Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.7 LAccepted-AOC BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹8.8 L+₹11,981 (1.37%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance Higher bid | |
| 3 | L3₹10.0 L+₹1.3 L (14.5%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L3 | Rejected-Finance Higher bid | |
| 4 | Rejected-Technical 2 MIRZA MAHEDI LANE 25 RAFI AHMED KIDWAI ROAD KOLKATA 700016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | - | Rejected-Technical Documents are not in order | |
| 5 | Rejected-Technical | - | Rejected-Technical Documents are not in order |
Tender Value
₹10.9 L
EMD Value
₹21,715
Closing Date
7 May 2022, 1:00 pmClosed
EE, South 24 Pgs Elect Divn
57/2 D H Road
Urgent Fire detective work at Diamond Harbour Govt. Medical college and Hospital, Diamond Harbour South 24pgs.
2022_WBPWD_376260_1
WBPWD/EE/S24PED/eNIT03/22-23
Open Tender
FIRE FIGHTING ORG
Item Rate
30 days
Diamond Harbour
Please refer Tender documents.
4 documents required · 4 mandatory
₹21,715
South 24 Pgs Elect Divn
26 Aug 2022
12 Apr 2022
10 May 2022
12 Apr 2022
7 May 2022
22 Apr 2022
21 Apr 2022
Amount
Additional Infrastructure at Old Hospital Building : Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent Optical-Thermal Multi-criteria Detector (UL/ULC approved). (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Edwards) [Deatiled specification given in Annexure-A]
Supply, installation, testing & commissioning of addressable Manual call point (UL/ULC approved). (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Edwards) [Deatiled specification given in Annexure-A]
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex / Havells / RR Kabel / Polycab) with 20mm NB PVC 'FR' rigid conduit pipe (Red Colour) on the surface of the wall. (Make : Polycab/Presto/Precision-Medium). [Deatiled specification given in Annexure-A]
Commsioning Charges for new dectector to existing Panel Both addressable And non Conventional panel
New Infrastructure at Covid Hospital Buildig : SITC of Microprocessor based addressable fully networkable fire alarm control panel (VDS / UL-FM approved) suitable for the devices as stated in thefollowing items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.Thc panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved make : Honeywell / Siemens / Edward / Bosch / Jhonson Control / Securiton / Secutron). [Deatiled specification given in Annexure-A]
SITC of of Micropresssor controlled IP Addressable Intelligent Optical-Thermal Multi-criteria Detector (VDS/UL-FM approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring, complete with base. (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Honeywell / Siemens / Edward / Bosch / Jhonson Control / Securiton / Secutron). [Deatiled specification given in Annexure-A]
SITC of IP Addressable Manual call point (VDS/UL-FM approved) with in built short circuit fault isolator as per NFPA style 7 wiring. (Numbers of addressable devices in a group will be as per latest recommended. (Approved make : Honeywell / Siemens / Edward / Bosch / Jhonson Control / Securiton / Secutron). [Deatiled specification given in Annexure-A]
SITC of Addressable Hooter-cum-Strobe (VDS/UL-FM approved) (sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Honeywell / Siemens / Edward / Bosch / Jhonson Control / Securiton / Secutron). [Deatiled specification given in Annexure-A]
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex / Havells / RR Kabel / Polycab) with 20mm NB PVC 'FR' rigid conduit pipe (Red Colour) on the surface of the wall. (Make : Polycab/Presto/Precision-Medium). [Deatiled specification given in Annexure-A]
Supply & Fixing 240 V, 4 nos. 6A, plug socket with separate 4 nos. 6 A Piano key type switch, indicator & 16A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required, as per GS.
NOTE : 1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. 3. As built drawing shall be submitted in Both soft (CAD) & hard copy format..Drawing shall be approved by the Engineer in charge before the commence of the work. 4. Necessary Certificate from the Competent Authority / Statutory body should be obtained by the executing agency if asked by EIC 5. The work shall be completed in all respect and shall be free from all kinds of defects/deficiencies/damages in equipment, materials, components and other auxiliaries and workmanship from any cause whatsoever for a period of five years warrenty or, total replacement in case of major defects or fault for both the FACP and the battery as appicable. 6. Test Certificates of individual components may be produced if asked by EIC. 7. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered. 8. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. 9. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. 10. If any discrepancy arises between two similar clauses, the clause as stated later, will supersede former one in following sequence: i) Form 2911 ii) eNIT iii) Annexure-A iv) BOQ
11. All the rates should be quoted inclusive of all taxes & duties, District Charge and LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 5 (five) years from the date of commissioning.
PERFECT IMAGE SOLUTIONS
GLYPTIC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .