Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.6 LAccepted-AOC DOOR NO 7 2 30 3 OPP APSEB SUB STATION OLD GAJUWAKA MARRIPALEM VISAKHAPATNAM 530026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L1 | Accepted-AOC Lowest Bid Accepted | |
| 2 | L2₹33.9 L+₹2.2 L (7.06%)Rejected-Finance 7 32 1 PRASANTHI NAGAR GOPALAPATNAM VISAKHAPATNAM 530 027 | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | L2 | Rejected-Finance Not Being Lowest Bidder |
Tender Value
₹33.5 L
EMD Value
₹67,000
Closing Date
1 Jan 2024, 6:00 pmClosed
Col KK Srivastava, Commander Works Engineer
Commander Works Engineers, Visakhapatnam
PROVISION OF FIRE ALARM AND FIRE PROTECTION SYSTEMS IN BLDG Nos. 321 V FLT P-15, INAS 333 P-81, INAS 311 P-144, INAS 350 P-143 AT INS DEGA AND P-1 ADMIN BLDG AT RECEIVING STATION UNDER GE ND VISAKHAPATNAM
2023_MES_612530_2
82368/E8
Open Tender
Civil Works
Item Rate
120 days
Visakhapatnam
Class D
Category c vi
9 documents required · 9 mandatory
₹500
Garrison Engineer Naval Depot
₹67,000
Yes
20 Mar 2024
5 Dec 2023
3 Jan 2024
5 Dec 2023
1 Jan 2024
12 Dec 2023
Amount
Supplying, installing testing and commissioning of Addressable type Fire Alarm Panel complying BSEN-54 Parts 2 and 4, that supports phone number dialing using DTMF tones and meets the Ademco Contact ID Data format according to the SIA DC - 05 Standards, 1-4 Loop formats expandable upto 8-9 loops, Up to 1000 fire detection zones 200 per panel and Modules per each loop, complete all as specified and as directed and consisting of the following features:-
Notes: [a] The rate quoted shall also deemed to include for the following provisions also:- [i] Supply and installation of Batteries 12v 18/07Ah- 02 Nos [ii] Supply and installation of 24 volt Fault Torrent Network card with built in diagnostics and is fully monitored for both short and open circuit faults between nodes installed in fire alarm panel with maximum 200 Network nodes. [iii] Installation, commisioning and testing by OEM and submission of satisfactory test report on completion testing of whole system. [iv] The contractor shall provide proper Demo of the whole system on complete installation and shall provide 2 years Manufacturer/OEM warranty certificate for smooth functioning of complete system. Make: Apollo / Cooper / Notifier / Honeywell.
Supply, Installation, testing and commissioning of GSM communicator for converting the PSTN Ademco PSTN Contact ID codes of the fire alarm panels to readable SMS notifications and SIA - 09 IP over GPRS network to central monitoring station (CMS) and connecting to Fire detection and alarm system complete all as specified and as directed and consisting of the following features:-
[a] GSM Module with 4G GSM version of 2G QUAD BAND (850/900/1800/1900 MHz). [b] Direct mount Antenna with SMA Male L-Type Connector-CDMA and WCDMA, 2.5 dBi Gain and 850-2100/2400 MHz [c] IP communicator for fire alarm control panels, [d] Supports full transmission Contact ID over IP SIA-DC09 event information to security monitoring station. [e] 4/8 General alarm inputs including power supply voltage monitoring via SMS message, 800 remote control users via free short call [f] 800 users control by GSM call or using Maxim- Dallas i-Button keys, [g] Configuration using standard mini-USB cable. [h] Remote configuration and firmware upgrade, [j] Testing and diagnostic of the module via USB by using program SOFTWARE with features for troubleshooting and testing of the module via USB PC for saving time for installer and allow real time monitoring of module parameters, input/output and GSM modem status (IMEI, SIM registration) etc. [k] Shall Support up to 32 temperature sensors or 1 humidity/temperature sensor for automation purposes such as HVAC temperature control, alarm and control with extra sensor. (l)Free configuration and diagnostic software, [m] Free android APP and WEB cloud service with Software for Mobile/Tab's/PC's - 1 Set with each Panel [n] Central Alarm Monitoring at security through cloud-based software (With out end receiver) with PC/TAB/Mobile [Cost of PC/TAB/Mobile shall not be included in the rate quoted for this item].
Notes: [a] The rate quoted shall also deemed to include for the following provisions also:- [i] Installation, commisioning and testing by OEM and submission of satisfactory test report on completion testing of whole system. [ii] The contractor shall provide proper Demo of the whole system on complete installation and shall provide 2 years Manufacturer/OEM warranty certificate for smooth functioning of complete system. Make: Apollo / Cooper / Notifier / Honeywell.
Supplying, installating, testing and commissioning of All-in-one Desktop PC with Windows Operating System , Processor Brand Intel CPU, Monitor Resolution 1920 x1080, Hard Drive Type 16 GB RAM, Drive Capacity 1 TB Storage alongwith suitable capacity UPS at centralized locations including testing entire system with mock activation of FIRE ALARM CONDITIONS all as specified and as directed and with the following features:- [a] 13th Generation Intel® Core™ i5 processor [b] Windows 11 Home Single Language [c] 68.6 cm (27) diagonal FHD display, Antiglare IPS & IR Tiltable Camera Intel® UMA [d] 1 TB PCIe® NVMe™ M.2 SSD [e] 16 GB DDR4-3200 MHz RAM (2 x 8 GB) [f] Height Adjustable Stand Testing and commissioning: Entire system with mock activation of FIRE ALARM CONDITIONS. Make : DELL/HP/Lenovo. NOTE : 5 years on site replacement warranty for complete system and providing OEM warranty certificate and minimum 5 years SIM recharge for networking/communication & validity for complete system. Notes: The rate quoted shall also deemed to include for the following provisions also: [i] 5 years on site replacement warranty for complete system and providing OEM warranty certificate and minimum 5 years SIM recharge for networking/communication & validity for complete system.
[ii] Integration of the following Software with All-in-one Desk Top PC by downloading from GSM Moudule connector [a] Remote configuration and firmware upgradation, free configuration and diagnostic software including testing and diagnostic of the module via USB by using program software. Troubleshooting and testing of the module via USB PC; this saves time for installer and allows real time monitoring of module parameters, input/output and GSM modem status (IMEI, SIM, registration) etc. Virtually unlimited event log. [b] Customarising WEB APP software with edit facility and shall have a product support for 10 years. Data received by the central server is available now for monitoring through WEB APP software from anywhere in the yard. Wireless Data Module transmitter/communicator can be configured from the central control room PC through wireless WEB APP Software/ application. The parameters can be renamed according to their sensing application and name the second area as "Server Room" as it has been placed in the server room for fire alarm monitoring. Naming can be done from the WEB APP Software. The WEB APP software has other features also as you can edit the sampling rate of data received from the server, registration of modules, setting of SMS alerts and the table fields can be viewed/hided to make it more convenient for user to access panel remotely using APP, Sort Call, SMS.
Supplying, installing, testing and commissioning of Auto-Aligning Beam Detector with Laser Alignment alongwith transmitter and receiver to give smoke signal by using projected beam of light, provided as per area requirement including provision of Monitor Module for facilitating third party devices to interface with Addressable Panel including all accessories complete all as specified and as directed with following specifications:-. [a] Operating Distance 8-100m, [b] Supply Voltage 14-36 V DC, [c] Operating Current (1 Detector) 6mA (2 Detectors) 8.5mA Operating Current (Alignment mode with 1 37mA or 2 Detectors) [d] Response Threshold (Default 35%) 10-60% Delays (User settable, default 35%) [e] Alarm 2-30 Seconds Fault 2-30 Seconds Operating Distance 8-100m [f] Operating Temperature Minus 10 to Plus 55 Deg C [g] Storage Temperature Minus 40 to Plus 85 Deg C [h] Humidity (non condensing) 0-93% RH [j] IP Rating IP-54 [k] Contact Rating 100mA @ 36V DC Cable Length (System controller to Detector) 100m (2 Core) Optical Wave Length 850nm). Make:- Apollo / Cooper / Notifier / Honeywell.
Supplying, installing and testing of Multisensor Detector with self built intelligence Complying with and type certified to EN 54 and conforming to IS – 11360 comprising of optical smoke and thermistor temperature sensors to give both combined signal as well as a separate heat signal for improved false alongwith isolator modules as required, provided as per area requirement below or above the false ceiling complete all as specified and as directed and with following specifications:-
[a] Communications protocol: Honeywell/ Notifier/ Apollo/ Series 90/ XP95 5-9V peak to peak [b] Operating voltage: 17-28V DC [c] Quiescent current: 500μA peak [d] Power-up surge current: 1mA [e] Maximum power-up time: 10s [f] Alarm LED current: 3.5mA [g] Remote LED current: 4mA at 5V (measured across remote load) [h] Clean air analogue value: 23 +4/-0 [i] Alarm level analogue value: 55 [j] Alarm indicator: 2 colourless Light Emitting Diodes (LEDs); illuminated red in alarm Optional remote LED [k] Dimensions:100mm diameter 50mm height 58mm (height in base) [l] Weight: Detector: 105g Detector in base: 160g [m] Materials: Housing: White polycarbonate V-0 rated to UL94 [n] Terminals: Nickel plated stainless steel [n] Smoke element only: Chamber configuration: Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light [o] Sensor: Silicon PIN photo-diode Make: Apollo / Cooper / Notifier / Honeywell Note: The rate quoted shall also deemed to include for 5 years on site replacement warranty for complete system and providing OEM warranty certificate and minimum 5 years SIM recharge for networking/communication & validity for complete system.
Supplying, Installing, testing and Commissioning of Fire Alarm Open area Sounder/ Siren with Visual Indicator controlled by the full core Protocol duly programmed with the fire control panel, horizontal type, single stage, wall mounted, continous normal operation for minimum 50 minutes with sound level 65 DB to 120 DB measured at 1.5 metre with sound output variation of + 5 DB with 2000 mtrs range complete all as specified and directed.
Supplying, Installing, testing and Commissioning of Fire Alarm Open area Sounder/ Siren with Visual Indicator controlled by the full core Protocol duly programmed with the fire control panel, horizontal type, single stage, wall mounted, continous normal operation for minimum 50 minutes with sound level 65 DB to 120 DB measured at 1.5 metre with sound output variation of + 5 DB with 1000 mtrs range complete all as specified and directed.
Supplying, fixing and testing of Addressable dual action manual call point/ pull station, resettable type, having integrally mounted addressable module to monitor and report contact status complying with latest standards and is designed to interface with DIP switches of Metal body with anti-corrosive coated, with hex Key including all accessories complete all as specified and as directed.
Supplying, installing and testing of Addressable electronic loop sounder cum strobe with xenon flash tube duly integrated with In-built UL listed Isolator/ control Module with supervisory features and power supply inputs including all accessories, flush/ ceiling mounted type with box complete all as specified and as directed.
Supplying and fixing of stove enamelled rigid steel Conduit, 20 mm dia including all accessories, fixed to walls/ ceilings complete all as specified and as directed.
Supplying and fixing of Rigid non-metallic heavy duty PVC Conduit, 20 mm dia including all accessories, fixed to walls/ ceilings complete all as specified and as directed.
Supplying, laying, testing and commissioning of 2 Core x 1.50 Sq.mm, Flexible PVC insulated, pair twisted and screened, high conductivity electrolytic copper conductor cable , ISI marked, 1100 Volts, FRLS Grade, conforming to IS 1554 Part -1 & IS 5831, drawn through pipes / sleeving through pipe in duct including suitable size Double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. complete all as specified and as directed.
S & F Electronic wall mounted time delay Voltage stabilizer of 2 KVA Capacity, Automatic Operation, for input variation of 170 Volts to 250 Volts with stabilised voltage of 230 Volts with accuracy of ± 2.5% complete all as specified. Make: V Guard/ Servo/ Kee Line
M & L for Point Wiring complete with 1100 Volts, FRLS Grade, 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, conforming to IS - 694 drawn through and including heavy duty PVC Conduit, 20 mm dia including all accessories concealed in Walls / Roofs / Floors / Ceiling etc. or surface type / semi concealed type and Modular Type Pressed Metal Flush Box made out of 2mm thick MS Sheet of suitable size and including Modular type Base / Grid Frame & Cover Frame for housing Modular Type Switches, Sockets and Regulators etc. concealed in walls, including 1100 Volts, FRLS Grade, 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable as earth continuity conductor with colour coding and connecting to Earth Dolly for One 3 Pin Socket Outlet 6 Amps controlled by one switch on Independent Board including cutting chasing for concealed wiring as required and making good the disturbed surfaces all as per existing complete all as specified and as directed.
S & F Switch, Modular Type, One Module, Single Pole, One Way, 6 Amps, 230 Volts complete all as specified and as directed.
S & F Socket Outlet, 3 Pin, 6 Amps, Modular Type, Two Modules, 230 Volts, complete all as specified and as directed.
M & L for Sub main wiring with 2 runs of single core 4 Sq.mm Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLSH Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 25 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. or surface type / semi concealed type including One run of 4 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLSH Grade earth continuity conductor including making good disturbed surfaces complete all as specified and as directed. Note: 3 runs of 4 Sq.mm PVC insulated coper conductor cable & one run of 25 mm dia PVC Conduit will be measured as one unit
M & L for Sub main wiring with 2 runs of single core 1.5 Sq.mm Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLSH Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 20 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. or surface type / semi concealed type including One run of 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLSH Grade earth continuity conductor including making good disturbed surfaces complete all as specified and as directed. Note: 3 runs of 1.5 Sq.mm PVC insulated coper conductor cable & one run of 20 mm dia PVC Conduit will be measured as one unit
S & F MCB DB, SPN, 2 Way, 240 Volts, with DIN Channel, Single Door without bus bar flush mounted with wall including making good disturbed surfaces complete all as specified and as directed.
S & F MCB DB, SPN, 8 Way, 240 Volts, with DIN Channel, Double Door with 200 Amps rated bus bar suitable for mounting MCBs flush mounted with wall including making good disturbed surfaces complete all as specified and as directed.
S & F MCB, SPN, 6 to 32 Amps, 10 KA, 'C' Curve, AC, 230 Volts, 50 Hz complete all as specified and as directed.
S & F MCB, SP, 6 to 32 Amps, 10 KA, 'C' Curve, AC, 230 Volts, 50 Hz complete all as specified and as directed.
S & F RCBO, DP 30mA, 6-32 A , 415 Volt, complete all as specified and directed.
Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 4 mm GI Wire [Earth Lead] and GI pipe 15 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified and as directed.
MVV Prasad
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .