Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹1.0 Cr
EMD Value
₹2.0 L
Closing Date
19 Nov 2026, 3:00 pm7d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Facility Director
OFFICE OF Facility director, .NSB, BARCF, Kalpakkam
Supply Installation Testing and Commissioning of Air Cooled Packaged Air Conditioning Units Including Refrigerant Piping GI Ducting Electrical Works Insulation Air Distribution System and Associated Works at NDDP MPDD Kalpakkam
2026_BARC_932510_1
BARCF/MPDD/OM/TR/9/2026
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
90 days
KALPAKKAM
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹2.0 L
4 Nov 2026
4 Nov 2026
26 Nov 2026
5 Nov 2026
19 Nov 2026
10 Nov 2026
6 Nov 2026 - 9 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of air cooled microprocessor controlled Packaged Air conditioners 11.0 TR nominal capacity, 7480 m3/h (4400cfm) - 4 Nos (Working) & 2 Nos (Stand by)equipped with scroll hermetically sealed compressors, cross hatched copper tube lanced fins condenser, evaporator fan, thermostatic expansion valve DX-type evaporator, filter, temperature control, etc., as per the scope of work. | 6 | Nos. | - | - |
| 2 | Supply, installation, testing and commissioning of air cooled microprocessor controlled Packaged Air conditioners 16.5 TR nominal capacity, 11220 m3/h (6600cfm) - 4 Nos (Working) & 2 Nos (Stand by)equipped with scroll hermetically sealed compressors, cross hatched copper tube lanced fins condenser, evaporator fan, thermostatic expansion valve DX-type evaporator, filter, temperature control, etc., as per the scope of work. | 6 | Nos. | - | - |
| 3 | Supply and installation of complete Set of copper tubes of size OD 1 1/8" (28.58 mm) with wall thickness of 1.83 mm & OD 5/8" (15.88 mm) with wall thickness of 1.02 mm as per specification and scope of work. | 90 | RM | - | - |
| 4 | Supply and installation of complete Set of copper tubes of size OD 7/8" (22.22 mm) with wall thickness of 1.40 mm & OD 5/8" (15.88 mm) with wall thickness of 1.02 mm as per specification and scope of work. | 90 | RM | - | - |
| 5 | Supply and installation, 4C X 25 sq.mm 1.1kV grade Copper conductor PVC insulation flat wire armored PVC outer sheath cables as per the detailed specification. | 100 | RM | - | - |
| 6 | Supply and installation of 4C X 16 sq.mm 1.1kV grade Copper conductor PVC insulation flat wire armoured PVC outer sheath cables as per the detailed specification. | 100 | RM | - | - |
| 7 | Supply and installation of 3C X 2.5 sq.mm 1.1kV grade Copper conductor insulation round wire armoured PVC outer sheath cables as per the detailed specification. | 180 | RM | - | - |
| 8 | Supply and installation of 3C X 1.5 sq.mm 1.1kV grade Copper conductor insulation round wire armoured PVC outer sheath cables as per the detailed specification. | 180 | RM | - | - |
| 9 | End Termination of the 4C x 25 Sq.mm including cable gland ear thing Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. | 12 | Nos | - | - |
| 10 | End Termination of the 4C x 16 Sq.mm including cable gland earthing Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. | 12 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.38 MB
TENDER.pdf
Tender Documents • 2.19 MB
CPWDGCC14.pdf
Additional Documents • 1.46 MB
BOQ_979956.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .