Loading…
Loading…
Tender Value
₹43.4 L
EMD Value
₹86,800
Closing Date
31 Aug 2026, 3:00 pm7d left
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
MAINTENANC
12 conditions · 1 needing a document upload
The tenderer shall possess a valid Electrical Contractor License, issued by any State Government or Union Territory Administration, authorizing execution of electrical works up to 650 V. The contractor shall have in his employment or shall engage a person holding a valid certificate of competency issued by any State Government or Union Territory Administration for supervision of electrical works up to 650 V. Offers not accompanied by a valid Electrical Contractor License and requisite Supervisor competency for works up to 650V shall be summarily rejected.
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
47 conditions · 6 needing a document upload
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) /Limited Liability Partnership (LLP) etc. and corresponding documents shall be submitted by the tenderer as per the composition of the Firm.
The Bid Security shall be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure- VIA of GCC and shall be valid for a period of 90 days beyond the bid validity period. Non submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document within 5 working days of deadline of submission of bids.
Eligibility criteria :- Eligibility criteria shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self attested / digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document.
Tender Form (First sheet, Second sheet) of the GCC April 2022.
Certificate format (Affidavit) which available as Annexure - V in Mandatory documents. A facility has already created for online submission of Annexure V of GCC in IREPS module, uploading of physically signed Annexure V by tenderer has been discontinued.
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) /Limited Liability Partnership (LLP) etc.
The corresponding documents shall be submitted by the tenderer as per the composition of the Firm: Sole Proprietorship Firm: (i) All documents in terms of Para 10 of the Tender Form (Second Sheet) above. HUF: (i) A copy of a notarized affidavit on Stamp Paper declaring that he who is submitting the tender on behalf of HUF is in the position of 'Karta' of Hindu Undivided Family (HUF) and he has the authority, power and consent given by other members to act on behalf of HUF. (ii) All other documents in terms of Para10 of the Tender Form (Second Sheet) above. Partnership Firm: (i) All documents as mentioned in para18 of the Tender Form (Second Sheet). Company registered under Companies Act 2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above. LLP (Limited Liability Partnership): (i) A copy of LLP Agreement (ii) A copy of Certificate of Incorporation (iii) A copy of Power of Attorney/Authorization issued by the LLP in favour of the individual to sign the tender on behalf of the LLP and create liability against the LLP. (iv) An undertaking by all partners of the LLP that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP or JV in which they were / are partners/members. Concealment / wrong information in regard to above shall make the contract liable for determination under Clause 62 of the Standard General Conditions of Contract. (v) All other documents in terms of Para10 of the Tender Form (Second Sheet). Registered Society & Registered Trust: (i) A copy of Certificate of Registration (ii) A copy of Memorandum of Association of Society/Trust Deed (iii) A copy of Power of Attorney in favour of the individual to sign the tender documents and create liability against the Society/Trust. (iv) A copy of Rules & Regulations of the Society (v) All other documents in terms of Para 10 of the Tender Form (Second Sheet) above.
The tenderer shall be required to submit the Bid Security with the tender for the due performance with the stipulation to keep the offer open till such date as per Clause No.5 of PART -1 of the GCC, April 2022.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Guntakal Division -Guntakal: 1. Electrical Arrangements for Upgradation/Modification of Loco body washing Cum Rain water leakage testing plant as per RDSO Guidelines at Locomotive Shed, Guntakal and 2. Provision of Electrical Arrangements for the Upgradation of Infrastructure facilities for homing of electrical locomotives in existing link bay at Diesel Shed Guntakal.
GTL-EM-27-2026-27~SCOR
GTL-EM-27-2026-27
Open
Works - General
6 Months
Anantapur, Andhra Pradesh
₹0
₹86,800
7 Aug 2026
7 Aug 2026
17 Aug 2026
124 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 9,23,676.24 | ||
| — | Item Breakup for | details. | — | ||
| Supply , installation , testing and commissioning of ISI marked monoblock type, energy efficient EE4 3 HP pump, suitable to deliver water to 8-20 Mtr. head, at the rate of 4.5-13.4 LPS approx., 3ph motor, complete as per IS 9079:2002 with suction of 65mm and delivery of 50 mm with all connected accessories equivalent to model no: KDI-318 EE4 of kirloskar make or Equivalent Reputed Make. | — | — | — | 54,030 | |
| — | Item Breakup for | details. | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 50 sqmm XLPE insulated PVC sheathed Aluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necassary lugs and terminations. | — | — | — | 68,936 | |
| — | Item Breakup for | details. | — | ||
| Supply and Erection of HDPE pipe of 50 mm of PE-100, PN6 class as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 16,000 | |
| — | Item Breakup for | details. | — | ||
| Supply, laying and connecting of 25x3mm GI Flat with 40GSM Zink coated, conforming to IS:280-2006 or latest, it is to be laid & connected from equipment to earth electrode for continuity. | — | — | — | 1,650 | |
| — | Item Breakup for | details. | — | ||
| Supply and laying of 8 SWG GI wire with 40GSM Zink coated, conforming to IS:280- 2006 or latest, it is to be laid with armourd cable for earth continuity. | — | — | — | 2,400 | |
| — | Item Breakup for | details. | — | ||
| Excavation of cable trench in all types soil of size of size 400mm wide x 1 mtr. deep, and making good of the same to its original form and shape after complete including all connected materials and works up to the satisfaction of the Engineer at Site.The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 7,521 | |
| — | Item Breakup for | details. | — | ||
| Excavation of cable trench in cement concrete bed flooring by using power drill to a depth of 1.0 Mtr and a width of 0.3mtr. After laying the pipe and refilling the trench with excavated earth and undertaking cement concrete bed flooring to its original shape as was prevailing earlier to the satisfaction of Railways site Engineer and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013.The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 35,840 | |
| — | Item Breakup for | details. | — | ||
| Supply and Running of 25 mm dia, Ivory coloured PVC conduit (ISI marked) of wall thickness not less than 2 mm along with junction boxes, bends and all accessories etc. as required as per site requirement. Running of conduit, fixing with suitableclamps and nuts in groove / open /shelter. | — | — | — | 4,864 | |
| — | Item Breakup for | details. | — | ||
| Provision of concealed wiring with two runs of 1.5 Sq,mm 1100 Volts and one run of flexible copper conductor 1.5 Sq,mm 1100 Volts FRLS PVC insulated wires ISI marked (Phase, neutral and earth)( upto 10 meters lenght) in the PVC conduit pipe with 6A flush modular type switch including 2 way switches where ever required, ceiling rose, bulb holder and modular type plate cover to MS switch control box including all labour charges complete for light points, ceiling fans and exhaust fans points cat walk points and ioh service buidling points etc. accessories. | — | — | — | 20,163 | |
| — | Item Breakup for | details. | — | ||
| Supply and run of 2 nos, 2.5 sqmm, 1100 V PVC (FRLS) insulated flexible copper conductor wires and one run of 1.5 sqmm PVC (FRLS) insulated flexible copper cable for earthing in existing PVC conduit Pipe conforming to IS 694 (2010) with latest amendments. | — | — | — | 20,400 | |
| — | Item Breakup for | details. | — | ||
| Supply and run of 2 nos, 6.0 sqmm, 1100 V PVC (FRLS) insulated flexible copper conductor wires and one run of 2.5 sqmm PVC (FRLS) insulated flexible copper cable for earthing in existing PVC conduit/Casing and capping pipe. | — | — | — | 36,190 | |
| — | Item Breakup for | details. | — | ||
| Supply, Transportation, Erection & commissioning of 5mtr long hot dip galvanised Octagonal pole (IS 875) with 130mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet (S 355 JO steel plate for shaft), along with base plate IS 2062 of size 200x200x12mm, M16x600 long J type EN8 grade foundation bolts, 1000mm long single/ Double arm bracket Including the Supply of Suitable bolts with Bakelite Sheet with MCB ( for mounting inside the base compartment of pole ) including Erection & commissioning of 5 mtr. octagonal pole including RCC concrete foundation & plinth in hard soil including excavation of soil, tamping of concrete, grounting and supply of other required materials and accessories complete. | — | — | — | 1,83,736 | |
| — | Item Breakup for | details. | — | ||
| Service connection to the fitting from the junction box of 5 mtrs Octogonal pole by means of PVC insulated copper conductor of 3 core 1.5 Sq mm with necessary lugs at the juction box and necessary termination at the luminaire complete. | — | — | — | 3,650 | |
| — | Item Breakup for | details. | — | ||
| Supply and fixing of junction box suitable for street light poles model no.GSJB306-T of size 275mm X135mm X 110mm with 4 nos of connectors and suitable clamps for fixing , Fire retardant -Class FV-0 as per IS:11731 Part-II or V-0 as per UL-94. (fixing should be required as per instruction of site supervisor). Suitable clamps for fixing (MS Clamps 02 Sets for each Box with necessary bolts and nuts as per site condition for GI channels/poles as per the directions of Site engineer. | — | — | — | 8,500 | |
| — | Item Breakup for | details. | — | ||
| Supply and fixing of LED street light fittings of 70W with suitable driver with all connected materials as per attached railway specification. | — | — | — | 1,24,400 | |
| — | Item Breakup for | details. | — | ||
| Supply and Erection of 200W LED Flood light fitting as per attached railway specification. | — | — | — | 26,510 | |
| — | Item Breakup for | details. | — | ||
| Fabrication and erection of 14 SWG CRCA sheet steel enclosure of suitable size for outdoor LT feeder pillar with Double Door, including cutting, bending drilling, welding and reveting etc, complete with cleaning with 7 tank process and painting with EPOXY powder coating including cost and conveyance of all materials and labour charges. The MDBs shall be mounted on suitable required size of CC plinth (CC plinth cost will be paid separately) and secured with bolts, nuts and washers as advised by Engineer at site. The panel comprising of 200A tinned Copper Bus Bar(RYB & N of same size) required shape supported with appropriate DMC / SMC barriers and colour coded with heat shrinkable sleeves,LT 3 Phase Digital Multifunction energy meter with 3 lines LCD display for measuring all the parameters( Voltage/ Current/ Power/Frequency/power factor /kw/kwh/ kvar/kvarh) , Current T/Fs, indication lamps for incoming & outgoing feeders. suppot insulatorS, neutral links,Incoming & outgoing terminals,suitable cable termination glands , grommets, lugs, connecting wires and all other accessories suit with the following switchgear and accessories. The cables should be properly terminated in the switchgears with necessary lugs and all necessary accessories complete.The panel should comprise of the following Switchgear. Makes: ABB/Seimens/L&T/ Schneider /Legrand/Havells/Indo-Asian.(Drawing approval to be taken prior to supply) Supply and installation of DPX3 160 thermal magnetic based release ; Icu = 36K A; 100A 4 Pole MCCB conform to IEC 60947-2 of model no. 4200 95 of Legrand make with extended ROM , spreader links (2 sets), Make: Legrand,ABB,Siemens,Schneider,L&T(D-Shine). -2 no's Supply and instllation of DPX3 160 thermal magnetic based release ; Icu = 36kA; 63A 4 Pole MCCB conform to IEC 60947-2 of model no. 4200 93 of Legrand make or it's equivalent with extended ROM , spreader links (2 sets), Make: Legrand,ABB,Siemens,Schneider,L&T(D-Shine). Supply and erection of C curve DP MCBs of 32 /25/20A with all connected accessories. Makes: legrand/L&T/C&S /Siemens/Schnider/ABB/Havells-4 no's Supply and fixing of C curve FP MCBs of 32 A with all connected accessories .Makes: ABB/Schneider/L&T/Indo asin/C&S Makes -4 no's Supply and erection of LT 3 Phase Digital Multifunction energy meter with 3 lines LCD display for measuring all the parameters( Voltage/ Current/ Power/Frequency/power factor /kw/kwh/ kvar/kvarh) on existing box panel board including connections complete.-1 no's Supply and erection of LT current transformer with primary 100/5A to 1000/5A ratio in the existing panel including connections complete-4 no's | — | — | — | 1,00,108 | |
| — | Item Breakup for | details. | — | ||
| Cement concrete solid block masonry in foundation and plinth or wall with factory made blocks with cement concrete 1:3:6 with all labour complete.(The wall should be properly plastered as per the advise of site supervisor) | — | — | — | 1,34,810 | |
| — | Item Breakup for | details. | — | ||
| Supply and installation of 160 A 4P MCCB, 36 KA, Micro processor based adjustable with LSIG protection conform to IEC 60947-2 model no. 4205 37 of Legrand make or it's equivalent make with extended ROM , spreader links (2 sets). | — | — | — | 39,582 | |
| — | Item Breakup for | details. | — | ||
| Supply and fixing of SPN DB's,8 way 8 module confirming to IEC:61439 IP 43 with metal door model no.507611 of legrand make or its equivalent reputed make | — | — | — | 4,312 | |
| — | Item Breakup for | details. | — | ||
| Supply and Erection of B curve 16A DP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection ISI / CE Marked as per IS/IEC 60898 - 1 or its latest amendments Cat.Nos: 811050 with all connected accessories. | — | — | — | 1,325.2 | |
| — | Item Breakup for | details. | — | ||
| Supply and Erection of B curve 10A SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection ISI / CE Marked as per IS/IEC 60898 - 1 or its latest amendments Cat.Nos: 811010 with all connected accessories. | — | — | — | 1,840 | |
| — | Item Breakup for | details. | — | ||
| Supply and Erection of B curve 6A SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection ISI / CE Marked as per IS/IEC 60898 - 1 or its latest amendments Cat.Nos: 811010 with all connected accessories. | — | — | — | 1,840 | |
| — | Item Breakup for | details. | — | ||
| Excavation of earth for one pit in any soil and refilling as per RDSO Drg No.ETI/OHE/P/ 7021 (MOD.A) or if any latest. | — | — | — | 987.99 | |
| — | Item Breakup for | details. | — | ||
| Supply and erection of "Earth Electrode 3.1 mtrs length with 3.65 mmthickness including GI socket and nuts(3.1 mtrs ) as per the RDSO Drg No.ETI/OHE/P/ 7021 (MOD.A) or if any latest. | — | — | — | 3,375.32 | |
| — | Item Breakup for | details. | — | ||
| Drilling of holes as per the RDSO Drg No.ETI/OHE/P/ 7021 (MOD.A) or if any latest. | — | — | — | 484.5 | |
| — | Item Breakup for | details. | — | ||
| Supply and erection of Charcoal (Inspection by Consignee) | — | — | — | 1,509.3 | |
| — | Item Breakup for | details. | — | ||
| Supply and erection of Salt (Inspection by Consignee) | — | — | — | 1,043.7 | |
| — | Item Breakup for | details. | — | ||
| Provision of RCC earth pit hollow box of size300 mm x 300 mm x300mm with 50 mm wall thickness as per Drg.no. SDO/RDSO/E&B/001 by using M20 Grade precast RCC. It includes fixing of earth pits at various locations and RCC precast slabs with hook to cover Earth pits of dimensions as shown in IRSEM drg no 19-D6. (All the required men, material and transportation are to be arranged by contractor). Inspection by Consignee. | — | — | — | 2,609.58 | |
| — | Item Breakup for | details. | — | ||
| — | Item Breakup for | details. | — | ||
| Supply erection, testing and comissioning of Maintenance free earthing with all necessary accessories complete according to IS 3043-1987 and as per RDSO spec No:rdso/spec/ps/0109(rev.0)-2008 Amendment'1'. | — | — | — | 14,313 | |
| — | — | — | 34,15,507 | ||
| — | Item Breakup for | details. | — | ||
| Design, Fabrication, supply, fixing, connecting, testing and commissioning of 16 watts LED pit lights fitting, (10W+4 W+2 W) Aluminum die cast with IP67 Protection necessary hardware material suitable to work on 24 V DC/48V AC. 3 Dimentional type for pit llighting as per latest CEE Specification) Note Prior Approval to be taken including all accessories. Fixing, connecting, testing and commissioning of 16 W LED pit lighting (10W+4W+2W) with IP 67 protection necessary hardware material for pit lighting including all accessories. | — | — | — | 3,04,780 | |
| — | Item Breakup for | details. | — | ||
| Design, Supply, fixing connecting, testing and commissioning of Control Panel Unit containing 3 Nos. SMPS POWER SUPPLY UNITS enclosed in sheet steel enclosure with all connected safety accessories, Indications & Controls, dedicated for the High Power LED Based 16 W LED Pit/Catwalk Lights as per following Specification PANEL containing 3 nos of SMPS units, Each will be suitable for 7 Nos of Pit/Catwalk lights total 7x3=21 Nos of Pit/Walk lights) Specification for each SMPS Unit: Input Voltage: 180V to 260Volts, Output Voltage :24 Volts dc+/- 1% Regulation-C, Output Current: 10 Amps Each SMPS, Protection : Short Circuit Proof, Over Voltage Protection, Ripple:< 200mv including all accessories.Fixing, connecting, testing and commissioning of SMPS BASED Power supply units with all connected accessories including cable connectors etc. | — | — | — | 69,390 | |
| — | Item Breakup for | details. | — | ||
| Supply and fixing of Junction box similar to Cat. No. D9045 of M/s Hensel Make or Equivalent Reputed Make. Incl. fixing. | — | — | — | 24,500 | |
| — | Item Breakup for | details. | — | ||
| Supply and erection of CPVC pipe SDR-13.5 class-I pipe of size 32 mm (1 1/4 inch) as per IS 157778/8/2007 conduit pipe with all required accessories such as short/long bends, CPVC/PVC juction boxes including masonary work(chipping and making good) and labour charges etc. | — | — | — | 60,824 | |
| — | Item Breakup for | details. | — | ||
| Supply, erection testing and commissioning of welding terminal box (hinged type) made up of sheet steel of not less than 16 swg complete with 12 mm thick nylon sheet to fix terminals with terminal studs, bolts, nuts etc complete including mounting arrangements to the supporting structure/rail/pole/wall including all accessories wiht locking arrangements. | — | — | — | 12,860 | |
| — | Item Breakup for | details. | — | ||
| Design, fabrication, supply, fixing, testing, connecting and commissioning of suitable size of plastic box (FRP of minimum thickness of 3mm, with 12mm hylam sheet duly mounting with one no. of 125 Amps 415 volts 3P+N+E plug socket and 125Amps 4 pole MCCB complete with provision of cable for incoming and out going. The scope of work includes complete supply and fixing of suitable clamps, bolts, nuts, washers, lugs, cable glands and locking arrangements. The FRP box fixed on the columns/ walls with necessary clamps and rag bolts etc. NOTE: 1. All MCCBs fitted with Microprocessor based/electronic release based relays. 2. ICs =100% ICU. | — | — | — | 5,10,640 | |
| — | Item Breakup for | details. | — | ||
| Supply, Laying and Termination of 4 core 185 sqmm XLPE insulated underground armoured aluminium cable with heat resistant insulation as per IS 7098(Part 1)1988 or latest amendment with suitable lugs. | — | — | — | 3,30,762 | |
| — | Item Breakup for | details. | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
CEGE Technical Circular
ATTACHMENT
ListofLikelySuppliers.pdf
ATTACHMENT
GCC Apr 2022 with Correction slips
ATTACHMENT
JPO Digging of cables
ATTACHMENT
EarthingSpecificationMFEandOther.pdf
ATTACHMENT
Scopeofworkforwiring.pdf
ATTACHMENT
CEGETechnicalCircular07-04-2022_compressed.pdf
ATTACHMENT
GCC_April-2022WithCorrectionSlips._compressed.pdf
ATTACHMENT
RlyBd-JPO-DiggingofCables2013-Re-Circulatedin2022-LATEST.pdf
ATTACHMENT
RITESInspection.pdf
ATTACHMENT
Technicalspecifications--9-26.pdf
ATTACHMENT
MEDIUMVOLTAGELTPANELS.pdf
ATTACHMENT
NITIREPSWorks.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].