Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 19 PAOTA C ROAD JODHPUR | JODHPUR | RAJASTHAN | 342001 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹7.4 L
EMD Value
₹14,800
Closing Date
18 Jul 2022, 6:00 pmClosed
AGE (I) R AND D JODHPUR
AGE (I) R AND D JODHPUR, Defence Laboratory, Ratanada Palace, Jodhpur - 342 011 (Raj)
REPAIR AND MAINT OF PUMPSETS, FIRE HYDRANTS AND ELECTRIC PANELS RELATED WORKS AT DEFENCE LAB JODHPUR
2022_MES_533450_1
8487/E8
Open Tender
Civil Works
Item Rate
180 days
AGE (I) R AND D JODHPUR
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
AGE (I) R AND D JODHPUR
₹14,800
Yes
28 Jul 2022
24 Jun 2022
20 Jul 2022
24 Jun 2022
18 Jul 2022
4 Jul 2022
25 Jun 2022 - 2 Jul 2022
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables or laying of pipe,errection of poles, struts / stays etc including taking out cable cover or stone slab, not exceeding 10 sqm on plan and getting out in soft/loose soil complete all as specified and directed by Engineer-in-charge.
Taking down old / unserviceable under ground LT cable of any cross-sectional area from trenches/walls / poles after disconnecting connections complete all as specified and directed by Engineer-in-charge.
Supply, laying,jointing,connecting and testing and fixing or passing through pipe or laid in trenches, 1100 Volt grade heavy duty cable XLPE insulated, armoured electric cable with aluminium conductor ,cross-sectional area 70 sq.mm 3.5 core complete all as specified and directed by Engineer-in-charge.
M&L sand cushioning to undergound cable with using tibba sand and gently punning for cushioning to cable complete all as specified and directed by Engineer-in-charge. Note: For the purpose of payment only punned thickness will be measured.
Supply & laying 40 to 50 mm thick roughly hammer dressed Jodhpur stone patti cable cover 25 to 30cm wide and n. exc 60cm long each laid dry abutting with each other with maximum gap between adjacent slabs n.ex 10 mm complete all as specified & directed by Engineer-in-charge.
Material and Labour for Cutting/ Chassing or Boring as required in hard standing/PCC / Road exceeding 10 Cm girth for concealed to GI tubing and making good to disturbed surface with cement mortar 1:3 to match with existing surfaces including facing/finishing where as required or as directed by Engineer-in-charge
Supply & laying steel Tubing galvanized medium grade (ISI Marked) 80 mm bore with all fittings ISI marked laid in trenches complete all as specified and directed by Engineer-in-charge.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and directed by Engineer-in-charge.
Removing excavated any type of soil to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-charge.
S&F bus bar chamber of size 900x600x600mm suitable of 3 phase 433V outdoor type fabricated out of 3.15mm thick MS sheet with 200A rated aluminium busbar 4Nos., PVC sleeves (coloured red, yellow, blue and black) with suitable locking arrangments and four legged angle iron stand made of angle iron of size 40x40x6mm duly grouted in and including foundation in PCC 1:2:4 type C1 using 20mm graded stone aggregates alongwith all necesary cable connections, lugs and cable glands including applying two coats of synthetic enamel paint (of approved tint) over a coat of red oxide zinc chrom primer complete all as specified and as directed by engineer-in-charge.
M&L for cable jointing kit for 1.1kV earthed grade cable for straight through heat shrink type joint indoor / outdoor with jointing material and accessories suitable for 3.5 core, 70 to 150 mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and directed by engineer-in-charge.
Taking down old unserviceable MCCB's and MCB's of any type and size complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic release, 400 Amps, 36 KA, 4 pole,415 volts, complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic release protection type 250 Amps, 36 KA, 4 pole,415 volts, complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic proctection type 415 volts,200 Amps, 25 KA, 3 pole complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic proctection type 415 volts, 125 Amps, 25 KA, 3 pole complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic proctection type 415 volts, 125 Amps, 25 KA, 4 pole complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic proctection type 415 volts, 100 Amps, 25 KA, 3 pole complete all as specified and directed by Engineer-in-charge.
Supply & Fixing MCCB Thermal magnetic proctection type 415 volts, 63 Amps, 16 KA, 3 pole complete all as specified and directed by Engineer-in-charge.
Supply and fixing Contactor, 3 phase, 415 volt, suitable for 60 HP motor star delta starter with all necessary connection including taking down old un-serviceable contractor complete all as specified and directed by Engineer-in-charge.
Supply and fixing Contactor, 3 phase, 415 volt, suitable for 20 HP motor star delta starter with all necessary connection including taking down old un-serviceable contractor complete all as specified and directed by Engineer-in-charge.
Supply and fixing Contactor, 3 phase, 415 volt, suitable for 10 HP motor star delta starter with all necessary connection including taking down old un-serviceable contractor complete all as specified and directed by Engineer-in-charge.
Disconnecting and taking out centrifugal pump with motor of capacity 60 HP of any make and model from the foundation & dismantling for overhauling and repair by replacing the pump bearing, bush, gland bush, coupling and impeller,etc re-assembling after replacement of unserviceable parts, connecting with the suction/discharge line with correct alignment and making the electric connection including testing complete all as specified and directed by Engineer-in-charge. Note: (i) Pump bearing, bush, gland bush, coupling and impeller etc will be measured and paid separately as supply only under respective items of this schedule.
Disconnecting and taking out Centrifugal /Monoblock pump with motor of capacity 20 HP. of any make and model from the foundation & dismantling for overhauling and repair by replacing the pump bearing, bush, gland bush, coupling and impeller,pumpshaft etc re-assembling after replacement of unserviceable parts, connecting with the suction/discharge line with correct alignment and making the electric connection including testing complete all as specified and directed by Engineer-in-charge. Note: (i) Pump bearing, bush, gland bush, coupling and impeller etc will be measured and paid separately as supply only under respective items of this schedule.
Disconnecting and taking out Monoblock pump with motor of capacity 10 HP. of any make and model from the foundation & dismantling for overhauling and repair by replacing the pump bearing, bush, gland bush, coupling and impeller,pumpshaft etc re-assembling after replacement of unserviceable parts, connecting with the suction/discharge line with correct alignment and making the electric connection including testing complete all as specified and directed by Engineer-in-charge. Note: (i) Pump bearing, bush, gland bush, coupling and impeller etc will be measured and paid separately as supply only under respective items of this schedule.
Material & Labour for rewinding the armature housing of pump motor dismantled with super enameled copper winding wire of appropriate gauge of thermal class “E” insulation complete all as specified and directed by Eng-In-Chrage
Supply only CI Impeller suitable for 60 HP Centrifugal pump set. complete all as specified and directed by Engineer-in-charge.
Supply only CI Impeller suitable for 20 HP Centrifugal/Monoblock pump set. complete all as specified and directed by Engineer-in-charge.
Supply only CI Impeller suitable for 10 HP Monoblock pump set complete all as specified and directed by Engineer-in-charge.
Supply only ball bearing suitable for 60 HP Centrifugal pump set complete all as specified and directed by Engineer-in-charge.
Supply only ball bearing suitable for 20 HP Centrifugal/monoblock pump set complete all as specified and directed by Engineer-in-charge.
Supply only ball bearing suitable for 10 HP Monoblock pump set complete all as specified and directed by Engineer-in-charge.
Supply only gland bush suitable for Centrifugal pump set of capacity 60 HP complete all as specified and directed by Engineer-in-charge.
Supply only gland bush suitable for Centrifugal/Monoblock pump set of capacity 20 HP complete all as specified and directed by Engineer-in-charge.
Supply only gland bush suitable for Monoblock pump set of capacity 10 HP complete all as specified and directed by Engineer-in-charge.
Supply only MS coupling with rubber seal suitable for 60 HP Centrifugal pump set with electic motor. complete all as specified and directed by Engineer-in-charge.
Supply only MS coupling with rubber seal suitable for 20 HP Centrifugal pump set with electric motor. complete all as specified and directed by Engineer-in-charge.
Disconnecting and taking out pump with motor of capacity 03 HP. of any make and model from the foundation & dismantling for overhauling and repair by replacing rewinding ,the pump bearing, bush, gland bush, coupling and impeller,pumpshaft etc re-assembling after replacement of unserviceable parts, connecting with the suction/discharge line with correct alignment and making the electric connection including testing complete all as specified and directed by Engineer-in-charge. Note:The cost of rewinding, Pump bearing, bush, gland bush, coupling and impeller are included in this item.No seprate payement shall be made for supplying these items.
Material & Labour for renewal of earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground level, connected to Galvanised earth lead wire of 4mm dia by means of bolts nuts check nuts and washers of galvanized iron or steel all as shown in the electrical plate No. 3 of MES SSR part –I connected to all earth test point all as specified and testing on completion including provision of earth lead protected by 15 mm bore light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation, earth work in any type of starta, PCC pit with RCC pit with M 25 (Design mix) cover,char coal,salt,funnel etccomplete. Note:-Rate quoted by the tenderers shall be deemed to include for following provisions:-(i) Excavation & eart work in any type of starta including removing of surplus material upto 100M (ii)PCC (1:3:6) type C1 using 20mm graded stone aggergate in pit& 40 mm thick precast RCC,M-25 design mix concrete cover 50x50 cm with 8mm round bar@15 cm C/C both ways.(iii) Main earth wire 4mm dia from earth eletrode to test point upto 7.5 mtr.(iv)Funnel with watering pipe(GI pipe) 20mm bore(ISI marked)medium grade & copper lugs and charcoal & salt as reqd.(v) GI protection pipe of size 15 mm bore light grade upto 7.5m. .
M&L for preparation of old painted steel surface of centrifugal pump set of 60 HP capacity by scraping ,rubbing and removing of dirt/dust oil spot and making surface smooth ready for painting and applying one coat synthetic enameled paint complete all as specified and directed by Engineer-in-charge.
Material & Labour for preparation of old painted steel surface of monoblock/Centrifugal pump set of capacity upto 20 HP by scraping ,rubbing and removing of dirt/dust oil spot and making surface smooth ready for painting and applying one coat synthetic enameled paint complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement Star Delta starter complete unit suitable for 10 HP motor including single phase preventer and connected accessaries complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement Star Delta starter complete unit suitable for 20 HP motor including single phase preventer and connected accessaries complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement Star Delta starter complete unit suitable for 60 HP motor including single phase preventer and connected accessaries complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement DOL starter complete unit suitable for 3 HP motor including single phase preventer and connected accessaries complete all as specified and directed by Engineer-in-charge.
Material and labour for Removal / Taking up of submersible pump of any capacity by disconnecting electric cable and delivery pipes etc and lowering pump along with pipe and cable on completion of repairs including connecting and testing etc complete all as specified and directed by Engineer-in-Charge
Material and labour for Repair of submerssible pump/motor 03 HP, 230/415 volts by transporting to civil work shop, opening, taking out old burnt out winding, preparing for re -winding with PVC insulated copper winding of suitable gauge including all materials as required, re-assembling, testing at work shop, transporting back to site and connecting with pipe & electric supply after the pump is lowered and testing the pump for smooth functioning etc complete all as specified and directed by Engineer-in-Charge
Material & Labour for Cleaning of underground /semi underground RCC reservoir of capacity 1,00,000 gallon at main pump house by draining out storage water completely with mud pump or throwing out manually with buckets and cleaning of inner surface of bottom and walls of tank by removing complete accumulated sludge/mud, dirt etc including removing of roots, bushes etc with wire brush and finally washing with fresh water and disinfecting the reservoir with 2% solution of Potassium permanganate including writing date of cleaning with white synthetic enamel paint and removing sludge, scale, mud etc to a distance not exceeding 50 meter and depositing complete all as specified and directed by the Engineer-in -Charge
All as per item No. 48 above but overhead reservoir of capacity 40,000 gallon at 18 meter staging at main pump house complete all as specified and directed by the Engineer-in -Charge.
All as per item No. 48 above but capacity 25,000 gallon at main pump house and fire fighting pump house complete all as specified and directed by Engineer-in-charge.
All as per item no. 48 above but capacity 20000 gallon at Training institute complete all as specified and directed by Engineer-in-charge.
All as per item no. 48 above but capacity 5,000 gallon at Transit facility complete all as specified and directed by Engineer-in-charge.
Taking up or down old unserviceable sluice valves and Supply & Fixing 80 mm bore sluice valve long body, PN 1.6 with brass spindle both end flanged ISI marked complete with CI wheel nut bolt washer and rubber packing conforming to IS 14846-2000, complete all as specified and directed by Engineer-in-charge.
Taking up or down oldd unserviceable sluice valves and Supply & Fixing 150 mm bore sluice valve long body, PN 1.6 with brass spindle both end flanged ISI marked complete with CI wheel nut bolt washer and rubber packing conforming to IS 14846-2000, complete all as specified and directed by Engineer-in-charge.
Taking up or down old unservicable oblique type gun metal landing valve and Supply and Fixing oblique type gun metal landing valve single headed of size 63mm, inlet 3' NB flanded, outlet- female instantaneous with grey cast iron handle wheel with fixing arrangement viz- GI flange 100 mm/GI flange 80mm, GI bend 80/100 mm, GI nipple 100 mm/GI nipple 80 mm complete all as specified and directed by Engineer-in-charge.
Supply and Fixing in replacement Aqua Dura Reinforced rubber lined hose with Elastomeric coating conforming to IS : 636/19088 Type-A with gun metal end connection on both ends of 30 mtr length including taking down old unsv hose complete all as specified and directed by Engineer-in-charge.
Supply and Fixing Gun metal short branch pipe 63 mm instantaneous inlet, made threaded outlet, 15mm bore nozzle long including taking down old unserviceable gun metal short brnach complete all as specified and directed by Engr in Charge.
Supply & Fixing Aviation obstruction light , LED Base cat part NO. AOL/DE-48, 2 x 24 watt LED double emitter type on over head tank of 18 mtr staging complete all as specified and directed by Engineer-in-charge. Make : Kalin or equivalent
Supply, installation and testing complete of Digital water level indicator with sensors, Aux supply 230 Volts, Type DDS-2, capacity 7 meters operating on single phase supply direct display in 19 mm size digit system in meter of water Overhead tank 18 mtr staging ensuring alarm while water fall or rise over predetrmined limit with the following description. make:- Seco type DDS-2 . (a) The entire unit must operate through compact electronic circuit, which must ensure reliable opration at 230 V +/ - 10% at 50 Hz + / - 5% with reliable in digit display and alarm at low and high level of semi UG sump. (b) One circuit must be housed in high impact polystrene molded box with nylon molded connection strips. The level system must resistance transducer, while unaffected by corrosion and other contamination available in water. The product must be controlled by micro switch. (c) The whole unit must be electronically controlled and the upper level and lower level indication must be highly sensitive micro switch. The complete unit must be in two parts. Each complete part must be fitted in MS CRC sheet box seperately complete all as specified and directed by Engineer-in-charge.
Material & Labour Painting with one coat of synthetic enamelled ordinary tint,fire hydrant box sizes 800x600x250mm double door complete all as specified and directed by Engineer-in-charge.
Supply and laying in repairs Synthetic insulating mat of size 2mx1mx10mm complete all as specified and directed by Engineer-in-charge.
Material and labour for gland packing of sluice valves 80/100/150 mm bore with proper size asbestos graphite gland packing rope etc complete all as specified and directed by Engineer-in-charge.
Supply & applying of grease best quality for 3 to 60 HP pump/motor etc complete all as specified and directed by Engineer-in-charge.
Supply and Fixing for digital type voltmeter 0-500 volts range, flush type, AC, 50Hz in existing panel boards after disconnecting of cables and testing including removing of unserviceable voltmeter complete all as specified and directed by Engineer-in-charge.
Supply and Fixing for digital type ammeter suitable for 10 HP to 60 HP pumpset panel ,flush type with appropriate CTs, AC, 50Hz in existing panel boards after disconnecting of cables and testing including removing unserviceable item complete all as specified and directed by engineer-in-charge
Supply and Fix LED phase indicating lamp R-Y-B colour as required at site complete with base holder suitable for AC, 240 volts and testing including removing of old unserviceable lamps complete all as specified and directed. Make : Minilec / L&T / Siemens/AE
Material & Labour for disconnecting pressure pump set 0.5 HP AC 230 volts and dismantaling motor, rewinding with super enamelled copper wire, refitting, and fixed in same position/other positionincluding testing etc complete all as specified and directed by Engineer-in-charge.
vinayandsons
M/S SUMAN ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .