Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
21 Nov 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Shri A K Sinha IDSE CWE
HQ CWE (AF) Chiloda Military Engineer Services P.O CRPF Campus Vayu Shakti Nagar Gandhinagar 382042
REPAIR AND MAINTENANCE OF INTERNAL AND EXTERNAL ELECTRICAL WATER STP AND AC PLANT INSTALLATIONS AT AT ZONE A AREA AT WADSAR UNDER GE AF CHILODA
2026_MES_794849_1
82369/CHL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Wadsar
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Chiloda
₹98,000
21 Nov 2026
19 Oct 2026
23 Nov 2026
19 Oct 2026
21 Nov 2026
14 Nov 2026
19 Oct 2026 - 2 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Visiting and checking of health of Electrical installation 11 KV (Main receiving sub station) at for UGOR on monthly basics . Including attend all minor faults of entire Installion consisting of
Transformers of capacity 1250 KVA x 02 Nos ,
VCBs, Battery Banks, LT Panels having various type MCCBs/ACBs etc. checking the silica gel, topping up of transformer oil, followed with before and after testing of dieletric strength. Dehydration of transformer oil annually. All the consumable items are measured and paid seprately as under and directed by Engr- in - charge in the following shifts: | 12 | Each Job | - | - |
| 1.01 | M & L for Filteration of transformer oil of transformer installed at sub station UGOR to achieve electric strength of 65 KV for 1 minute at 4mm gap as per relevant IS with portable filteration plant, testing of oil for di electric strength before and after filteration shall be conducted all as directed by the Engineer in Charge Note : Test results after filteration shall be produced on completion. (1780 Ltrs x 02) complete all as specified and directed. | 3,351 | Ltrs | - | - |
| 1.02 | Supply and topping up new transformer oil into the conservator tank/body tank of the transformer at various location complete all as directed by the Engineer-in-charge. oil grade IS 335 with dielectric strength value not less then 65 KV complete all as specified and directed. | 209 | Ltrs | - | - |
| 2 | Visiting and checking of health for maintaining of HVAC installation at UGOR. Including attending all minor faults of entire HVAC Installion consisting of Chiller of 140TR X 02 Nos- cleaning,coolant check, cleaning air filters Air handling unit (02 Nos)- cleaning motor blower & chilled water coil,alignment of motor blower, cleaning RCC saucers drain, checking inlet and outlet valves,
Chiller and hot water pump - descaling of water,bearing alignment,oil leakage check,impeller/guard check,checking pump strainer and wire mesh,
Hot water generator- cleaning outer body ,
Fresh and exhaust fan- cleaning body,oil greacing motor shaft ,
HVAC MV panels- cleaning outer body , including following work/ job as under mention . All the consumable items are measured and paid seprately all as specified and as directed by Engr- in - charge. | 12 | Each Job | - | - |
| 2.01 | M & L for Taking out honey comb filter of EMP chiller from its existing postion and refixing the same to its original postion after finelly clean using high speed airblower with the Cleaning of condenser fins, coolant condenser cleaning on weelky basics complete all as specified and directed. | 52 | Each Job | - | - |
| 2.02 | Material and labour for checking Coolant level in HVAC system on monthy basics and top with coolent grade Sr no 5163579 Glycol Pro Pylena 5 Gal complete all as specified and directed. | 60 | Ltrs | - | - |
| 2.03 | M & L for Taking out pre filter of AHU from its existing postion and refixing the same to its original postion after finelly clean using high speed airblower of size 610mmx610mmx50mm as specified and directed by Engr in charge | 12 | Per month | - | - |
| 2.04 | M & L for Taking out pre filter of AHU from its existing postion and refixing the same to its original postion after finelly clean using high speed airblower of size 610mmx 610mm x50mm , EFF 10 Micron of AHU on monthly basis complete all as specified and directed. | 12 | Per month | - | - |
| 2.05 | M & L for Taking out pre filter of AHU from its existing postion and refixing the same to its original postion after finelly clean using high speed airblower of size 610mmx305mmx 50mm,EFF 10 Micron of AHU on monthly basic and relaced the damaged complete all as specified and directed. | 12 | Per month | - | - |
| 2.06 | M & L for Taking out Bag filter of AHU from its existing postion and refixing the same to its original postion after finelly clean using high speed airblower of Bag filter of size 610mmx610mmx 50mm, EFF 03 Micron of AHU on monthly basic and relaced the damaged complete all as specified and directed. | 12 | Per month | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
tender82369.pdf
Tender Documents • 1.32 MB
BOQ_891481.xls
BOQ • 0.28 MB
corr2_82369.pdf
PDF • 0.20 MB
corr1.pdf
PDF • 0.20 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .