Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.7 LAccepted-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹26.5 L+₹3.6 L (15.5%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-Finance Other than lowest bidder |
Tender Value
₹13.6 L
EMD Value
₹27,240
Closing Date
3 Dec 2019, 6:00 pmClosed
GE UTILITY AMBALA CANTT
GE UTILITY AMBALA CANTT PIN-133001
SPECIAL REPAIRS REPLACEMENT OF UNSV LT PANELS ALONGWITH UG OH CABLES STREET LIGHTS WITH ALLIED WORKS AT HRDC 40 ARTY DIV SIG REGT AND CERTAIN SANCTIONED WORKS UNDER GE UTILITY AMBALA CANTT
2019_MES_294693_1
GE(U)/AMB-41/2019-20
Open Tender
Civil Works
Item Rate
240 days
AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹27,240
Yes
8 Oct 2020
5 Nov 2019
4 Dec 2019
5 Nov 2019
3 Dec 2019
20 Nov 2019
5 Nov 2019 - 19 Nov 2019
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose / soft soil and getting out for under ground cable / erection of poles/laying of pipes, stays etc complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and exc 1.5 mtr but n.exc 3mtr deep in loose / soft soil for laying of LT under ground cable and getting out incl dressing and ramming of bottom of excavation complete all as specified and directed.
Returning, filling, including spreading levelling , watering and well ramming excavated soil in layers n.exc 25cm thick in trenches after cable have been laid complete all as specified and as directed.
Removing of excavated surplus soil obtained from excavation to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed .
M&L sand cushioning for cable with river washed clean dry sharp sand and punning to provide required cover as per SSR Part – I complete all as directed. Note: Punned thickness of sand layer shall be paid to contractor
Material and labour well burnt old size sub Class ‘B’ bricks, laid flat, in trenches for cable protection complete all as specified and as directed by the Engineer-in-Charge.
M&L PCC (1:4:8) type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed by Engineer-in-Charge.
M&L PCC (1:3:6) type C-2 (using 20mm graded crushed stone aggregate) as in foot paths in any thickness as required at site, exposed surface of roads finishing surface smooth without using extra cement including necessary form work complete all as specified and directed by Engineer-in-Charge.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. Note: (i) Earth work, sand, bricks , removing, returning filling Aluminium thimbles/lugs will be paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
Description all as per Item Ser No 09 here in before but for 4.0 core 16 Sqmm.
Description all as per Item Ser No 09 here in before but for 4.0 core 25 Sqmm.
Description all as per Item Ser No 09 here in before but for 3.5 core 50 Sqmm.
Description all as per Item Ser No 09 here in before but for 3.5 core 150 Sqmm.
Description all as per Item Ser No 09 here in before but for 3.5 core 185 Sqmm.
Dismantling and taking down old unserviceable PCC pole any type and any size after disconnecting all electrical connection incl clearance of site complete all as the direction of Engr-in-Charge.
Supply , erection of PCC pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and as directed by Engr-in-charge. Note: Earth work and PCC shall be measured and paid separately. (ii) Description as specified and directed by Engr-in-Charge will be printed on each pole without any extra cost.
Supply and fix in replacement stay assembly complete with all accessories, such as stay plate 230X230X6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc. all as per electrical plate No 1 or SSR part 1 and as directed . Note: Only excavation and PCC work will be measured and paid separately.
M & L in replacement cross arms, bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed.
Supply & Fix in replacement 1100 volt grade heavy duty cable PVC insulated aluminium stranded conductor PVC sheathed suspended by insulating hanger not more than 1 mtr apart including 4mm suspension wire, cable size 10 sqmm twin core stranded conductor complete all as specified and directed.
Supply and Fixing of rigid non-metallic PVC conduit of dia 40 mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts saddles pipe hooks etc complete all as specified and directed.
Material and labour in replacement GI tubing 80 mm bore light grade, on poles,on walls, under floors, road crossing, as required at site complete all as directed by Engr-in Charge. Note: Clamps, Nut bolts, saddle etc will be measured and paid separately.
Description all as per item No 21 above but 40 mm dia.
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as per direction of Engr-In-Charge.
M&L aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified and as directed by Engineer-in-Charge.
M&L in replacement shackle type porcelain vitreous white or brown insulator including GI straps, washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm height, 90 mm dia, section of strap 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed by Engineer-in-Charge.
S & F in replacement pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm height and 65 mm dia with GI spindle two GI washer and one GI nut complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old u/s earthing and Material & labour earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 40mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old u/s earthing and Material & labour earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge.
Supply & installation of desert cooler of size 660x660x825mm (height) with outer body made out of PGI (Plain Galvanised iron) sheet not less than 0.90mm thickness for fixed part, thickness of PGI sheet for shutter not less than 0.70mm thick, front grill made out of PGI sheet with minimum weight 2.80Kgs or plastic grill as approved. Electric driven copper wounded fan motor 500mm sweep, three speed (high /medium/low) with metalic blade duly painted with synthetic enamel anticorrosive oven cured paint fitted to body, 1400RPM, 230 Volt, 50Hz and submersible pump for required flow of water (single phase) having nominal air flow capacity 4000cum per hour, wood wool pad shall be of proper thickness as approved complete all as specified and as directed.
M&L MS work such as angle iron flat iron (40mmx40mmx5mm) for desert cooler stand in any shape and size complete welding and cutting as directed and inclusive of one primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. Note: Size of angle iron, flat iron will be as per the direction of Engineer-in-Charge.
M&L point wiring with 2.5 sqmm copper stranded conductor PVC insulated and unsheathed cable ISI marked (FRLS) and drawing in and including non metallic medium grade not less then 19mm dia PVC conduit (heavy duty) ISI marked on surface of wall/ceiling with and including all conduit fitting clamps gutties, etc for one light point control by one switch including in MS sunken box or pressed steel terminal boxes with provision of new 2.8 mm thick plastic lamination sheet and housing the switches with brass screw and washers and PVC insulated continues earth wire of size 2.5 Sqmm (FRLS) of green colour to earth metal parts of fitting as specified and directed by Engr-in-Charge.
M&L point wiring with 4.00 sqmm copper stranded conductor PVC insulated and unsheathed cable ISI marked (FRLS) and drawing in and including non metallic medium grade not less then 19mm dia PVC conduit (heavy duty) ISI marked on surface of wall/ceiling with and including all conduit fitting clamps gutties, etc for one light point control by one switch including in MS sunken box or pressed steel terminal boxes with provision of new 2.8 mm thick plastic lamination sheet and housing the switches with brass screw and washers and PVC insulated continues earth wire of size 2.5 Sqmm (FRLS) of green colour to earth metal parts of fitting as specified and directed by Engr-in-Charge.
S&F socket out let 3 pin, 5/15 Amps flush type ISI Marked complete all as specified and directed by Engineer-in-Charge.
S&F switch piano flush type single pole one way 15 Amp ISI Marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5% and of capacity 5.0 KVA complete all as specified and directed by Engr-in-Charge.
Supply and installation air cooled split unit air conditioner hot and cold, electric driven with cordless remote control and with inbuilt air ioniser and Plasma filter for better indoor air quality with 5 star rating and EER 3.2 of capacity 2.0 TR complete all as specified and directed.
M&L single pole and neutral encosure with 2 pin and earth plug and socket complete with one single pole MCB SP 20 Amps ISI marked complete all as directed.
M&L wall stand for 2.0 TR capacity AC ready made out of MS angle of suitable size with stand load satisfactory complete all as directed
Supply and fixing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to pole or any other indicated suitation for loop earthing etc required 4mm dia galvanised iron or steel wire complete all as direction of Engr-in-Charge.
S & F in replacement of sheet metal enclosure triple pole and neutral 12 way with 200 Amps rated bus bar, 415 volts, double door incl concealed in wall, incoming and outgoing connections with suitable size of lugs/thimbles complete as per direction of Engr-in-Charge. Note :- (i) Enclosure will be concealed on wall or fixed on pole/wall as per site requirement without any extra cost. All demolition, cement work, clamps, nut, bolts, washers etc include in quoted rates. (ii) Cost of making description as per section of Engr-in-Charge is incl in quoted rate.
Supply and Fixing in replacement MCCB TPN 63 Amps, 415 volts, 16 KA, 4 pole, Ics= 100% Icu , overload adjustable short circuit fixed type incl complete connection all as per direction of Engr-in-Charge.
Supply and Fixing in replacement isolator/MCB 40 Amps, 240 volts, SP, breaking capacity 10 KA, ISI marked all as specified and directed.
Supply & fixing in replacement , installation commissioning and testing polycarbonate CPRI approved OEM made LT Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical should be IK-08 (5 Joule) in accordance with IEC 62262. The manufacture of board/panel shall be submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH ICE 60529. The gasket should be internally embedded made of polyurethane. The manufacrurer of board/panel shall submitted a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with EIC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily. Temperature Rise, dielectric properties, short circuit withstand current rated peak & short time withstand current and rated conditional short circuit current, Effectiveness of protective circuits. The board manufacturer must submit the copy of type test reports for polycarbonate thermoplastic board only. The test report submitted of other material of construction like MS , SS will not be applicable Guarantee and warranty certificates will be accepted only from orginal manufacture. The panel should pass glow wire test 960 C in accordance with 60695-2-11 flame retardant and self-extinguishing. Outdoor Box for MCCB suitable for 63 amp to 200 amp complete as per direction of Engr-in-Charge, Note : (i) Enclosure will be concealed on wall or fixed on pole/wall with MS chamber minimum 3mm thickness as per site requirement without any extra cost. All demolition, cement work, clamps, nut, bolts, washers etc included in quoted rates. (ii) Cost of making description as per direction of Engr-in-Charge is incl in quoted rate.
Taking down old switches and S & F of Automatic street light control with infrared sensor based NATRURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) . Three phase load of 8 KW for automatic switching of street lights. Nature switch operation should be based on Natural light Lux level . Required illuminance level for switching ON is < 30 Lux and for switching OFF < 10 Lux. The sensoe should also have part night operation facility of min.4 hrs to max 12 hrs. VMS should have adjustable over & under voltage trip level and protection against phase loss, Beurarl loss & phase reverse incl power contractors ( 3 nos of capacity 25 amps per phase each) and incoming ( 3 nos of capacity 32 amps each) - outgoing MCB (3 nos of capacity 32 amps each) & main load circuit wiring (Copper) of minimum 10 Sqmm. The sensor, VSM, power contractor, MCBs incl conected items should be enclosed in a pole/wall mountable enclosure made of rust proof, electric sock proof termite proof and FR grade SMC junction box conforming to IP54. The circuit should also have provision for manual operation (i.e sensor & VMS By pass option). Model: Swadeep 02EC8KW3P - VMS or equivelent in Schneider/Havells/Legrand. Make (i) Nature switch : Kakatiya Energy Systems/Healer/Bajaj (ii) Power contractor - L&T / BCH/Schneider (iii) Voltage Controlling Device - L&T or equivalent (IV) MCB- Hager/Schneider/L&T/Legrand, (v) Enclosure & circuit sheet - Sintex (shock proof , rust proof, termite proof, FR rade) (v) Circuit wiring-Polycab/Finolex Note (i)SS Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty cirtificate must be provided by contractor.
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 volts for XLPE cable of size 3.5/4.0 x 10 - 50 Sqmm complete all as directed by Engr-in-Charge.
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 volts for XLPE cable of size 3.5 x 70 - 150 Sqmm complete all as directed by Engr-in-Charge.
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 volts for XLPE cable of size 3.5 x 185 - 300 Sqmm complete all as directed by Engr-in-Charge.
Dismantling and taking down old UNSV street light fitting and Material and labour for new LED street light fitting of 70 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, TOP opening separate driver compartment with frame IP 66 protection suitable for pole mounting SMD led array with lense , cool white 6500 K LED efficacy>120 lm/W and system efficacy 90 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160V-300 V, power factor>0.95, working temperature range - 20 decree C to 60 degree C , built in surge protection of more than 9KV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting, welding, drilling holes,SS nut bolts& washer complete all as directed by Engr-in-Charge.
Supply and Fix new street light bracket made out of GI pipe medium grade 40 mm dia approx length not less than 120 cm bend to shape including new clamps made out of MS flat of size 30x4 mm thick including cutting, welding drilling holes, nut bolts, washers etc including two coats of aluminium paint over one coat of red oxide primer on MS work complete all as specified and directed by Engr-in-Charge.
Supply & fixing in repairs, installation commissioning and testing polycarbonate CPRI approved OEM made LT Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical should be IK-08 (5 Joule) in accordance with IEC 62262. The manufacture of board/panel shall be submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH ICE 60529. The gasket should be internally embedded made of polyurethane. The manufacruree of board/panel shall submitted a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with EIC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily. Temperature Rise, dielectric properties, short circuit withstand current rated peak & short time withstand current and rated conditional short circuit current, Effectiveness of protective circuits. The board manufacturer must submit the copy of type test reports for polycarbonate thermoplastic board only. The test repoty submitted of other material of construction like MS , SS will not be applicable Guarantee and warrantee certificates will be accepted only from orginal manufacture. The panel should pass glow wire test 960 C in accordance with 60695-2-11 flame retardant and self-extinguishing. Aluminium strip bus bars of appropriate size TPN 400 AMPs capacity sleeve insulated in color code mounted on epoxy insulators - 01 set.
(i) Supply and fixing MCCB 400 Amps, 10 KA 4 pole 415 Volts AC, (incoming) - 01 No
(ii) Supply and fixing MCCB 125 Amps, 10 KA 4 pole 415 Volts AC, (outgoing) - 04 Nos
(iii) Supply and fixing connected with MCCB 4 pole over voltage relay 230 V AC, U>275 V AC, 3 Phase in 1 module suitable for 3 Ph+N - 01 No
(iv) RYB indication LED type 22.5 mm dia, 230 volts protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos.
(vii) Misc items like screws, cable tie, copper cable 1.5/2.5 sqmm, cable lugs, sleeves etc
NOTE :- (i) The quoted rate shall includes minor items such as lugs, SS nuts bolts & washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel size and drawing shall be approved before placong of order from Engr-in-Charge/GE . (iv) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating busbar strip type duly insulated.
Supply and Fixing of rigid non-metallic PVC conduit of dia 25 mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts saddles pipe hooks etc.
Supply & Fix of passing through pipe , 1100 volts grade heavy duty, PVC insulated armoured 3 core copper stranded conductor cable of size 4 sqmm nominal cross section with connection in KIOSK box and street/security light complete all as specified and directed by Engr-in-Charge.
Supply and Fix of LED street light fitting of 120 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, TOP opening separate driver compartment with frame IP 66 protection suitable for pole mounting SMD led array with lense , cool white 6500 K LED efficacy>120 lm/W and system efficacy 90lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160V-300 V, power factor>0.95, working temperature range - 20 decree C to 60 degree C , built in surge protection of more than 9KV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting, welding, drilling holes, SS nut bolts & washer complete all as directed by Engr-in-Charge.
Supply and fixing HDPE tubing 50 mm dia of pressure rating 6 Kgf/Cm sqmm fixing on pole coping walls under floors, road crossing etc reqd at site and as per direction of Engr-in-Charge. Note : Cast of clamp, nut, bolts, saddle etc for fixing is incl in quoted rates.
S & F of Automatic street light control with infrared sensor based NATRURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) . Three phase load of 5 KW for automatic switching of street lights. Nature switch operation should be based on Natural light Lux level . Required illuminance level for switching ON is < 30 Lux and for switching OFF < 10 Lux. The nature switch alongwith power contractor (s) input supply MCB (s) and out put (load) MCB (s) should be enclosed in pole/wall mountable enclosure made of rest proof, electric shock proof termite proof and FR grade SMC junction box conforming to IP54. The circuit should be three phase load of 5 KW, input MCB rating 25-32 Amps, contactor rating 20-25 Amps, output MCB Rating 25 Amps, Madel : Swadeep 02EC5KW3P or equivelent in Schneider/Havells/Legrand. Make (i) Nature switch : Kakatiya Energy Systems/Healer/Bajaj (ii) Power contractor - L&T / BCH/Schneider (iii) Voltage Controlling Device - L&T (IV) MCB- Hager/Schneider/L&T/Legrand, (v) Enclosure & circuit sheet - Sintex (shock proof , rust proof, termite proof, FR rade) (v) Circuit wiring-Polycab/Finolex Note (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty cirtificate must be provided by contractor.(iv) Cost of marking description on the box is incl quoted rate.
S&F shock proof fire retradrant non transparent Kiosks pole box of size 310x210x120 mm made of engineering plastic on piece mounting, for out door type heavy duty, with three phase and neutral connectors suitable for connecting cable upto 95 sqmm. Suitable to house 3 nos cable with end termination joint with rail din for fixing DP MCB, incl MCB DP 6 Amp 'B' curve, fixing on steel tubular pole with the help of 02 nos clamp 20x4 mm including nuts, bolts washer etc and duly painted both side with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Make : Universal switch gearscontrol/Schneider/Sintex/Hensel or as approved by GE.
Supply ,installation commissioning and testing out door type cubical panel board outer shell of size 400x400x300 mm made out of 3.15 mm thick MS sheet and inner shell made of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm above and 45 cm below the ground level frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body abd door ) lockable/openable with arrangement of pad locking on both doors incl 2 Nos of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 volts, 50 Hz, incl Aluminium bus bar of capacity 200 Amps. tested at factory approved from CPRI approved factory fabricated having modern febrication and testing process follwed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS : 8623/93 comprising of the following :-
(i) Supply and fixing MCCB 100 Amps, 16 KA 4 pole 415 Volts AC, (incoming) - 01 No
(ii) Supply and fixing MCCB 63 Amps, 16 KA 4 pole 415 Volts AC, (Outgoing) - 01 No
(iii) Supply and fixing connected with MCCB 4 pole over voltage relay 230 V AC, U>275 V AC, 3 Phase in 1 module suitable for 3 Ph+N - 01 No
(iv) RYB indication LED type 22.5 mm dia, 230 volts protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos.
(VII) Misc items like screws, cable tie, copper cable 1.5/2.5 sqmm, cable lugs, sleeves etc
NOTE :- (i) The quoted rate shall includes minor items such as lugs,SS nuts & bolts, SS washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel size and drawing shall be approved before placong of order from Engr-in-Charge/GE . (iv) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating busbar strip type duly insulated. (v) Luvers shall be provided with steel (SS) jali provided only.
Supply and laying in trenches GI pipe 50 mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge. Note - Disturbed surface shall be make good by contractor without any extra cost.
Description all as per Item Ser No 58 here in before but 40mm bore.
Description all as per Item Ser No 58 here in before but 25mm bore.
Description all as per Item Ser No 58 here in before but 20mm bore.
Supply and fix gun metal globe or gate valve ISI marked with iron wheel screwed down high pressure screwed both ends for iron pipe of size 25mm bore complete all as specified and directed by Engineer-in-Charge.
S&F PVC Float valves of size 20 mm high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic ball screwed for iron pipe and fixed complete all as specified and directed.
R D Bansal
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .