Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 LAccepted-AOC | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹38.2 L+₹1.3 L (3.38%)Rejected-Finance | L2 | Rejected-Finance NOT L1 | |
| 3 | L3₹39.5 L+₹2.5 L (6.90%)Rejected-Finance VILLAGE GOROIMARI PO HALESWAR TEZPUR 784104 DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784104 | L3 | Rejected-Finance NOT L1 | |
| 4 | L4₹39.6 L+₹2.6 L (7.17%)Rejected-Finance | L4 | Rejected-Finance NOT L1 | |
| 5 | L5₹39.7 L+₹2.8 L (7.50%)Rejected-Finance | L5 | Rejected-Finance NOT L1 |
Tender Value
Refer Docs
EMD Value
₹78,800
Closing Date
23 Jun 2022, 6:00 pmClosed
GE (AF) TEZPUR
GE (AF) TEZPUR POST-SALONIBARI DIST- SONITPUR ASSAM-784104
COMPREHENSIVE AND PREVENTIVE MAINTAINANCE OF BMS SYSTEM AND FIRE ALARM SYSTEM AT WSA COMPLEX AT AIRFORCE STATION TEZPUR UNDER GE AF TEZPUR
2022_MES_529942_1
GE(AF)/TEZ/8665 OF 2022-23
Open Tender
Civil Works
Item Rate
330 days
AFS TEZPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (AF) TEZPUR
₹78,800
Yes
31 Dec 2022
10 Jun 2022
25 Jun 2022
10 Jun 2022
23 Jun 2022
18 Jun 2022
Amount
1- Material & labour for preventive and comprenshive maintenance of Building Management System (BMS) and fire alarm system with main control panels installed at building No.B-6 (BMS Room) includes BMS Software, Supervisory controllers, field controllers, field devices and shielded flexible cable and connected system installed at different locations at building No. B-1 ,B-2 ,B-3, B-4, B-5, and B-6. Make- SIEMENS through OEM i.e M/S SIEMENS or authorised dealer /service agent /channel partener of M/S SIEMENS duly authorised by M/S SIEMENS to carry out the job on their behalf as per MOU for the following components / parts /system by servicing /repairing/maintenance and including replacement of defective parts /system and when required to keeep the systems fully functional for 24 X 7 complete all as specified and directed by ENGR-IN-CHARGE. Note : 1. An expert engineer / technician having sound knowladge of above mentioned BMS & Fire alarm system alongwith a helper shall be deployed at site for general, shift on all working days to carry out daily maintenance / checking of both the system . He will be made to stay at a near by area to attend any emergenncy work at site during holiday/off hours also. This will ensure the performance of the utilities. In addition to that 4 Nos Preventive maintenance will be carried out by trained professionals on quaterly basis. The unit rate quoted will be deemed to include the cost of the same and no extra payment will be made on this account . 2. All the visit covered under quoted rate, the person deputed by service provider shall make a service report, which will be signed by Engr-in-chage and service provider and will retain in record. 3. Free repair/replacement of the parts for the equipment covered under comprehensive AMC subject to the exclusions listed hereunder. Such replacement of faulty parts shall became the property of service provider. 4. Attention is brought to the notice of the bidder that MOU with SIEMENS (i.e. OEM) has to be submitted to Engr-in-charge before commencement of work failing which no payment will be released.
NOTE: BIDDER SHALL ALSO CONSIDER FOLLOWING WHILE QUOTING UNIT RATE :- FAD:- (i)Networkable Microprocessor based analouge adressable type Fire Control panel with OFC media networking moduel, Zonal indication ,zener panel with OFC media networking module,Zonal Indication, Zener barriers, provisions ofSingle booster for network OFC connectivity with Battery Power pack as per spefications. One loop panel with loop cards (99 Detector +99 Drives)- 03 Nos. (ii) Analogue adressable type multi sensor smoke photo electric detector with LED indication lamp and all fixing accessories-47 Nos. (iii) Response indicators with LED indication lamp-10 Nos (iv)Analouge adressable loop sounders with all fixing materials-32 Nos. (v) Pull type Mannual call stations with adressable monitor module -30 Nos (vi) Flame proof Pull type Manual call stations with adressable moniter module along with fixing accessories-04. (vii) Flame proof loop sounders with all fixing materials along with fixing acessories-04 Nos. (viii)Weather proof type analouge adressable Ordinary Pull type Manual call points fixing access complete-13 Nos (ix) Adressable control modules for tripping of AHU' and Activation of Siren in case of fire emergency-06 Nos (x) Self alligned motorised adressable Flame proof Beam detector (Set of Emmiter &Receiver ) with LED status indicater ,sensitivity measurement filters and other mounting accessories monitor modules along with complete accessories Monitor mdules along with complete accessories- 04 Nos (xi) Fault isolater modules with protective housing -09 Nos (xii) Exit (sinage)Light Fixture with 1.5 hrs battery backup with profile make -14 Nos. (xiii) Flame proof Exit (Signage) Light Fixture-04 Nos (xiv) Twisted pair 1.5 sqmm, shilded FRLS insulated copper conductor, flexible wire trough MS conduct -4491.90 RM.
(xv) CPU comprising of intel 1.3 processor ,4GB RAM, 500 GB HDD, intel motherboard of 3.4GHZ,19" LED Monitor ,Keyboard,Mouse, Network Adaptor, Graphic card connected toFire Alarm Panels .The CPU suitable to intigrate number of FACPs located in various locations wih software to display location of fire/activated device monitoring on the map of the entire facility with t display location of fire/activated device monitoring on the map of the entire facility with zoom capability and windows 7 professional 64 bit multitasking software with liscence ,A3 officejet printer and all acessories.CPU suitable to connect single mode Optic fibre csble and along with required module/converters to be added for OF cable as required.
BMS :- (i) Windos based graphical user software, web based with GUI, alarming , Reporting software as specifications with minimum one multi user fscility -01 No (ii) System interface unit (High Speed Deivice Router/Gateway ) that can be connected over BAC net/ IP Backbone ,BAC net over ethernet.Communicable with Native BAC net protocol over high speed MS/TPLAN.Having a high-speed true microprocessor global controller with BAC net comunication processor.Having Battery backup Real Time Clock -01 No. (III) Pentium IV PC 1.15 GHz with 128 MB RAM 40GB HDD ,52X CD ROM with inkjet Printer & Battery backup for minimum 30 minutes including integrations, repeters routers and any equipment as required foe cabling beyond 1.5 km length as required incluiding necessary lighting protection as required earthing and safeties as required -01 No. (iv) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. DDC 1 of required points aas per minimum data of points given in i/o summary (plants room) 100 points controller -01 Set. (v) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. DDC 2 of required points as per minimum data of points given in i/o summery 75 points controller (Total DDC Controller alongwith enclouser for 7 CSU's as per IO LIST) -06 Sets. (VI) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser.DDC 3 of required points as per minimum data of points given in i/o summery 50 points controller -02 sets. (vii) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. DDC 4 required points as per minimum data of points given in i/o summary 30 points controller-03 sets. (viii) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclosure temperature and relative humidity sensors suitable for duct mounting type - 44 Nos (ix) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. Ambient temprature &Humidity sensor -01 No. (x) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. Immersion type temprature sensor -06 Nos
(xi) Net workable DDC Controller with supply relays , wiring trays , wiring in an enclouser. Filter Dp switches with NO/NC contact adjustable with range 0-50 mm WC -44 Nos. (xii) 2C X 1.0 Sqmm screened unarmoured cable -5181 RM.. (xiii) 4CX1.0 Sqmm screened unarmoured cable -1914 RM. (xiv) 8C X 1.0 Sqmm screened cable -278 RM. (xv) 25mm dia GI conduit 16 G ISI Marked complete with acessories like bends ,tees junction boxes, clamps, screws etc- 3862 RM. junctions boxes, clampes ,screws etc -3862 RM. (xvi) 32mm dia GI conduit 16 G ISI Marked complete with acessories like bends ,tees, Junction boxes, clamps,screw etc- 1052 RM. (xvii) UPS 500 VA with Battery backup for 30 minutes -11 Nos. (xviii) UPS 1000 VA with Battery backup for 60 minutes -02No. Note :- (a) In case of any breakdown/defect /fault in the BMS/ Fire alarm, system is put off the follwing penalities shall be imposed on the contractor:- (i) Response time to attend any type of complaint lodged with the contractor/ his rep informed via telephonecally/email will be 08(Eight) houres. Rs 2000/- (Rupees two thousand ) per hour shall be recovered from his payment for not responding to the complaint /fault after 08 hours from the lodging of the complaint. (ii) Contract will provide contract details of his responsible persons and OEM rep, who can be contacted in case of emergency to lodge the complaint.
M/S L N ENTERPRISE
Singhs Construction
M/S TRADE CENTRE
Maa Mira Enterprise
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .