Assistant Manager (North West Zone)
Supply and Installation of New fire fighting system in new AMC Buildings in Bodakdev wards and different wards of North West Zone of AMC
345309
Tender No 325_ Notice no_06/2026-27
Open
Miscellaneous Works
Works
Ahmedabad
5 documents required · 5 mandatory
₹1,500
Municipal commissioner, Ahmedabad
₹30,000
16 Sept 2026
16 Sept 2026
16 Sept 2026
28 Sept 2026
16 Sept 2026
Name of work :-Supply and Installation of New fire fighting system in new AMC Buildings in bodakdev wards and different wards of North West Zone of AMC
Rate Amount Approved Make
S.No. Description Qty Unit
Supply & Supply &
Installation Installation
Part-A - Fire Hydrant System
Supply, Installation, Testing & Commissioning of Fire Hydrant & Sprinkler
System as per the Technical Specifications & tender Drawings .The work shall
be Completed in all respect as per the Instruction of Engineer Incharge.The
system shall be Integrated with BMS (Refer the Technical Specifications of
BMS Specified in Electrical Tender Document).The Auto Glow Signage
applicable for the respective system shall be scope of Vendor.The Vendor shall
Prepare and submit 06 Sets of detailed shop Drawings as per Tender
Specifications/Tender Drawings, Vendor also shall Submit 06 Sets of As Built
Drawings and 03 Sets of Soft Copy (in the form of CD in Editable Format
alongwith applicable Test Certificates,Data Sheets,Operation & Maintenance
Supply, installation, testing, & commissioning of electric driven Main Fire
1 1 Set 350,000.00 350000.0 Kirloskar / Wilo / Lubi
Pump suitable for automatic operation consisting of the following specification.
Back Pull out ,centrifugal end suction type pump complete for delivery of
m3/hr (2280 LPM) with 2900 rpm against a total head of 70 metres with bronze
1.1 impeller complete with Gland Packing with Complete accessories like Base
Frame,Anti vibration Pads,Coupling etc to make the system functional in all
Squirrel cage induction , 3 phase ,415 Volt, 50 Hz, Energy Efficient Motor
1.2 suitable for above pump. (As per the Specifications of Motors specified in the
Electrical tender Document)
Supply, installation, testing, & commissioning of diesel engine driven Standby
2 Fire Pump suitable for automatic operation consisting of the following ( as per 1 Set 625,000.00 625000.0 Kirloskar / Wilo / Lubi
specification ).
Back Pull out ,centrifugal end suction type pump complete for delivery of
m3/hr (2280 LPM) 2150 rpm against a total head of 70 metres with bronze
2.1 impeller complete with Gland Packing with Complete accessories like Base
Frame,Anti vibration Pads,Coupling etc to make the system functional in all
Air cooled (Radiator Type) Diesel Engine developing suitable Power for the
above pump Complete with Exhaust Silencer,Hot Insulation with
Cladding,Supports ,Painting Complete with Battery,Charging system,Cables,
2.2 Panel (As per General Specifications in electrical Tender),Diesel Tank (Min
capacity for 4 Hrs Opration) Complete with Nozzles,Level Indicator, Isolation
Valves etc with Mounting Stand ,duly painted (Frame & Tank) in all respect to
make the System Functional.
Supplying, installing, testing, & commissioning of Electric Motor driven Pump
3 suitable for automatic operation consisting of the following ( as per 1 Set 75,000.00 75000.0 Kirloskar / Wilo / Lubi
specification ).- (Terrace Pump)
Back Pull out ,centrifugal end suction type pump complete for delivery of
LPM against a total head of 30 metres with bronze impeller complete with
Gland Packing with Complete accessories like Base Frame,Anti vibration
Pads,Coupling etc to make the system functional in all respect.
Squirrel cage induction , 3 phase ,415 Volt, 50 Hz, Energy Efficient Motor
suitable for above pump. (As per the Specifications of Motors specified in the
Electrical tender Document) & Supply, Installation, testing & commissioning of
cubical type floor mounted Electrical panel.The panel shall be designed as per
IS standard & Refer General Specifications of LT Panels defined in Electrical
Tender Document including the list approved makes.The Panel shall have
facility to Operate in Auto/Manual Mode of Terrace Pump. The Pressure
Switch ,Flow switch and control Cabling in between for the Individual Terrace
Pump shall be part of Vendor's Scope.
All incoming power & control cables of suitable size from panel to motors,
pressure switches, etc. including termination with Copper Lugs & Double
4 Compression Cable Glands, Cable Tray and Earthing as per IS standard and 1 Set 65,000.00 65000.0 Polycan, Finolex,Avocab
Defined in General Specification of Electrification of Electrical Tender
Document including Approved Makes.
Supply, Installation, testing & commissioning of single headed SS 304, ISI
mark oblique pattern hydrant valve with 80mm diameter flanged inlet & 63 mm Newage/ Winco / Shah
instantaneous type female out let with pvc cap- chain spring release type lug Bhogilal/Protecto
and accessories as per IS: 5290- 1983 (Type ‘A’)
Supply,Installation, testing & commissioning first aid hose reel, full swinging
with 30 mtr long, 25mm dia rubber lined, with ss 304 shut off nozzle of 6 mm Newage/ Winco / Shah
dia. confirming to IS: 884, 1969 including 25mm dia pipe connection from riser Bhogilal / Protecto
to hose reel with complete accessories.
Supply ,Installation, testing & commissioning air vessel of Min 450 mm dia. (8
mm thick) 1.5 meter long made from M.S with 25mm-dia spring-loaded air
release valve, safety valve and gunmetal full way valve. The Vessel shall be
7 Painted with one Coat of Red Oxide and Two Coats of Synthetic Enamel Paint . 1 Nos 30,000.00 30000.0 Giacomini / Rapidrop / Sant
The Vessel shall be Fixed and Mounted by Vendor including anchoring etc.
Two Numbers Extra Air vents with Isolation Ball valves to be Provided in the
Piping at the Highest Point.
Pipe - Jindal Hissar / Tata
Supply ,Installation, testing & commissioning of M.S. pipe heavy Class ‘C’ ISI
Pipe Fittings - VS Forge / JM /
marked as per IS: 1239/IS 3589 Part-I including cutting, screwing, welding etc.
U Bolt / Pipe Clamp - Hi tech
Nut bolts - TVS / Unbrako
with all fittings as tees, elbows, reducers, flanges clamps hangers painting with
Gasket - Uniklinger /
one coat of primer and two coats of synthetic enamel paint of approve shade.
Paint - Berger / Asian
a 250 NB (6 mm Thickness) 1 Mtrs 4,500.00
b 200 NB (6 mm Thickness) 1 Mtrs 3,500.00
e 80 NB 1 Mtrs 1,350.00
f 65 NB 1 Mtrs 1,150.00
g 50 NB 1 Mtrs 950.00
g 40 NB 1 Mtrs 750.00
g 32 NB 1 Mtrs 550.00
h 25 NB 1 Mtrs 450.00
S.I.T.C of Pressure gauges - Glycerine Filled SS 304 with all accessories like
9 1 Nos 3,500.00 3500.0 H Guru, Micro, Excel
needle- valve, Syphon etc. Range 0-16 Kg/cm2 , Dial - 150 mm, Size - 1/2 "
Supply,Installation, testing & commissioning of Diaphragm Type Pressure
10 switch, housing shall be die cast aluminum with SS 316 moving parts like 1 Nos 3,500.00 3500.0 Danfoss / Indfoss
pressure element and socket. the range 0 to 10 Kg/cm2..
Supply ,Fabrication,Erection and Painting of Steel Structure with one coat of Local / ISI Approved &
11 Red Oxide and Two Coat of Synthetic Enamel Paint for Support complete in 1 Kgs. 120.00 120.0 Anchor Fastner - Hilti /
all respect with the anchoring etc. Fischer
Excavation,back Filling and min 100 mm sand bedding of Underground Pipes
as defined in Technical Specification
Excavation 1 m3 650.00
Supply and fixing of Valve chamber including C.I.cover of size 750x750 mm
including excavation, C.C. bedding 1:4:8 100 mm thk., 230 mm thk brick
13 masonary with 100 mm thk. C.C. coping over masonary 15 mm thk. Smooth 1 Nos 24,600.00
cement plaster inside and rough cement plaster outside including curing as
defifined in Civil Tender Specification
Supply, Instalation,Testing & Commissioning of NP-03 Grade Hume Pipe
14 mm dia. (Refer Drawing - HAL-UM-302) & the specifications/Laying Refer 1 Mtrs 1,700.00
Civil Tender Specification.
Supply, Installation, testing & commissioning cast iron double flanged
,including mating Flanges,type IS marked sluice valve of the following size
15 Audco,Advance, Zoloto
complete with bolts, nuts, washers and inserted rubber gaskets as required: As
defined in Technical Specification
Supply, Installation, testing & commissioning ISI marked C.I (SS304 Disc)
Butterfly valve of P.N 1.6 Rating as per Technical Specification ,the mating
16 Audco,Advance, Zoloto
flange and additional Pair of Flanges shall be considered to Fix the distance
piece with Butterfly Valve.
250 NB (Gear Operated) 1 Nos. 32,000.00
200 NB (Gear Operated) 1 Nos 24,000.00
Supply,installation ,testing & commissioning of Ball Valves 3 Piece Design
17 ,Body - Forged or Cast Carbon Steel ,Trim and Ball SS410 , Seat SS410 Audco,Advance, Zoloto
Threaded End as per Technical Specification
Supply,Installation, testing & commissioning ISI marked C.I double flanged
18 dual plate type Non- Return valves (SS 304 disc) Complete with Mating Audco,Advance, Zoloto
Flanges,Nuts,Bolts and Gaskets, As per Technical Specification
Supply, installation, testing and commissioning of "Y" type Flanged Strainer
with SS 410 mesh of at least 10 times pipe area with flanged inlet and outlet
19 Audco,Advance, Zoloto
complete Complete with Mating Flanges,Nuts,Bolts and Gaskets, As per
Technical Specification.
S.I.T.C of ISI marked Ball Type Foot Valve, CI Body & Nitrile Reinforced Ball
20 Audco,Advance, Zoloto
PN 1.0 rating with matching Flanges , Nut, bolts, washer & Gaskets.
S.I.T.C of SS 304 63mm dia branch pipe as per ISI Standard , Complete in all Newage/ Winco / Shah
respect with Nuts,Bolts ,Gasket etc .As per Technical Specification Bhogilal/Protecto
Supply & Installation of outdoor type hose cabinet fabricated from 16g M.S
sheet with full front glass door and locking arrangement suitable to
accommodate , 2 no of 15 meter long hose pipe and one branch pipe. It should Newage/ Winco / Shah
be painted with one coat of primer and two coat of synthetic enamel paint. Bhogilal/Protecto
Complete in all respect with Fixing Supports of Steel Members Duly Painted in
same color and Clamping arrangement.
Supply & Installation of outdoor type hose cabinet fabricated from weather
proof FRP sheet with full front glass door and locking arrangement suitable to
accommodate , 2 no of 15 meter long hose pipe and one branch pipe. It should Newage/ Winco / Shah
be painted with one coat of primer and two coat of synthetic enamel paint. Bhogilal/Protecto
Complete in all respect with Fixing Supports of Steel Members Duly Painted in
same color and Clamping arrangement.
Supply,Installation, testing & commissioning 63mm dia 15mtr long reinforced
Newage/ Winco / Shah
24 rubber lined hose pipe confirming to IS: 636-1962 PART-A with ISI SS 304 1 Nos 5,500.00
Bhogilal/Protecto
male and female coupling, complete in all respect.
Supply,Installatation,Testing & Commissioning of gun metal 4 way fire brigade
Newage/ Winco / Shah
25 in let connection with 63mm instantaneous coupling with plug, cap, chain, 1 Nos 12,500.00
Bhogilal/Protecto
complete in all respect including, Nuts,Bolts,Gaskets etc.
Supply,Installation, testing & commissioning of 100 mm dia size gun metal
way Drawl off connection with 63mm instantaneous Coupling with Plug, Newage/ Winco / Shah
Cap,chain,C.I. Foot Valve,complete in all respect, complete with Bhogilal/Protecto
Nuts,Bolts,Gaskets etc.
Wrapping and Coating of Under Ground Piping with 4 MM Pypkot anti
27 1 M2 550.00 550.0 IWL/Equivalent
Corosive tape , As per Technical Specification
Flow Meter (turbine type/Mechanical Type) On line for Fire Hydrant Pump
Flow Testing - working Flow 137 m3/hr (Actres/Kranti Make), Body C.I.
28 turbine of SS, Hermetically Sealed, Environmentaly protected, Complete with 1 Nos. 100,000.00
fixing arrangement and mating flanges to make the flow meter functional in all
Centrifugal,Electrical Operated,Vertical, Mono Block, Motor above & Pump
Below,Dewatering Pump for Pump Room , Complete with Electrical
Panel,Level control & Cable etc. For auto operation, Capacity -270 LPM, Head -
29 15 Meters, The Pump shall be suitable to Pump Dust,Dirt and Suspended solids 1 Set 45,000.00 45000.0 Kirloskar / Wilo / Lubi
of same nature, Complete with Aluminium Body,SS 304 Impeller,SS
Fasteners,SS 410 Shaft. The Power supply shall be 3 Phase,415 Volt and the
Cable in between from Panel to Pump shall be vendor's scope. Refer the
Secifications & Approved makes of General Specification of Electrical Tender.
Obtaining approval on entire Fire Protection and detection system from Local
Fire Brigade authority / Insurance co. or from any other statutory body with all
respect the Statutory Approval Charges paid to the Statutory authorities will be
re imburshed by HAL on reciept of written approval from Statutory authority
and against submission of Payment reciepts from Statutory Authorities.(Legal
Fess shall be paid Be Extra.)
Supply & Installation of 6 Kg ABC Extinguisher of stored pressure type with
mono ammonium phosphate discharge tube and pressure gauge complete.
Tenderer shall give 3 years guarantee on cylinder with gas and powder.
Quantity & Quality shall be as Latest Code -15683/BIS Standard.
Supply & Installation of CO2 Fire Extinguisher of 4.5 Kg capacity fitted with
screw down type high pressure control valve with 1.0 M long rubber braided
32 discharge hose with horn. The Body shall be CCE approved with IS:2878 1 Nos 5,500.00
marking and supplied with initial charge of CO2 gas. The valve shall conform
to IS:3224.Quantity & Quality shall be as Latest Code -15683/BIS Standard.
Supply & Installation of 2 Kg ABC Extinguisher of stored pressure type with
mono ammonium phosphate discharge tube and pressure gauge complete.
Tenderer shall give 5 years guarantee on cylinder with gas and powder.Quantity
& Quality shall be as Latest Code -15683/BIS Standard.
Supply & Installation of Fire Bucket 9 Liters Complete with Bucket hanging
arrangement,Canopy and Stand duly Painted with one coat of Red Oxide and
Two Coats of Synthetic Enamel Paint.Quantity & Quality shall be as Latest
Code -15683/BIS Standard.
S.I.T.C of Fire extinguisher cap. 6 Ltr. filled with Wet Chemical / K Type for
35 Kitchen, Portable Type, Applicable fire classes A & K, Confirms to ISI 1 Nos 18,000.00
Approved IS 15683:2006.
S.I.T.C of Fire extinguisher cap. 4 kg.Clean Agent type HHFC 36 FA Confirms
37 S.I.T.C of Fire extinguisher cap. 5 kg.Modular type Poweder Base as per ISI. 1 Nos 4,500.00
Supply, Installation, testing and Commissioning of Sprinkler Alarm Valve with
Trim and Water Motor Gong Bell, Working press 175 PSI, Hydraulic Testing
Pressure 350 PSI, Body High Tensile C.I. , Seat Ring & Clapper - Bronze,
Cover Bolts Steel,Clapper Disc -EPDM & other accessories as UL Listed/FM
approved Specification. The Mechanical Gong Diameter 205 MM, UL
Listed/FM Approved.
Supply Installation testing & Commissioning of Flow switch for the maximum
working temperature of 250°C with flameproof protection. Sensing Element of
SS 316. The Flow switch shall hooked up with the Fire Alarm system the
Provision is the part of Vendor's Scope. The Flow Switch shall be UL
Listed/FM Approved.
b 100NB 1 Mtrs 8,500.00
c 80NB 1 Mtrs 7,500.00
d 65NB 1 Mtrs 6,500.00
e 50NB 1 Mtrs 5,500.00
Sprinkler K-5.6, 57 Deg.C, Standard Response, Standard Coverage. Maximum
Working Pressure: 175 psi (12 bar),Thread size: 1/2” (15 mm) NPT,Sprinkler
Body: Brass Casting,Body Cap: Stainless Steel,Deflector: Copper,Deflector
40 Pins: Stainless Steel,Compression Screw: Brass,Fusible Link Assembly:
Beryllium Nickel and Eutectic Solder,Fusible Link Levers: Stainless Steel,Lever
Bar: Copper Alloy,Belleville Spring Sealing Assembly: Nickel Alloy, coated on
both sides with Teflon Tape and Escutcheon Plate: Brass & Sprinkler Finish-
Chrome Finished.Sprinkler Heads Shall be UL Listed Approved
Upright Type Sprinkler Heads 1 Nos 450.00
Pendent Type Sprinkler Heads 1 Nos 450.00
Side Wall Sprinkler 1 Nos 550.00
Side Wall Extended Throw Sprinkler 1 Nos 650.00
S.I.T.C of Air release valve with Body Brass, Internal Parts & Float HDPE
complete with all accessories.
S.I.T.C of Inspector's Test Connection with Orifice and Isolation Gun Metal
Ball valves with screwed ends lever operated ASTM A 105,TRIM 13% Cr.
800# Including 25NB dia. pipes, fittings, Open Sprinkler, Coupling, pressure
gauge, Sight glass & Wall mounted MS Box for better operations. Nos
S.I.T.C of Flexible Dropper Unit - Complete with Braided SS Hose, Support
Bracket, Inlet/Outlet Connectors and Square Bar - Mild Steel, zinc plated,
Nipples, Reducer and other accessories. Size - 1 X 1/2" or 3/4" with 750 /
1000mm / 1500mm length
750mm length 1 Nos 1,000.00
1000mm length 1 Nos 1,400.00
1500mm length 1 Nos 1,800.00
Providing and fixing Orifice plates, S.S. 304, 12 mm thick, bore and
construction as per TAC's Sprinklers manual / IS:15105, for all horizontal
44 tapping for hydrant system for reduction of pressure in the range of 3.5-7.00 1 Nos 1,850.00
Kg/cm2 including one pair of Slip-on-Flange, nuts, bolts, gasket and complete
45 S.I.T.C of SS Metalic Expansion Bellows for Pumps with ASA # 150 Rating
S.I.T.C of Microprocessor based 4 loop capacity analogue Addressable Fire
Alarm Control Panel with minimum 80 characters LCD display, 800 event plus
200 alarm log history events, QWERTY keypad for programming. The panel
should be equipped with sufficient numbers of loops considering 20% spare
capacity in each loop. Each l0oop shall have a capacity of minimum 300 analog
46 1 Nos 300,000.00 300000.0 HoneyWell/GST
addressable devices. The panel shall work in degrade mode in case of CPU
failure. Four access levels, flash EPROM, 240 volts AC power supply,
automatic battery charger, 24 volts sealed lead acid batteries sufficient for
hours normal working and 30 mins in alarm condition. Designed to meet UL
864, 10th Edition.
S.I.T.C of Active Repeater Panel with 80 Characters Liquid Crystal Display
47 2 Nos 120,000.00 240000.0 HoneyWell/GST
with backlit control.
S.I.T.C of approved make Addressable Photoelectric Smoke Detector with
sensitivity range of 0.5 to 4.0% obs/ft. The detector shall have group decision
technology for faster response & avoid false alarms. The detector shall have
48 2 Nos 3,750.00 7500.0 HoneyWell/GST
twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly
rotary decimal switches.The detector shall work on coperative mode to avoid
false alarm.The detector shall comply UL268, 7th Edition guidelines.
49 S.I.T.C of Response indicator for all detectors located above false ceiling 2 Nos 170.00 340.0 HoneyWell/GST
S.I.T.C of approved make Addressable Rate of Rise Heat Detector rated at
deg C/min. The detector shall have twin bi-colour LED for 360 deg viewing.
50 2 Nos 3,850.00 7700.0 HoneyWell/GST
Addressing shall be with user friendly rotary decimal switches. Detector shall
comply UL521 guideline.
S.I.T.C of approved make Addressable Duct Smoke Detector.The High
Sensitivity Duct Smoke Detectors capable of 0.02% obs/ft sensisitivity with
51 Smoke Prove/Tubes and Addressable detectors including the cost of mounting 2 Nos 4,500.00 9000.0 HoneyWell/GST
accessories complete as per specifications and as required. Product Shall be
listed under UL Listed to standard 268A-7th edition & FM approved
S.I.T.C of approved make Addressable Loop Powered Autoaligned Beam
Detector. The beam detector shall be used for High Ceiling application with a
detection range from 5 upto 100 mtrs and highly resistant to building
52 movement; tolerates +/- 1° movement, Resistant to solid object intrusion, , Built- 1 Nos 48,500.00 48500.0 HoneyWell/GST
in imager heater, Resistant to strong light sources; does not alarm when
saturated by sunlight, Automatic sensitivity threshold level settings and drift
compensation. The detector shall be IP-55 compliant.
S.I.T.C of Sounder cum Strobe with Control Module rated at 80 dBA @ 3m for
53 Audible annunciation and 115cd flashintg at 1 Hz for visual indication. UL 2 Nos 4,350.00 8700.0 HoneyWell/GST
S.I.T.C of Addressable Manual Call Point (Break Glass Type). The device
54 2 Nos 5,500.00 11000.0 HoneyWell/GST
shall have an LED which shall blink in normal state & get steady on activation
to monitor the heath status of the device. The device shall comply UL approval.
SS.I.T.C of approved make Addressable Control Module for Sounders / Strobes
/ Sounder cum Strobes. The control module shall provide supervised NAC
output rated at 24v DC, 2A. The device shall have an LED which shall blink in
55 normal state & get steady on activation to monitor the heath status of the 2 Nos 4,850.00 9700.0 HoneyWell/GST
device. Addressing shall be with user friendly rotary decimal switches. Module
shall be supplied with mounting plate from OEM for ease of installation &
S.I.T.C of approved make Addressable Monitor Module for Sprinklers, Panic
Bars & other Third Party Inputs. The monitor module shall monitor potential
56 free contacts. The device shall have an LED which shall blink in normal state & 2 Nos 4,550.00 9100.0 HoneyWell/GST
get steady on activation to monitor the heath status of the device. Addressing
shall be with user friendly rotary decimal switches. Module shall be supplied
with mounting plate from OEM for ease of installation & maintenance.
S.I.T.C of approved make Isolator Module for Isolating short / dewired / loose
circuits with automatic resetting arrangement. Isolator Base can also be
57 proposed, however in that case needs to be considered with each detector & 2 Nos 3,850.00 7700.0 HoneyWell/GST
module. The device shall have an LED which shall blink in normal state & get
steady on activation to monitor the heath status of the device. Module shall be
supplied with mounting plate from OEM for ease of installation & maintenance.
S.I.T.C of of 2 Core X 1.5 Sq.mm FRLS Multistrand PVC insulated Copper
58 2 rmt. 130.00 260.0 Polycab/Finolex/Avocab
armoured cable with all required accessories.
Providing floor mounting stand for keeping 4 Nos. of Fire Buckets 1500 mm in
length, 900 mm in height frame made out of 30x30x4 mm. angle iron with cross
supports for legs, welded with 4 hooks and duly painted with one coat of red
59 lead and two coats of silver paint. With providing round bottom Fire bucket of 2 Nos 2,850.00
9 Litres capacity (4 nos) as per IS: 2546 made out of 24 gauge G.I. sheet with
extra handle at bottom duly painted white inside and red outside with Fire
mark, on provided stand .
S.I.T.C of Emergency evacuation Exit sinages self illuminating with battery
back up of 2 hrs, along with all required accessories such as driver, Junction
box etc required to complete the job.
61 Agni 4 Nos 650.00 2600.0 Agni
S.I.T.C of 2 Zone Microprocessor Based Main Alarm Panel With Power
Supply & Built In LCD Display, Real Time Clock & Event Logging.
63 S.I.T.C of Conventional Electronic Hooter with strobe 2 Nos 950.00 1900.0 Agni
64 S.I.T.C of Conventional Manual Call Point 2 Nos 650.00 1300.0 Agni
S.I.T.C of 2 core x 1 sq. mm flexible wire with pvc conduit & accessories for
65 2 rmt. 70.00 140.0 Polycab/Finolex/Avocab
S.I.T.C of 3 core x 1 sq. mm flexible wire with pvc conduit & accessories for
66 3.22 rmt. 90.00 289.8 Polycab/Finolex/Avocab
on off switch from pump house to each floor
67 S.I.T.C of Conventional Smoke detectors 2 Nos 1,350.00 2700.0 Appollo/System Sensor
68 S.I.T.C of of Conventional Heat detectors 2 Nos 1,550.00 3100.0 Appollo/System Sensor
69 S.I.T.C of of Fire retadent Paint 2 Hour Rating 2 Lit. 950.00
70 S.I.T.C of Fire Rated door 2 Hours Rating size as per Requirement. 2 Nos.
71 S.I.T.C of Fire Men Axe. As per the Requirement. 2 Nos. 1,650.00
Supply & Fixing of Auto glow Signage's (ACP SHEET / HEAVY FOAM
Fire Equipment 4" X 12" 2 Nos. 350.00
Fire Extinguisher 8" X 4" 2 Nos. 350.00
Incase of fire do not use lift, use, Use staircase 8’’ X 8’’ 2 Nos. 500.00
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
T.No. 325 BOQ.pdf
T.No. 325 Tender Documents.pdf
CCRS Penalty Circular.pdf
Technical Specification for Fire Protection System_16.10.25.pdf
Technical Specifications for Fire Alarm _16.10.25.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .