Manager Projects
KEL Kochi
CONSTRUCTION OF KUFOS STAFF QUARTERS (PART 2) ( BALANCE WORKS- ELECTRIFICATION and PASSENGER LIFT)
2022_KEL_485590_2
KRO/ BDC/1119/2022
Open Tender
Electrical Works
Item Rate
720 days
KEL Kochi
As per NIT
6 documents required · 6 mandatory
₹2,950
₹50,000
Yes
5 May 2022
19 Apr 2022
3 May 2022
19 Apr 2022
30 Apr 2022
19 Apr 2022
19 Apr 2022 - 30 Apr 2022
Amount
DG SET
Installation, Testing and Commissioning of 200KVA, 3 Phase 415V, 0.8 power factor, comprising of diesel engine, fuel tank, alternator, base plate radiator, control panel with MCCB starting equipment exciter, home silencer and all necessary accessories etc. complete as required. (Including Acoustic Enclosure). This scope also includes the testing of Energy Meter, CTs, Relays etc and obtaining test certificate from KSEB / Electrical Inspectorate. (*All Statutory fees should be remitted by the Client / Consumeror it should be reimbursed on the submission of supporting documents).
SWITCH BOARDS
SB - 1 (EB Supply)
Supply, installation, testing & commissioning of cubicle type 50 Hz AC supply system having sufficient front surface area steel of 2mm thick for frame work and covers, 3mm thick for Switch Board Panel suitable for 415 V, 3 Phase, 4 wire, fabricated in compartmentalised design from CRCA sheet gland, plates cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 800 Amps capacity extensible type TPN Aluminum alloy bus bars of high conductivity, DMC / SMC / FRP bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 6 mm at the rear with switch gears with required size of AL. bus bars and control wiring with 1.5 sq. mm. PVC insulated FRLSH copper conductor cables, cable alleys etc. The panel shall conform to Electrical Inspectorate & KSEB standards and it shall only be manufactured after getting approval from Electrical Electrical Inspectorate, KSEB and the consultant.
Busbar
1 Runs of 63 x 10mm AL.Busbar for each Phase
1 Runs of 40 x 10mm AL.Busbar for Neutral
Incomer
1 Nos - 400A 36kA 4P Microprocessor based MCCB with
ROM, Spreader & Shunt Release
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 400/5A CL:1, 10VA CT
1 Nos - 400/5A CL:1, 10VA CT with control wiring for
adding APFC Panel in Future
1 Nos - Digital Multifunction Meter measuring V, A, F,
KWH, KVA, PF with Control MCBs
1 Nos - Earth Leakage Relay with CBCT
Surge Protection Device
1 Nos - 8 Module DIN Rail Mounting Type 1 + Type 2 /
Class 1 + class II 100kA SPD on the incoming side of EB
Supply with all necessary accessories etc. complete as
as required. The connections to RYB Phases, Neutral and
Earth shall be done using 16 Sq.mm FRLSH Single Core
Flexible Copper Conductor Cables with less than 0.45m in
length.
Outgoings
1 Nos - 250A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
2 Nos - 200A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
3 Nos - 160A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
SB - 2 (DG Supply)
Supply, installation, testing & commissioning of cubicle type
Switch Board Panel suitable for 415 V, 3 Phase, 4 wire,
50 Hz AC supply system having sufficient front surface area
fabricated in compartmentalised design from CRCA sheet
steel of 2mm thick for frame work and covers, 3mm thick
for gland, plates cleaning & finishing complete with 7 tank
process for powder coating in approved shade, having 800
Amps capacity extensible type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar
supports, with short circuit withstand capacity of 31 MVA
for 1 Sec., bottom base channel of MS section not less than
100 mm x 50 mm x 5 mm thick, fabrication shall be done in
transportable sections, entire panel shall have a common
copper earth bar of size 25 mm x 6 mm at the rear with
2 Nos. earth stud, solid connections from main bus bar to
switch gears with required size of AL. bus bars and control
wiring with 1.5 sq. mm. PVC insulated FRLSH copper
conductor cables, cable alleys etc. The panel shall conform
to Electrical Inspectorate & KSEB standards and it shall
only be manufactured after getting approval from Electrical
Inspectorate, KSEB and the consultant.
Busbar
1 Runs of 63 x 10mm AL.Busbar for each Phase
1 Runs of 40 x 10mm AL.Busbar for Neutral
Incomer
1 Nos - 400A 36kA 4P Microprocessor based MCCB with
ROM, Spreader & Shunt Release
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 400/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V, A, F,
KWH, KVA, PF with Control MCBs
1 Nos - Earth Leakage Relay with CBCT
Surge Protection Device
1 Nos - 8 Module DIN Rail Mounting Type 1 + Type 2 /
Class 1 + class II 100kA SPD on the incoming side of DG
Supply with all necessary accessories etc. complete as
as required. The connections to RYB Phases, Neutral and
Earth shall be done using 16 Sq.mm FRLSH Single Core
Flexible Copper Conductor Cables with less than 0.45m in
length.
Outgoings
1 Nos - 200A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
1 Nos - 160A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
2 Nos - 125A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
2 Nos - 100A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM, Spreader,
Digital Multifunction Meter measuring V, A, F, KWH,
KVA, PF with Control MCBs and CTs
SUB SWITCH BOARD
SSB - 1 (Common Panel)
Supply, installation, testing & commissioning of cubicle type
Sub Switch Board Panel suitable for 415 V, 3 Phase, 4 wire,
50 Hz AC supply system having sufficient front surface area
fabricated in compartmentalised design from CRCA sheet
steel of 2mm thick for frame work and covers, 3mm thick
for gland, plates cleaning & finishing complete with 7 tank
process for powder coating in approved shade, having 400
Amps capacity extensible type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar
supports, with short circuit withstand capacity of 31 MVA
for 1 Sec., bottom base channel of MS section not less than
100 mm x 50 mm x 5 mm thick, fabrication shall be done in
transportable sections, entire panel shall have a common
copper earth bar of size 25 mm x 6 mm at the rear with
2 Nos. earth stud, solid connections from main bus bar to
switch gears with required size of AL. bus bars and control
wiring with 1.5 sq. mm. PVC insulated FRLSH copper
conductor cables, cable alleys etc. The panel shall conform
to Electrical Inspectorate & KSEB standards and it shall
only be manufactured after getting approval from Electrical
Inspectorate, KSEB and the consultant.
Busbar
1 Runs of 40 x 10mm AL.Busbar for each Phase
1 Runs of 32 x 10mm AL.Busbar for Neutral
EB Side with Metering
4 Nos - Busbar Provision for fixing CTs
1 Nos - Provision for Fixing Three Phase Energy Meter
3 Nos - 200A Bakelite/Open Type Fuse Units with HRC
Fuse of suitable rating
1 Nos - 200A Neutral Link
There shall be KSEB Sealing Provision of CT Compartment
and Metering Compartment
1 Nos - 200A 4P Switch Disconnector
1 Set - RYB Indication lamps with Control MCBs
3 Nos - 200/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V, A, F,
KWH, KVA, PF with Control MCBs
1 Nos - 200A 4P Power Contactor (AC3)
DG Side
1 Nos - 200A 4P Switch Disconnector
1 Set RYB Indication lamps with Control MCBs
3 Nos - 200/5A CL:1, 10VA CT
1 Nos - Digital Multifunction Meter measuring V, A, F,
KWH, KVA, PF with Control MCBs
1 Nos - 200A 4P Power Contactor (AC3)
AMF control suitable for controling EB Supply & DG Supply
with AMF Relay with Control MCBs, Timer, Contactor
Mechanical Interlock and all other necessary accessories
complete with wiring as required.
Surge Protection Device
2 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 /
Class 1 + class II 100kA SPD on the incoming side of EB
Supply and DG Supply with all necessary accessories etc.
complete as required. The connections to RYB Phases,
Neutral and Earth shall be done using 10 Sq.mm FRLSH
Single Core Flexible Copper Conductor Cables with less than
0.45m in length.
Outgoings
1 Nos - 125A 4P Switch Disconnector
2 Nos - 100A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM and Spreader
1 Nos - 80A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM and Spreader
1 Nos - 63A 25kA 4P Thermal magnetic type MCCB
having 70 to 100% setting provision with ROM and Spreader
2 Nos - Street/Outdoor/Common Lighting Cubicle with 40A
30mA 4P RCCB, 40A 4P MCB, 40A 4P Contactor, 24Hour
OFF (Red) Push buttons, ON (Green) - OFF (Red)
Indication lamps with Control MCBs, etc.complete as
required.
METERING PANEL
Supply, installation, testing & commissioning of cubicle type
Metering Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz
AC supply system having sufficient front surface area
fabricated in compartmentalised design from CRCA sheet
steel of 2mm thick for frame work and covers, 3mm thick
for gland, plates cleaning & finishing complete with 7 tank
process for powder coating in approved shade, having 400
Amps capacity extensible type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar
supports, with short circuit withstand capacity of 31 MVA
for 1 Sec., bottom base channel of MS section not less than
100 mm x 50 mm x 5 mm thick, fabrication shall be done in
transportable sections, entire panel shall have a common
copper earth bar of size 25 mm x 6 mm at the rear with
2 Nos. earth stud, solid connections from main bus bar to
switch gears with required size of AL. bus bars and control
wiring with 1.5 sq. mm. PVC insulated FRLSH copper
conductor cables, cable alleys etc. The panel shall conform
to Electrical Inspectorate & KSEB standards and it shall
only be manufactured after getting approval from Electrical
Inspectorate, KSEB and the consultant.
Busbar
1 Runs of 25 x 10mm AL.Busbar for each Phase
1 Runs of 25 x 10mm AL.Busbar for Neutral
There shall be KSEB Sealing Provision of Busbar Chamber.
Incomer
1 Nos - 160 4P Isolator
1 Set - RYB Indication lamps with Control MCBs
There shall be KSEB Sealing Provision of Incomer Isolator
Compartment.
Surge Protection Device
1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 /
Class 1 + class II 100kA SPD on the incoming supply side
with all necessary accessories etc. complete as required.
The connections to RYB Phases, Neutral and Earth shall be
done using 10 Sq.mm FRLSH Single Core Flexible Copper
Conductor Cables with less than 0.45m in length.
Outgoing Compartment - 1
7 Nos - Provision for fixing Three Phase Energy Meter
There shall be KSEB Sealing Provision of Metering
Compartment Door.
Outgoing Compartment - 2
21 Nos - 63A Bakelite Fuse Unit with HRC Fuse of suitable
rating
7 Nos - 63A Neutral Link
7 Nos - 40A 4P C Curve MCB
7 Nos - ACCL
Wiring
All wiring and connections shall be done from Busbar to
Energy Meters, From Energy Meters to Fuses & Neutral
Links, From Fuses & Neutral Links to MCBs, From MCBs
to ACCL etc. using 6.0 Sq.mm FRLS Single Core Flexible
Copper conductor cables.
ACCL Specification
45A Micro Controller based full load changeover system
(EB to DG & DG to EB) in Metal Enclosure with 1 Nos
45A 4P Power Contactor (AC1) in EB Side and 1 Nos 45A
4P contactor (AC1) in DG Side, 2 Nos 10A Auxiliary
Contacts for contactor interlocking, 100A Elmex connectors
for making connections in EB Side, DG Side and load etc.
complete as required. All the internal wirings shall be done
using 6.0 Sq.mm Single Core Flexible Copper conductor
cables.
Supply, installation, testing & commissioning of cubicle type
Metering Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz
AC supply system having sufficient front surface area
fabricated in compartmentalised design from CRCA sheet
steel of 2mm thick for frame work and covers, 3mm thick
for gland, plates cleaning & finishing complete with 7 tank
process for powder coating in approved shade, having 400
Amps capacity extensible type TPN Aluminum alloy bus
bars of high conductivity, DMC / SMC / FRP bus bar
supports, with short circuit withstand capacity of 31 MVA
for 1 Sec., bottom base channel of MS section not less than
100 mm x 50 mm x 5 mm thick, fabrication shall be done in
transportable sections, entire panel shall have a common
copper earth bar of size 25 mm x 6 mm at the rear with
2 Nos. earth stud, solid connections from main bus bar to
switch gears with required size of AL. bus bars and control
wiring with 1.5 sq. mm. PVC insulated FRLSH copper
conductor cables, cable alleys etc. The panel shall conform
to Electrical Inspectorate & KSEB standards and it shall
only be manufactured after getting approval from Electrical
Inspectorate, KSEB and the consultant.
Busbar
1 Runs of 25 x 10mm AL.Busbar for each Phase
1 Runs of 25 x 10mm AL.Busbar for Neutral
There shall be KSEB Sealing Provision of Busbar Chamber.
Incomer
1 Nos - 160 4P Isolator
1 Set - RYB Indication lamps with Control MCBs
There shall be KSEB Sealing Provision of Incomer Isolator
Compartment.
Surge Protection Device
1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 /
Class 1 + class II 100kA SPD on the incoming supply side
with all necessary accessories etc. complete as required.
The connections to RYB Phases, Neutral and Earth shall be
done using 10 Sq.mm FRLSH Single Core Flexible Copper
Conductor Cables with less than 0.45m in length.
Outgoing Compartment - 1
7 Nos - Provision for fixing Three Phase Energy Meter
There shall be KSEB Sealing Provision of Metering
Compartment Door.
Outgoing Compartment - 2
21 Nos - 63A Bakelite Fuse Unit with HRC Fuse of suitable
rating
7 Nos - 63A Neutral Link
7 Nos - 40A 4P C Curve MCB
7 Nos - ACCL
Wiring
All wiring and connections shall be done from Busbar to
Energy Meters, From Energy Meters to Fuses & Neutral
Links, From Fuses & Neutral Links to MCBs, From MCBs
to ACCL etc. using 6.0 Sq.mm FRLS Single Core Flexible
Copper conductor cables.
ACCL Specification
45A Micro Controller based full load changeover system
(EB to DG & DG to EB) in Metal Enclosure with 1 Nos
45A 4P Power Contactor (AC1) in EB Side and 1 Nos 45A
4P contactor (AC1) in DG Side, 2 Nos 10A Auxiliary
Contacts for contactor interlocking, 100A Elmex connectors
for making connections in EB Side, DG Side and load etc.
complete as required. All the internal wirings shall be done
using 6.0 Sq.mm Single Core Flexible Copper conductor
cables.
400A TP MCCB WITH CONTACTOR
Supply and installation of 400A TP Microprocessor based
MCCB with 400A 4P Power Contactor (AC3) with all its
accessories in the existing MSB Panel Board complete with
connections using additional bus bars with sleeves, nut bolt
and spring washers etc. complete as required after the
dismantling of existing 200A TPN FN Isolator. The scope
also includes the complete control wiring to contactor so as
to ensure that the supply is ON when there is EB Supply only.
DISTRIBUTION BOARD
Supply and fixing of following ways surface / recess
mounting, vertical type, 415 V, TPN MCCB distribution
board of sheet steel, dust protected, duly powder coated,
inclusive of 200A tinned copper bus bar, common neutral
link, earth bar, din bar for mounting MCBs (But without
MCBs (But without MCBs and incomer) as required.
8 Way , Double Door
6 Way , Double Door
Supply and fixing of following ways surface / recess
mounting, vertical type, 415 V, TPN MCB distribution board
of sheet steel, dust protected, duly powder coated, inclusive
of 200A tinned copper bus bar, common neutral link,
earth bar, din bar for mounting MCBs (But without MCBs
and incomer) as required.
8 Way (8 + 24), Double Door
6 Way (8 + 18), Double Door
Supply and fixing of following way, horizontal type three
pole and neutral, sheet steel, MCB distribution board, 415V,
on surface/recess, complete with tinned copper bus bar,
neutral bus bar, earth bar, din bar, interconnections, powder
coated including earthing as required. (But without MCB/
RCCB/Isolator)
6 Way (8 + 18), Double Door
4 Way (8 + 12), Double Door
Supply and fixing of following way, single pole and neutral,
sheet steel, MCB distribution board, 240V, on surface /
recess, complete with tinned copper bus bar, neutral bus
bar, earth bar, din bar, interconnections, powder coated
including earthing etc. as required. (But without MCB/RCCB
/Isolator)
16 Way, Double Door
Supply and fixing following rating and breaking capacity and
pole MCCB with thermal magnetic release having 70 to 100%
setting provision and terminal spreaders in the distribution
board including making connections, etc. complete as
required.
100A 25kA 4P MCCB
Supply and fixing following rating, four pole, (three phase
and neutral), 415V, Residual Current Circuit Breaker
(RCCB), having a sensitivity current 30 mA in the existing
MCB DB complete with connections, testing and
commissioning etc. as required.
Supply and fixing following rating, double pole, (single
phase and neutral),240V, Residual Current Circuit Breaker
(RCCB), having a sensitivity current 30 mA in the existing
MCB DB complete with connections, testing and
commissioning etc. as required.
Supply and fixing 5A to 32A rating, 240/415V, 10kA, "C "
Curve, miniature circuit breaker suitable for inductive load
of following poles in the existing MCB DB complete with
connections, testing and commissioning etc as required.
Single Pole
Double Pole
Triple Pole
40A to 63A Triple Pole
MCB DUMMY
Supply and fixing single pole blanking plate in the existing
MCB DB complete etc. as required.
ISOLATOR
Supply and fixing following rating, four pole, 415V,
isolator in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
100A 4P Isolator
63A 4P Isolator
40A 4P Isolator
Supply and fixing following rating, double pole, 240V,
isolator in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
63A 2P Isolator
40A 2P Isolator
METAL ENCLOSURE
Supply and fixing Sheet Steel enclosure on surface / recess
having provision to fix MCB/Isolator complete with
connections, testing and commmissioning etc. as required.
JUNCTION BOXES
Supply, installation, testing and commisioning of IP65
thermoplastic fire retardant and weather proof junction boxes
with bakelite connectors and/or having provision for fixing 4
Pole MCBs/Isolators and glanding cables.
LT CABLES
Supply, laying, testing and commissioning of PVC 1.1 KV
grade XLPE insulated armoured Aluminium cables of the
following sizes and laying in earth excavated trenches,
clamping in built up trenches, trays, racks, risers, trusses,
walls etc using heavy duty Aluminium Flat or heavy duty GI
spacer saddles of which spacing of clamps not exceeding
40cm and pulling through pipes including all minor civil
works.
3.5C x 400 Sq.mm Al. cable
3.5C x 300 Sq.mm Al. cable
3.5C x 240 Sq.mm Al. cable
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 2.5sq.mm Copper Armoured cable
2C x 2.5sq.mm Copper Armoured cable
4C x 1.5sq.mm Copper Armoured cable
2C x 1.5sq.mm Copper Armoured cable
GLANDING AND TERMINATION
Supply and making end termination with brass compression
gland and alluminium lugs for following size of PVC
insulated and PVC sheathed/ XLPE Aluminium conductor
cable of 1.1 KV grade as required.
3.5C x 400 Sq.mm Al. cable
3.5C x 300 Sq.mm Al. cable
3.5C x 240 Sq.mm Al. cable
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 2.5sq.mm Copper Armoured cable
2C x 2.5sq.mm Copper Armoured cable
4C x 1.5sq.mm Copper Armoured cable
2C x 1.5sq.mm Copper Armoured cable
GLAND EARTHING
Supply and providing gland earthing using Aluminium or
Copper strip / shim / wire using copper sockets etc.
complete as required conforming to Electrical Inspectorate
Standards.
3.5C x 400 Sq.mm Al. cable
3.5C x 300 Sq.mm Al. cable
3.5C x 240 Sq.mm Al. cable
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
4C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
4C x 6 Sq.mm Al. cable
4C x 2.5sq.mm Copper Armoured cable
2C x 2.5sq.mm Copper Armoured cable
4C x 1.5sq.mm Copper Armoured cable
2C x 1.5sq.mm Copper Armoured cable
EARTHING
Supply and providing earthing with CI earth plate 1200mm x
1200mm x 12.6mm thick electrode including accessories,
and providing masonary enclosure with cover plate having
locking arrangement and watering pipe of 2.7 meter long
etc. with charcoal/coke and salt as required conforming to
relevant IS and Electrical Inspectorate standards etc.
Supply and providing earthing with CI earth plate 600mm x
600mm x 6mm thick electrode including accessories,
and providing masonary enclosure with cover plate having
locking arrangement and watering pipe of 2.7 meter long
etc. with charcoal/coke and salt as required conforming to
relevant IS and Electrical Inspectorate standards etc.
EARTHING CONDUCTORS
Supply and providing the earth conductors of the following
sizes and laying in earth excavated trenches, clamping in
built up trenches , walls, trays, racks, risers, trusses, etc
using heavy duty Aluminium Flat or heavy duty GI spacer
saddles of which spacing of clamps not exceeding 90cm
without making holes in the earthing conductor and pulling
through pipes including all minor civil works. All the joints
should be properly tinned and connections should only be
done using SS Nut and Bolts with double washers etc as
required.
25 x 6 mm Copper Strip
25 x 3 mm Copper Strip
8 SWG Copper Wire
10 SWG Copper Wire
MS STRUCTURALS
Supply, fabrication and installation of cable tray and supports
using M.S angles and plates of adequate size painted with
one coat of Zinc chromate primer and two coats of black
enamel paint.
Supply, fabrication and installation of Panel Board mounting
supports using C Channels of adequate size painted with two
two coat of Zinc chromate primer and two coats of black
enamel paint.
Supply, fabrication and installation of checkered plates of
6mm thickness to use above the cable trenches duly
supported with channels and duly painted with two coat of
Zinc chromate primer and two coats of black enamel paint.
and as required.
CABLE ROUTE MARKER
Supply and fixing cable route marker with 10 cm X 10 cm
X 5 mm thick G.I. plate with inscription there on, bolted /
welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long
with painting and fixing the same in ground at 5 meter
intervel with cement concrete in M.15 Grade (1:2:4) etc.
complete as required.
PIPES FOR CABLE PROTECTION
Supply and laying of the following size medium class GI
pipe in ground/wall/ceiling complete with fittings.
50mm dia
80mm dia
100mm dia
150mm dia
Supply and laying of the following size DWC HDPE pipe
ISI marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II complete
with fitting and cutting, jointing etc. in the existing trench,
complete as required.
63mm dia
90mm dia
120mm dia
160mm dia
200mm dia
DG EXHAUST PIPING
Supply and laying of 200mm dia exhaust line with flexible
including bends, flanges, nut, bolt, packing, necessary
supports etc. and painting the same using Heat resistant
Aluminum paints.
Supply and laying of 150mm dia exhaust line with flexible
including bends, flanges, nut, bolt, packing, necessary
supports etc. and painting the same using Heat resistant
Aluminum paints.
Providing thermal insulation of exhaust line glass wool with
Al. Sheet, chicken mesh, necessary supports and screws.
POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell
point with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable in surface / recessed medium
class PVC conduit, with modular switch, modular plate,
suitable GI box / surface box and earthing the point with
1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.
Group B
Wiring for twin control light point with 1.5 sq.mm FRLS
PVC insulated copper conductor single core cable in surface
/recessed medium class PVC conduit, 2 way modular
switch, modular plate, suitable GI box / PVC surface box
and earthing point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc. as required.
Wiring for group controlled (looped) light point / fan point /
exhaust fan point / call bell point (without independent
switch etc.) with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable in surface / recessed medium
PVC conduit, and earthing the point with 1.5 sq.mm FRLS
PVC insulated copper conductor single core cable etc. as
required.
Group B
Supply and fixing two module stepped type electronic fan
regulator on the existing modular plate switch box including
connections but excluding modular plate etc. as required.
Supply and fixing suitable size GI box /PVC surface box
with modular plate and cover in front on surface or in
recess including providing and fixing 3 pin 5/6 A modular
socket outlet and 5/6 A modular switch, connections etc. as
required.
Supply and fixing suitable size GI box /PVC surface box
with modular plate and cover in front on surface or in
recess including providing and fixing 2 Nos. 3 pin 5/6 A
modular socket outlet and 2 Nos of 5/6 A modular switch,
connections etc. as required. (For light plugs to be used in
non residential buildings).
Supply and fixing suitable size GI box / PVC surface
box with modular plate and cover in front on surface or in
recess, including providing and fixing 6 pin 5/6 & 15/16 A
modular socket outlet and 15/16 A modular switch,
connections etc. as required
Supply and fixing suitable size GI box / PVC surface
box with modular plate and cover in front on surface or in
recess, including providing and fixing 2 Nos of 6 pin 5/6 &
15/16 A modular socket outlet and 2 Nos of 15/16 A
modular switch, connections etc. as required
Supply and fixing following size/ modules, GI box / PVC
surface box along with modular base and cover plate for
modular switches in surface or in recess etc. as required.
1 or 2 Module
3 Module
4 Module
6 Module
8 Module
12 Module
Supply and fixing following modular switch/socket on the
existing modular plate and switch box including connections
etc. as required.
Telephone socket outlet
TV antenna socket outlet
Data socket outlet
Supply and fixing 3 pin, 5A ceiling rose on the existing
junction box/wooden block including connections etc. as
required
Supply and fixing modular blanking plate on the existing
modular plate & switch box excluding modular plate as
required.
CIRCUIT WIRING
Wiring for circuit / submain wiring along with earth wire
with the following sizes of FRLS PVC insulated copper
conductor, single core cable in surface / recessed medium
class PVC conduit as required.
2 x 1.5 sqmm + 1 x 1.5 sq.mm earth wire
2 x 2.5 sqmm + 1 x 2.5 sq.mm earth wire
2 x 4.0 sqmm + 1 x 4.0 sq.mm earth wire
4 x 4.0 sqmm + 2 x 4.0 sq.mm earth wire
4 x 6.0 sqmm + 2 x 6.0 sq.mm earth wire
4 x 10.0 sqmm + 2 x 6.0 sq.mm earth wire
TELEPHONE, DATA, CCTV & TV WIRING
Supply and drawing following pair 0.5mm dia FRLS PVC
insulated annealed copper conductor, unarmoured telephone
cable in the existing surface/recessed PVC conduit as
required.
Supply and drawing of UTP 4 pair CAT 6 LAN Cable in the
existing surafce/recessed PVC conduit as required.
1 run of cable
Supply and drawing co-axial TV cable RG-6 grade, 0.7mm
solid copper conductor PE insulated, shielded with fine
tinned copper braid and protected with PVC sheath in the
existing surface/recessed PVC conduit as required.
SUPPLY AND LAYING OF CONDUITS
Supply and fixing of following sizes of medium class PVC
conduit along with accessories in surface/recess including
cutting the wall and making good the same in case of
recessed conduit as required.
SUPPLY OF LIGHT & OTHER FITTINGS
Supply and providing the following fittings and items at site
Battern/Angle Holder
LED Bulb (up to 12W)
20W LED Tube Set
24W LED Tube Set
100W LED Flood Light
50W LED Flood Light
26W BLDC Ceiling Fan of Sweep 1200mm
High Speed Metal Type Exhaust Fan of Sweep 225mm
High Speed Shutter Type Exhaust Fan of Sweep 200mm
High Speed Shutter Type Exhaust Fan of Sweep 150mm
INSTALLATION OF LIGHT & OTHER FITTINGS
Installation, testing and commissioning of PVC battern /
angle holder fitting complete with all accessories directly on
ceiling/wall, including giving connections etc. as required.
Installation, testing and commissioning of pre-wired,
flourescent fitting/compact flourescent fitting of all types
complete with all accessories and tube/lamp etc. directly on
ceiling/wall, including connections with 1.5 sq.mm FRLS
PVC insulated, copper conductor, single core cable and
earthing etc. as required.
Installation, testing and commissioning of 100W LED Flood
light fittings complete with all accessories directly on wall/
piller/ceiling, including giving connections etc. as required.
Installation, testing and commissioning of 50W LED Flood
light fittings complete with all accessories directly on wall/
piller/ceiling, including giving connections etc. as required.
Installation, testing and commissioning of ceiling fan,
including wiring the down rods of standard length (up to
30cm) with 1.5 sq.mm FRLS PVC insulated, copper .
conductor, single core cable etc. as required
Installation of exhaust fan in the existing opening, including
making good the damage, connection, testing,
commissioning etc. as required.
up to 450mm sweep
HIGH MAST LIGHT
Supply Part
Supply of 12 Meter High Mast shaft in one section suitable
for 55 m/sec wind speed along with head frame, luminaires
carriage suitable for 6 luminaires in symmetrical arrangement
and other complete accessories manufactured in factory.
Supply of raising lowering system comprising double drum
winch, 5mm diameter SS wire rope, trailing cable, connector,
integral power tool motor, manual handle, junction box,
lightning finial rod.
Supply of foundation bolts manufactured from special steel
along with nuts, washers, anchor plate and common
template etc. complete as required.
Supply of 150W LED Flood Light
Supply of LED type single dome aviation obstruction light
Installation Part
Construction of shallow foundation with M20 grade concrete
for the highmast considering the safe soil bearing capacity at
site as 10 T/sqmtr at 2 metre depth with all materials and
labour.
Erection of the high mast with the help of suitable tools and
plants, wiring of luminaires with all wiring materials like PVC
insulated PVC sheathed flexible cable of suitable copper
conductor cores of 1.5 sq. mm, lugs, MCB and all labour.
CCTV CAMERA
Supply Part
Supply of the following IP Camera System with all necessary
accessories etc. complete as required and providing 2 Years
Complete Warranty and Service Support.
IR Night Vision Bullet Camera (8.0 Mega Pixel & 30 Meter)
Switch (8 Channel)
NVR (8 Channel )
Surveillance Hard Disk (4 TB )
LED Monitor (17.3)
SMPS 10A
White Surface Box (4'' x 4'')
NVR Wall Mount Rack (6U)
Installation Part
Installation of Camera System with all required accessoriesand labour.
ENERGY METER & CT
Supply and installation of the following Energy Meters and CTs after getting it tested from Electrical Inspectorate / KSEB / TMR. (All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents.).
Three Phase 4 Wire CL : 1 (Direct Operated)
Three Phase 4 Wire CL : 0.5S (CT Operated)
Single Phase 2 Wire CL : 1
100/5A CL : 0.5S, 5VA Resin Cast CT
150/5A CL : 0.5S, 5VA Resin Cast CT
200/5A CL : 0.5S, 5VA Resin Cast CT
SAFETY EQUIPMENTS
Supply and fixing MV danger notice plate of 200 mm x 150mm, made of mild stee,l at least 2mm thick and vitreous enameled white on both sides and with inscriptions in signal red colour on front side as required.
Supply and fixing 2Kg Dry Chemical Powder (DCP) type fire extinguisher complete with Gun Metal cap, hose with squeeze grip nozzle, wall fixing brackets conforming to BIS: 2171 and with ISI mark
Supply and fixing safety instruction chart in word duly framed in good frame work as required.
Supply and providing a set of 2 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red oxide paint and written with white paint "FIRE" and mounted on MS angle iron frame with bracket of appropriate size and capacity including filling sand etc.
Supply and providing First Aid Box as approved by St.John Ambulance Brigade / Indian Red Cross conforming to IS 2217 : 1963
Supply and fixing laminated shock treatment chart duly mounted on a good frame work
Supply and providing electrical grade rubber mat of size 2m x 1m having 12mm thickness in front of panels and DBs conforming to IS 15652 : 2006 standard.
Supply and providing electrical grade rubber mat of size 2m x 1m having 6mm thickness in front of panels and DBs conforming to IS 15652 : 2006 standard.
Supply and providing tested industrial safety helmet conforming to IS 2925 : 1984
NAMING FOR IDENTIFICATION
Painting letters or figures of 2.5cm/4.5cm sizes with enamel paint as identification mark to Panel boards, DBs etc as required.
EARTH EXCAVATION AND BACK FILLING
Excavation of all types of soils for the laying of XLPE
insulated power cable, GI / HDPE / RCC Pipes, Earthing
Copper conductors to the required width and depth up to
1.2m and back filling after providing sand cushioning and
protective covering by laying bricks breadth wise above the
cable. The supply of sand and bricks will come within this
scope. The trench dimensions and specifications shall be as
per the Electrical Inspectorate, KSEB & CPWD standards.
Excavation and Back Filling
Supply and laying of Bricks
Supply and filling of sand
DOCUMENTATION
Preparation of drawings and getting approval from Electrical Inspectorate. (*All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents).
Submission of completion report, arranging Inpsection andobtaining Sanction Order from Electrical Inspectorate .(All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents.).
Co-ordination with KSEB for getting additional power allocation by the submission of 7 sets of HT agreement and executing the agreement etc.(All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents.).
Supply, Installation, Testing and Commissioning of Passenger Lift of reputed make. (Make:Schindler Group,KONE or equalent )
EXCLUSIVE OF GST
Note :1 All materials, Items, Equipment shall be best branded items with IS and approved by client/KEL
2:Rate should be inclusive of installation, testing and commissioning cost for all items
3.Rate should be Exclusive of GST.
4.Work should be executed as per DSR/PWD/Irrigation Dept. specification and direction of Engineer at site.
8.ELECTRICAL: Note: Rate should be inclusive of preparation of schematic diagram and getting approval from KSEB/Electrical Inspectorate. Statutory fees paid to KSEB/EI shall be paid by us separately.
9.1 Make of Electrical equipments/materials
All electrical materials/equipments shall be of best branded items with ISI, strictly as per schedule specification
Panel Boards: CPRI certified reputed manufacturers make
MCB/ELCB/DB - L&T/LEGRAND/SCHNEIRDER or equivalent
Cables & wires - Finolex/KEI/POLYCAB/RPG/V-GUARD
Switches/Sockets/Regulators - SCHEIDER/ABB/HAVELS/LEGRAND or equivalent
Rigid PVCPipes/Casing & Capping - A-ONE/REPUTED MAKE with ISI , Precession, Balco, GEO
Cable Glands & Sockets - REPUTED MAKE , Cosmos
Indicating Lamps - TEKINIC/RISHUB/STC, L&T, Schneider or equivalent
Ceiling/Exhaust fan: Havells, Orient, Usha, Crompton Greaves, Bajaj
SAAJCONSTRUCTIONS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .