping etc. with wooden battens and ballies height of propping and centering below supporting floor to ceiling not exceeding 4 mtrs and removal of the same for in situ reinforced concrete and plain concrete work in:-
Vertical surfaces such as walls (any thickness) portions and the like including attached pilasters buttresses, plinth and string courses and the like in all leads and lifts.
Providing and laying cement concrete 1:2:4 (1cement: 2 sand: 4graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work in foundatioin and plinth in all leads and lifts.
Foundation footing bases of columns and the like and mass concrete with in all leads and lifts and to the entire satisfaction of Engineer in charge.
Providing mild steel/tor steel reinforcement for RCC work including cutting bending, binding and placing in position complete upto floor two level.
PUMPING MACHINERY Markota phase Providing & Installation of horizontal spindle horizontal split casing / end suctions (back pull out arrangement ) single /double/multistage centrifugal pump or combination of pump in series of Mather and Platt / KSB/Kirloskar make as per BIS 1520-1980 with up to date amendments, read with IS:9137-1978 or latest edition suitable for lifting clear water . The pump should be fitted with bronze impellers of suitable alloys, priming funnels , casing rings, shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on MS/ Cast steel base plate ( base plate to be provided from the manufacturer,s of the pumping unit only) to squirrel cage drip proof induction motor of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments and suitable for operation on 400 (+/-) 10% volts, 50 cycles / second, three phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of + 10% and - 15% of the duty point head. The motor should be as per IS 325-1978 with up to date amendments.The pump set should suitable for operation on data given below:- Discharge:- 1.22 LPS or 4.392 M3 / Hrs per set, Total dynamic head :- 117.34 metre, LWL in sump well :- 844.00 metre, Shaft level:- 850.00 metre , Level at discharge point :- 910 metre , Residual head:- 3 metres, Static head:- 60 metre , Dia of Rising Main:- 50 mm , Length of Rising Main:- 2500 Rmt, Pumping Hours:- 16 hours, Coupling and base plate :- 2 sets, Turbidity :- less than 50 NTU, Temprature 20 degree to 45 degree centigrade.
Providing ICTP Main Switch with HRC fuses / side handled operated change over switch of L&T / crompton/ stanadards/ Havells make of suitable capacity operational rating as per IS 4064(part II) 1978 with up to date amendments)
Providing and fixing of floor/ wall mounted power factor shunk capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required 2.00KVAR rating according to HP offered including cables as per relevant ISI code of Siemens/Gloster/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date amendments .
Supplying fixing testing and successfully comissioning of floor mounted soft starter suitable for the pumping machinery of Crompoton Greaves / Siemens / L& T / ABB/ Allen Bradley duly certified by CE/UL/CSA suitable for motor operating in 200-480 VAC 3 phase Ambient temperature 25 degree to 60 degree cel. Ramp up time 0-20 second . inbuilt by pass system duly certified by CE/UL/CSA fully programmable including panel board with accessories and MCCB of reputed make with Ammeter,Voltmeter meter push button and single phase preventor complete. All digital display connected with motor etc. and all other connections needed to make the motor pump run successfully all as per the direction of Engineer in charge complete in all respects. The equipment supplied should be compatible / upgradable for use in future automization of the scheme with below mentioned technical specifications of soft panel / soft starter providing and fixing in position at site these accessories complete in all respect in all leads and lifts and carriage of material.
Providing and fixing double flanged Cast Iron sluice valve of Leader/Kirloskar/ KSB make class PN 1.00 of 40 mm dia capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per IS: 780-1984 with up to date amendments complete in all respects.
Providing and fixing double flanged Cast Iron sluice valve Leader/Kirloskar/KSB make one dia higher than pump for the delivery line of the pump capable of withstanding the normal seat pressure 16.320 kg/cm2 class PN 1.60 as per IS: 14846 with up to date amendments ( Total head i/c water hammer effect= 117.34 metre).
Providing and fixing double flanged Cast Iron reflux valve Leader/Kirloskar/KSB make one dia higher than pump for the delivery line of the pump capable of withstanding the normal seat pressure 16.32 kg/cm2 as per BS: 5312 (class PN 1.60) with up to date amendments ( Total head i/c water hammer effect= 117.34 metre).
Providing and fixing double flanged Cast iron non return valve Leader/Kirloskar/KSB make 40 mm dia withstanding the normal seat pressure 16.32 kg/cm2 (class PN 1.60 ) with up to date amendments ( Total head i/c water hammer effect=117.34 metre). IS 5312.
Providing and fixing circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0- 52 Kg/cm2
Providing and fixing double flanged GMS piping network for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as rappers, flanges, rubber gaskets minimum 3 mm in thickness as per IS 2712-1979, nuts and bolts as per IS:1364-1983, bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated.The size of various components are as under:- Suction pipe 40 mm dia M.C Minimum length= 5 metre Delivery pipe 32 mm dia M.C Minimum length= 10 metre Common header 40 mm dia M.C Minimum length = 10 metre The GMS tube confirming to IS :- 1239-1979 part-I Medium class flanged with MS flanges of table 5 in suction pipe and heavy class flanged with MS flanges of table 17 in delivery side and common header.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. Motor side: 4.00 mm2 or suitable capacity Min length = 20 mtrs. Supply side: 4.00 mm2 or suitable capacity Min. length =10 mtrs.
Providing and fixing double loop earthing with copper strips & copper plate 600 x600x3 mm thick complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
DEHRA PHASE Providing & Installation of horiontal spindle horizontal split casing / end suctions (back pull out arrangement ) single /double/multistage centrifugal pump or combination of pump in series of Mather and Platt / KSB/Kirloskar make as per BIS 1520-1980 with up to date amendments, read with IS:9137-1978 or latest edition suitable for lifting clear water . The pump should be fitted with bronze impellers of suitable alloys, priming funnels , casing rings, shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on MS/ Cast steel base plate ( base plate to be provided from the manufacturer,s of the pumping unit only) to squirrel cage drip proof induction motor of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments and suitable for operation on 400 (+/-) 10% volts, 50 cycles / second, three phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of + 10% and - 15% of the duty point head. The motor should be as per IS 325-1978 with up to date amendments.The pump set should suitable for operation on data given below:- Discharge:- 1.99 LPS or 7.164 M3 / Hrs per set, Total dynamic head :- 121.66 metre, LWL in sump well :- 844.00 metre, Shaft level:- 850.00 metre , Level at discharge point :- 920 metre , Residual head:- 3 metres, Static head:- 70 metre , Dia of Rising Main:- 65 mm , Length of Rising Main:- 3200 Rmt, Pumping Hours:- 16 hours, Coupling and base plate :- 2 sets, Turbidity :- less than 50 NTU, Temprature 20 degree to 45 degree centigrade.
Providing ICTP Main Switch with HRC fuses / side handled operated change over switch of L&T / crompton/ stanadards/ Havells make of suitable capacity operational rating as per IS 4064(part II) 1978 with up to date amendments)
Supplying fixing testing and successfully comissioning of floor mounted soft starter suitable for the pumping machinery of Crompoton Greaves / Siemens / L& T / ABB/ Allen Bradley duly certified by CE/UL/CSA suitable for motor operating in 200-480 VAC 3 phase Ambient temperature 25 degree to 60 degree cel. Ramp up time 0-20 second . inbuilt by pass system duly certified by CE/UL/CSA fully programmable including panel board with accessories and MCCB of reputed make with Ammeter,Voltmeter meter push button and single phase preventor complete. All digital display connected with motor etc. and all other connections needed to make the motor pump run successfully all as per the direction of Engineer in charge complete in all respects. The equipment supplied should be compatible / upgradable for use in future automization of the scheme with below mentioned technical specifications of soft panel / soft starter providing and fixing in position at site these accessories complete in all respect in all leads and lifts and carriage of material.
Providing and fixing double flanged Cast iron sluice valve of Leader/Kirloskar/KSB make class PN 1.60 of 40 mm dia capable of withstanding the normal seat pressure of 16.32 Kg/cm2 as per IS: 780-1984 with up to date amendments complete in all respects.
Providing and fixing double flanged Cast Iron sluice valve Leader/Kirloskar/KSB make 40 mm dia class PN 1.60 capable of withstanding the normal seat pressure 16.32 kg/cm2 as per IS: 14846 with up to date amendments ( Total head i/c water hammer effect= 121.66 metre).
Providing and fixing double flanged Cast Iron reflux valve Leader/Kirloskar/KSB make 40 mm dia capable of withstanding the normal seat pressure 16.32 kg/cm2 as per IS: 5312 with up to date amendments ( Total head i/c water hammer effect= 121.66 metre).
Providing and fixing double flanged Cast Iron non return valve Leader/Kirloskar/KSB make 32 mm dia withstanding the normal seat pressure 16.32 kg/cm2 as per IS 5312 (class PN 1.60) with up to date amendments ( Total head i/c water hammer effect=121.66 metre).
Providing and fixing circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0- 52 Kg/cm2
Providing and fixing double flanged GMS piping network for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as rappers, flanges, rubber gaskets minimum 3 mm in thickness as per IS 2712-1979, nuts and bolts as per IS:1364-1983, bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated.The size of various components are as under:- Suction pipe 40 mm dia M.C Minimum length= 5 metre Delivery pipe 32 mm dia M.C Minimum length= 10 metre Common header 32 mm dia M.C Minimum length = 10 metre The GMS tube confirming to IS :- 1239-1979 part-I Medium class flanged with MS flanges of table 5 in suction pipe and heavy class flanged with MS flanges of table 5 in delivery side and common header.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. Motor side: 4.00 mm2 Min length = 20 mtrs. Supply side: 4.00 mm2 Min. length =10 mtrs.
Providing and fixing double loop earthing with copper strips & copper plate 600 x600x3 mm thick complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
KOT KANJYAN TANDA PHASE Providing & Installation of horiontal spindle horizontal split casing / end suctions (back pull out arrangement ) single /double/multistage centrifugal pump or combination of pump in series of Mather and Platt / KSB/Kirloskar make as per BIS 1520-1980 with up to date amendments, read with IS:9137-1978 or latest edition suitable for lifting clear water . The pump should be fitted with bronze impellers of suitable alloys, priming funnels , casing rings, shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on MS/ Cast steel base plate ( base plate to be provided from the manufacturer,s of the pumping unit only) to squirrel cage drip proof induction motor of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments and suitable for operation on 400 (+/-) 10% volts, 50 cycles / second, three phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of + 10% and - 15% of the duty point head. The motor should be as per IS 325-1978 with up to date amendments.The pump set should suitable for operation on data given below:- Discharge:- 4.57 LPS or 16.452 M3 / Hrs per set, Total dynamic head :- 231.54 metre, LWL in sump well :- 823.00 metre, Shaft level:- 826.00 metre , Level at discharge point :- 970 metre , Residual head:- 3 metres, Static head:- 144 metre , Dia of Rising Main:- 80 mm , Length of Rising Main:- 3600 Rmt, Pumping Hours:- 16 hours, Coupling and base plate :- 2 sets, Turbidity :- less than 50 NTU, Temprature 20 degree to 45 degree centigrade.
Providing ICTP Main Switch with HRC fuses / side handled operated change over switch of L&T / crompton/ stanadard/ Havells make of suitable capacity operational rating as per IS 4064(part II) 1978 with up to date amendments)
Providing and fixing of floor/ wall mounted power factor shunk capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVAR rating according to HP offered including cables as per relevant ISI code of Siemens/Gloster/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date amendments .
Supplying fixing testing and successfully comissioning of floor mounted soft starter suitable for the pumping machinery of Crompoton Greaves / Siemens / L& T / ABB/ Allen Bradley duly certified by CE/UL/CSA suitable for motor operating in 200-480 VAC 3 phase Ambient temperature 25 degree to 60 degree cel. Ramp up time 0-20 second . inbuilt by pass system duly certified by CE/UL/CSA fully programmable including panel board with accessories and MCCB of reputed make with Ammeter,Voltmeter meter push button and single phase preventor complete. All digital display connected with motor etc. and all other connections needed to make the motor pump run successfully all as per the direction of Engineer in charge complete in all respects. The equipment supplied should be compatible / upgradable for use in future automization of the scheme with below mentioned technical specifications of soft panel / soft starter providing and fixing in position at site these accessories complete in all respect in all leads and lifts and carriage of material.
Providing and fixing double flanged Cast Iron sluice valve of Leader/Kirloskar/ KSB make class PN 1.00 of 40 mm dia capable of withstanding the normal seat pressure of 10.32 Kg/cm2 as per IS: 780-1984 with up to date amendments complete in all respects.
Providing and fixing double flanged Cast steel sluice valve Leader/Kirloskar/KSB make 40 mm dia capable of withstanding the normal seat pressure 52 kg/cm2 as per BIS: 1414 /API-600 (class ASA 300) with up to date amendments ( Total head i/c water hammer effect= 231.54 metre).
Providing and fixing double flanged Cast Steel reflux valve Leader/Kirloskar/KSB make 40 mm dia withstanding the normal seat pressure 52 kg/cm2 as per BIS: 1868 /API-600 (class ASA 300) with up to date amendments ( Total head i/c water hammer effect= 231.54 metre).
Providing and fixing double flanged Cast steel non return valve Leader/Kirloskar/KSB make 32 mm dia withstanding the normal seat pressure 52 kg/cm2 (class ASA 300) with up to date amendments ( Total head i/c water hammer effect=231.54 metre).
Providing and fixing circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0- 52 Kg/cm2
Providing and fixing double flanged GMS piping network for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as rappers, flanges, rubber gaskets minimum 3 mm in thickness as per IS 2712-1979, nuts and bolts as per IS:1364-1983, bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated.The size of various components are as under:- Suction pipe 40 mm dia M.C Minimum length= 5 metre Delivery pipe 32 mm dia M.C Minimum length= 10 metre Common header 32 mm dia M.C Minimum length = 10 metre The GMS tube confirming to IS :- 1239-1979 part-I Medium class flanged with MS flanges of table 5 in suction pipe and heavy class flanged with MS flanges of table 28 in delivery side and common header.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. Motor side: 6.0 mm2 Min length = 20 mtrs. Supply side: 10.00 mm2 Min. length =10 mtrs.
Providing and fixing double loop earthing with copper strips & copper plate 600 x600x3 mm thick complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
BOOSTER STAGE KANGRI PHASE Providing & Installation of mono submersible pumping set of KSB/Kirloskar/ Calma/ Johnsion/ Oswal make comprising to latest relevant code. The pump should be fitted with bronze impellers of suitable alloys as per IS 8034-1976latest suitable for clear water having greased packed bearings and shaft with wound stator on motor side with soft protection sleev on pump side ensuring better life for shaft of steel grade EN-8 coupled to a submersible squirrel cage electric induction motor (water proof type of required HP,RPM 2900 of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments , totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It also should be fitted with a device to take up the expansion of water with heating of motor . The pump set should include water level gaurds, erection clamps, cable clips and depth gauge etc. and suitable for operation on data given below:- A)SITE CONDITIONS:- Location of site :- Seer Khad Quality of water :- Clear water and turbidity less than 50 ppm Source:- Percolation well in right bank of seer khad having 6 metre dia & 8.00 metre depth. B)OPERATING CONDITIONS: AC Three phase current , 50 HZ operating frequency, 400 (+/-) rated voltage , double earthing system if required, speed of revolution, direction of rotation to be specified by the bidder, 20 hours , working hours per day , temperature of place specified up to 45 degree centigrade.C)MOTORBIS code BIS:- 9283-1979 with up to date amendments , Enclosure of motor as per BIS 4691-1985 (latest), continuous duty, Insulation class B. DETAIL OF SHAFT EXTENSION REQUIRED:- Break way torque to be given by he tenderer, but starting current should not exceed 2.5 times of the full load current. The motor should be able to withstand initial current of 2.5 times the rated current for two minutes without suffering damages or permanent deformations. D) PUMP The one set will work at a time and one set will act as stand bye , Two years normal maintenance as recommended by the manufacturer.E) Pump Operating Conditions:- 84.98 Metre Total Head, 82.00 Metre Static Head , 0.14 LPS Discharge , 1800 metre length of Rising Main 40 mm dia , - 15% to + 10% of total head limits of pump required to operate, Suction / delivery size of pump specified by the bidder, pump manufacturers certificate to be provided
Providing and Installation of suitable direct on line of MEI/Kilburn make starter confirming to BIS 8544 -1979 latest with upto date amendments for electric induction motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release with initial oil filing of suitable capacity.Starter i) Type ii) Make
Providing and fixing of M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal electric duly painted. The drawing of panel board shall be subject to approval of Engineer in charge
Providing and fixing of ICTP switches with HRC fuses of L&T/ Crompton /Havells make for required motor of suitable capacity as per IS: 4064-1978 with up to date amendments.
Providing and fixing of Bus bar chamber having 3 core copper bars of suitable rating for full length of three phase and one bar of half the rating of full length for neutral confirming to BIS 8064-1976 and 11353-1985 read with 5578-1985- latest with up to date ammendments .
Providing and fixing of MCB of Havell/MDS/ Kilburn Jyoti make of suitable capacity on incoming feeder with initial oil filling as per IS: 2516-1985 latest with up to date amendments with neutral linked under voltage release.
Providing and fixing Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments of 15 watts.
Providing and fixing 50 mm dial hour run metre of CEE/NEE make of suitable range as per relevant BIS specifications.
Providing and fixing double flanged Cast Iron sluice valve of Leader/Kirloskar/ KSB make class ASA PN 1.00 of 40 mm dia capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per IS: 780-1984 with up to date amendments. Head including water hammer effect = 84.98 metre.
Providing and fixing double flanged Cast iron swing check type reflux valve 40 mm dia of Leader/Kirloskar/KSB make class PN 1.0 and capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per IS: 14846 with up to date amendments.
Providing and laying copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.Motor side: 2.50 mm2 Min length = 20 mtrs. Supply side: 2.50 mm2 Min. length =10 mtrs.
Providing and fixing of PVC joint less flat water proof cable as per BIS 694-1990 latest with up to date amendments suitable for the pump sets offered from MCB to motor including all other electrical equipments/ accessories such as thimbles, flexible pipe solder, nuts and bolts, cable glands etc. laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities & in case of non acceptance by HPSEB authorities same shall be replaced by the bidder.
Providing and Laying double loop earthing with GI wire & GI plate complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Providing and fixing 100 mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-16 Kg/cm2
Providing and laying delivery pipe 32 mm dia and common header 32 mm dia GMS tubes Medium class as per IS 1239-1979 jointed with MS flanges of table 5 as per IS 6392-1971 up to a length of 20 metres including rappers, flanges, rubber gaskets, nuts and bolts bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.47
Providing and fixing of floor/ wall mounted power factor shunk capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required 2.00KVAR rating according to HP offered including cables as per relevant ISI code of Siemens/Gloster/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date amendments .
BHATWARA PHASE Providing & Installation of horiontal spindle horizontal split casing / end suctions (back pull out arrangement ) single /double/multistage centrifugal pump or combination of pump in series of Mather and Platt / KSB/Kirloskar make as per BIS 1520-1980 with up to date amendments, read with IS:9137-1978 or latest edition suitable for lifting clear water . The pump should be fitted with bronze impellers of suitable alloys, priming funnels , casing rings, shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on MS/ Cast steel base plate ( base plate to be provided from the manufacturer,s of the pumping unit only) to squirrel cage drip proof induction motor of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments and suitable for operation on 400 (+/-) 10% volts, 50 cycles / second, three phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of + 10% and - 15% of the duty point head. The motor should be as per IS 325-1978 with up to date amendments.The pump set should suitable for operation on data given below:- Discharge:- 0.90 LPS or 3.24 M3 / Hrs per set, Total dynamic head :- 157.22 metre, LWL in sump well :- 1000.00 metre, Shaft level:- 988.00 metre , Level at discharge point :- 1055.63 metre , Residual head:- 3 metres, Static head:- 67.63 metre , Dia of Rising Main:- 40 mm , Length of Rising Main:- 3000 Rmt, Pumping Hours:- 16 hours, Coupling and base plate :- 2 sets, Turbidity :- less than 50 NTU, Temprature 20 degree to 45 degree centigrade.
Providing ICTP Main Switch with HRC fuses / side handled operated change over switch of L&T / crompton/ stanadards/ Havells make of suitable capacity operational rating as per IS 4064(part II) 1978 with up to date amendments)
Supplying fixing testing and successfully comissioning of floor mounted soft starter suitable for the pumping machinery of Crompoton Greaves / Siemens / L& T / ABB/ Allen Bradley duly certified by CE/UL/CSA suitable for motor operating in 200-480 VAC 3 phase Ambient temperature 25 degree to 60 degree cel. Ramp up time 0-20 second . inbuilt by pass system duly certified by CE/UL/CSA fully programmable including panel board with accessories and MCCB of reputed make with Ammeter,Voltmeter meter push button and single phase preventor complete. All digital display connected with motor etc. and all other connections needed to make the motor pump run successfully all as per the direction of Engineer in charge complete in all respects. The equipment supplied should be compatible / upgradable for use in future automization of the scheme with below mentioned technical specifications of soft panel / soft starter providing and fixing in position at site these accessories complete in all respect in all leads and lifts and carriage of material.
Providing and fixing double flanged Cast iron sluice valve of Leader/Kirloskar/KSB make class PN 1.00 of 40 mm dia capable of withstanding the normal seat pressure of 16.32 Kg/cm2 as per IS: 780-1984 with up to date amendments complete in all respects.
Providing and fixing double flanged Cast steel sluice valve Leader/Kirloskar/KSB make 40 mm dia capable of withstanding the normal seat pressure 21 kg/cm2 as per BIS: 1414 /API-600 (class ASA 150) with up to date amendments ( Total head i/c water hammer effect= 157.22 metre).
Providing and fixing double flanged Cast Steel reflux valve Leader/Kirloskar/KSB make 40 mm dia capable of withstanding the normal seat pressure 21 kg/cm2 as per BIS: 1868 /API-600 (class ASA 150) with up to date amendments ( Total head i/c water hammer effect= 157.22 metre).
Providing and fixing double flanged Cast steel non return valve Leader/Kirloskar/KSB make 32 mm dia withstanding the normal seat pressure 21 kg/cm2 (class ASA 150) as per BIS 1868/ API 600 with up to date amendments ( Total head i/c water hammer effect=157.22 metre).
Providing and fixing100 mm dia circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0- 52 Kg/cm2
Providing and fixing double flanged GMS piping network for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as rappers, flanges, rubber gaskets minimum 3 mm in thickness as per IS 2712-1979, nuts and bolts as per IS:1364-1983, bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated.The size of various components are as under:- Suction pipe 40 mm dia M.C Minimum length= 15 metre Delivery pipe 32 mm dia M.C Minimum length= 5 metre Common header 32 mm dia M.C Minimum length = 10 metre The GMS tube confirming to IS :- 1239-1979 part-I Medium class flanged with MS flanges of table 5 in suction pipe and heavy class flanged with MS flanges of table 5 in delivery side and common header.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. Motor side: 4.00 mm2 Min length = 20 mtrs. Supply side: 4.00 mm2 Min. length =10 mtrs.
Providing and fixing double loop earthing with copper strips & copper plate 600 x600x3 mm thick complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
BOOSTER STAGE KOT DEHRA HATWAR Providing & Installation of mono submersible pumping set of KSB/Kirloskar/ Calma/ Johnsion/ Oswal make comprising to latest relevant code. The pump should be fitted with bronze impellers of suitable alloys as per IS 8034-1976 latest suitable for clear water having greased packed bearings and shaft with wound stator on motor side with soft protection sleeve on pump side ensuring better life for shaft of steel grade EN-8 coupled to a submersible squirrel cage electric induction motor (water proof type of required HP,RPM 2900 of standard make such as Kirloskar/Crompton/ BHEL confirming to BIS 9238-1979 latest with up to date amendments , totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It also should be fitted with a device to take up the expansion of water with heating of motor . The pump set should include water level gaurds, erection clamps, cable clips and depth gauge etc. and suitable for operation on data given below:- A)SITE CONDITIONS:- Location of site :- Seer Khad Quality of water :- Clear water and turbidity less than 50 ppm Source:- Percolation well in right bank of seer khad having 6 metre dia & 8.00 metre depth. B)OPERATING CONDITIONS: AC Three phase current , 50 HZ operating frequency, 400 (+/-) rated voltage , double earthing system if required, speed of revolution, direction of rotation to be specified by the bidder, 20 working hours per day , temprature of place specified up to 45 degree centigrade C)MOTOR BIS code BIS:- 9283-1979 with up to date amendments , Enclosure of motor as per BIS 4691-1985 (latest), continuous duty, Insulation class B. DETAIL OF SHAFT EXTENSION REQUIRED:- Break way torque to be given by he tenderer, but starting current should not exceed 2.5 times of the full load current. The motor should be able to withstand initial current of 2.5 times the rated current for two minutes without suffering damages or permanent deformations. D) PUMP The one set will work at a time and one set will act as stand bye , Two years normal maintenance as recommended by the manufacturer. E) Pump Operating Conditions:- 48.06 Metre Total Head, 37.00 Metre Static Head , 7.42 LPS Discharge , 780 metre length of Rising Main 125 mm dia , - 15% to + 10% of total head limits of pump required to operate, Suction / delivery size of pump specified by the bidder, pump manufacturers certificate to be provided
Supplying fixing testing and successfully comissioning of floor mounted soft starter suitable for the pumping machinery of Crompoton Greaves / Siemens / L& T / ABB/ Allen Bradley duly certified by CE/UL/CSA suitable for motor operating in 200-480 VAC 3 phase Ambient temperature 25 degree to 60 degree cel. Ramp up time 0-20 second . inbuilt by pass system duly certified by CE/UL/CSA fully programmable including panel board with accessories and MCCB of reputed make with Ammeter,Voltmeter meter push button and single phase preventor complete. All digital display connected with motor etc. and all other connections needed to make the motor pump run successfully all as per the direction of Engineer in charge complete in all respects. The equipment supplied should be compatible / upgradable for use in future automization of the scheme with below mentioned technical specifications of soft panel / soft starter providing and fixing in position at site these accessories complete in all respect in all leads and lifts and carriage of material.
Providing and fixing double flanged Cast Iron sluice valve of Leader/Kirloskar/KSB make class PN 1.00 of 40 mm dia capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per IS: 14846 with up to date amendments. Head including water hammer effect = 48.06 metre.
Providing and fixing double flanged Cast Iron swing check type reflux valve 100 mm dia of Leader/ Kirlosker / KSB make class PN 1.00 and capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per BIS: 5312-1984 Part I with up to date amendments.
Providing and fixing double flanged Cast iron NRV 125 mm dia of Leader/Kirloskar/Kartar make class PN 1.0 and capable of withstanding the normal seat pressure of 10.20 Kg/cm2 as per IS: 5312-1984 Part I with up to date amendments.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. Motor Side 4.00 mm2 Supply side: 4.00 mm2
Providing and fixing of PVC joint less flat water proof cable as per BIS 694-1990 latest with up to date amendments suitable for the pump sets offered from MCB to motor including all other electrical equipments/ accessories such as thimbles, flexible pipe solder, nuts and bolts, cable glands etc. laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities & in case of non acceptance by HPSEB authorities same shall be replaced by the bidder.
Providing and Laying double loop earthing with GI wire & GI plate complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm copper strips, digging of pits & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Providing and fixing 100 mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-16 Kg/cm2
Providing and laying delivery pipe 100 mm dia and common header 125 mm dia GMS tubes Medium class as per IS 1239-1979 jointed with MS flanges of table 17 as per IS 6392-1971 up to a length of 20 metres including rappers, flanges, rubber gaskets, nuts and bolts bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.69.
Providing and fixing of floor/ wall mounted power factor shunk capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required 4.00 KVAR rating or according to HP offered including cables as per relevant ISI code of Siemens/Gloster/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date amendments .
Raman Thakur Govt. Cont.
MNBN Enterprises
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .