Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹6.4 LAccepted-AOC | 1 | Accepted-AOC ACCEPTED BEING L-1 | |
| 2 | 2₹7.4 L+₹86,532.50 (13.3%)Rejected-AOC | 2 | Rejected-AOC REJECTED NOT BEING L-1 | |
| 3 | 3₹7.7 L+₹1.2 L (18.6%)Rejected-AOC | 3 | Rejected-AOC REJECTED NOT BEING L-1 |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
5 Sept 2023, 6:00 pmClosed
CWE YOL
HQ CWE YOL
REPAIR/MAINT OF HT UNDER GROUND CABLES, GOD, 11KV HT OH LINES, 2 POLE/4 POLE STRUCTURE AND CONNECTED ITEMS AT VARIOUS SUBSTATIONS AT YOL CANTT
2023_MES_612584_1
CWE/Y-46/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
YOL
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE (KH) YOL
₹16,000
Yes
2 Nov 2023
7 Aug 2023
12 Sept 2023
7 Aug 2023
5 Sept 2023
22 Aug 2023
Amount
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out in any type of soil, complete all as specified and directed.
All as per Srl Item No 1.00 above but depth exceeding 1.5 mtr and not exceeding 3.0 mtr.
Returning filling in (soil) including spreading, levelling, watering and well ramming in layers n.exc 25cms thick in any type of soil complete all as specified and directed.
Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed.
PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.
PCC 1:4:8 (nominal mix) type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.
Plain cement concrete 1:2:4 ( nominal mix ) type B-1 (using 20 mm graded crushed stone aggregates) as in in lintels upto 1.5m clear span, cills, steps; seismic and other similar ands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs , water troughs and the like including weathering, slightly rounded or chamfered angles and throating, including necessary formwork where required complete all as specified and directed.
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cms thick, complete all as specified and directed Note: Punned thickness shall be measured.
Sub class ‘B brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick including taking out old bricks, complete all as specified and directed.
Laying only retrived bricks as cable protection cover, laid dry, flat, transversally along the length of cable, on sand cushioning, with width equal to the length of the brick, complete all as specified and directed.
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 80mm size fixed with MS clamps, nuts and bolts as required including cutting of road or hardstanding by manual complete all as specified and directed.
Supply, jointing, fixing or passing through pipe, trenches or ducts, commissioning and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95Sqmm, 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part-2 for insulation and for conductors Class 2 to IS 8130-84, in trenches, floors, ducts passing through pipe for road crossing etc,including connecting & testing and disconnecting and taking down of old unserviceable HT cable complete all as specified and directed. (Note : Excavation, earth work, brick protection, sand cushioning and GI pipe etc shall be measured &paid for separately).
Material and labour for detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. faulty cable will be trace out by the agencies by meggering HT cable.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm with suitable clamps made out of flat iron 50X6mm including nuts, bolts and washers, complete all as specified.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm, complete all as specified.
Renewal of pin type insulator porcelain, vitreous, white/brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm dia and 150mm height for working pressure 11000 volts grade includng taking down existing insulators and removing from site, complete all as specified.
Supply, installation, testing and commissioning gang operated air break off load connecting switch HT, 11KV, tripple pole, each plate consisting galvanised steel base, verticle type mounted on 15 No's post insulators and steel frame, non ferrous knife and spring loaded contacts, arcing horns complete with dropout fuse element assembly, operating rod of GI pipe, medium grade, 20 mm dia (without joint) of suitable size and locking arrangement, connections, mild steel frame with PG clamps and sleeves etc required for current rating 200 amps capacity including taking down unservicable GOD of any type, shape & size with steel frame and removing from site all as specified and directed.
Steel tubular swaged poles complete with base plate 8mm thick welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-55 (11m long) including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC benching including numbering with black paint and painting with bituminous paint internally complete and externally for portion embedded in PCC including dismantling of old type of poles any length, complete all as specified and directed. Note:- Earth work & excavation and PCC shall be measured and paid under respective Items of BOQ.
Structural steel work as in cross arms, bracings, supports, clamp and back plate fabricated from steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed by Engineer-in-Charge and applying two coats of aluminium paint over one coat of red oxide zinc chrome primer including preparation of surfaces and dismantling old structural steel work in cross arms and stacking at site, complete all as specified & directed.
Renewal of disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, 'Two-in-series' assembly for tension with tension clamps for conductors working pressure 11000 Volts complete all as specified and directed.
Trimming up of tree branches upto 3 mtr all around HT overhead lines, removing cut branches from site as directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 3 mtr all around the line. Necessary permission will be obtained from department by contractor one day prior to trimming in particular area and shut down of that area will be arranged by department. (ii) Total length of line from supply point to load end will be measured for the purpose of payment, irrespective of the No of trees required to be trimed.
Cleaning of installation area from inside and outside by removing the vegetation, cleaning the fungus formation and nearby growth of wild vegetation, bushes to a distance of 50 metres complete all as specified and directed.
Painting to four pole structure made out of steel tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps, XPM jalli etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (Total 5 Nos) with white and green paint alternalely on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified & directed.
Painting to two pole structure made out of steel tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps, XPM jalli etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (Total 5 Nos) with white and green paint alternalely on external surfaceabove PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified & directed.
Jumper for LT/HT OH Lines with insulated color coding (Red, Green, Blue) with all connected items i.e. nuts, bolts, clamps etc upto length 3 to 5 Metre, fixed in poistion, complete all as specified.
Cutting of road for laying of cable through pipe and making good the disturbed surface by using cement concrete 1:2:4 type B-0, using 12.50graded crushed stone aggregate as required complete all as directed.
Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, n exc 5cm long, diameter of neck 11 to 15mm, complete all as specified and directed by Engr-in-Charge.
Fuse wire suitable for HT line of capacity 5,10, 20, 40 & Amps, complete all as specified.
Unbinding from insulators ACSR conductor any size of HT over head line for repairs, restretching of ACSR conductor to achieve proper sag and rewinding to the insulators using aluminium/ GI wire all as required at site or directed.
Loose filling with broken/crushed stone aggregate of size 20mm, complete all as specified.
Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of plate not less than 1.5 metre below ground level, connecting to galvanised iron wire 4.0mm dia (as earth lead wire), by means of bolt, nuts, check nuts and washer of galvanised and earth wire protected by provision of galvanised iron pipe light grade, 15mm bore including provn of concrete pit in PCC (1:2:4), type B-I using 20mm graded crushed stone aggregates with 40mm thick precast cover of size 550 mm X 550 mm X 75 mm of RCC (1:2:4), type B-I, reinforced with XPM (weight not less than 4 kg/ Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made to shape, galvanised iron medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and including earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified and testing on completion.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of plate not less than 1.5 metre below ground level, connecting to galvanised iron strip 32X6 mm size (as earth lead strip), by means of bolt, nuts, check nuts and washer of galvanised and earth wire protected by provision of galvanised iron pipe light grade, 40 mm bore including provn of concrete pit in plain cement concrete M-15 type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of rainforced cement concrete M-15 reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made to shape, galvanised iron medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and including earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified and testing on completion.
Deduct Credit Amount as per Schedule of credit as details given on Srl Page No 22 of tender doucments.
surinder kumar jindal & bros.
M/S MALHI CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .