Loading…
Loading…
Tender Value
₹5.8 Cr
EMD Value
₹11.6 L
Closing Date
4 Sept 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
MAINTENANC
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V = Advertised value of the tender in crores of Rupees N = Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The tenderer shall possess a valid Electrical Contractor License, issued by any State Government or Union Territory Administration, authorizing execution of electrical works up to 11 kV. The contractor shall have in his employment or shall engage a person holding a valid certificate of competency issued by any State Government or Union Territory Administration for supervision of electrical works up to 11 kV. Offers not accompanied by a valid Electrical Contractor License and requisite Supervisor competency for works up to 11 kV shall be summarily rejected.
Similar Nature of Work: Supply, installation, testing and commissioning of LT/HT electrical GS assets ORSupply, installation, testing and commissioning of electrification or rewiring of building/workshop. ORSupply, installation, testing and commissioning of Yard/circulating area/street lighting/tunnel/facade lighting. ORSupply, installation, testing and commissioning of high-mast lighting. ORSupply, installation, testing and commissioning of glow signages. ORSupply, installation, testing and commissioning of LT/HT electrical GS sub-station with at least 50% capacity of proposed sub-station ORRepair/overhauling of LT/HT electrical GS assets including LT/HT sub-stations.Note: The value of HT work is Rs. 1,18,09,351 out of total advertised value of Rs.5,81,86,756.42 and LT work has major monetary value. Hence, Vide. PCEE/SCR Ltr No. E.29/P/Similar nature of works Dt.30.12.2014 the similar nature of work pertaining the work which has major monetary value contribution is taken for definition of similar nature of work eligibility criteria.
49 conditions · 8 needing a document upload
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. and corresponding documents shall be submitted by the tenderer as per the composition of the Firm.
The Bid Security shall be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure- VIA of GCC and shall be valid for a period of 90 days beyond the bid validity period. Non-submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non- submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. The originalBank Guarantee should be delivered in person to the official nominated as indicated in the tender document within 5 working days of deadline of submission of bids.
Eligibility criteria :- Eligibility criteria shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self attested/digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document.
Tender Form (First sheet, Second sheet) of The GCC April 2022.
Certificate format (Affidavit) which available as Annexure - V in Mandatory documents. A facility has already created for online submission of Annexure Vof GCC in IREPS module, uploading of physically signed Annexure V by tenderer has been discontinued.
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) /Limited Liability Partnership (LLP) etc.
The corresponding documents shall be submitted by the tenderer as per the composition of the Firm: Sole Proprietorship Firm: (i) All documents in terms ofPara 10 of the Tender Form (Second Sheet) above. HUF: (i) A copy of a notarized affidavit on Stamp Paper declaring that he who is submitting the tender on behalf of HUF is in the position of 'Karta' of Hindu Undivided Family (HUF) and he has the authority, power and consent given by other members to acton behalf of HUF. (ii) All other documents in terms of Para 10 of the Tender Form (Second Sheet) above. Partnership Firm: (i) All documents as mentioned inpara18 of the Tender Form (Second Sheet). Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) /AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by theCompany(backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liabilityagainst the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above. LLP (Limited Liability Partnership): (i) A copyof LLP Agreement (ii) A copy of Certificate of Incorporation (iii) A copy of Power of Attorney/Authorization issued by the LLP in favour of the individual to sign the tender on behalf of the LLP and create liability against the LLP. (iv) Anundertaking by all partners of the LLP that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of Indiafrom participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP or JV in which they were /are partners/members. Concealment / wrong information in regard to above shall make the contract liable for determination under Clause 62 of the Standard General Conditions of Contract. (v) All other documents in terms of Para10 of the Tender Form (Second Sheet). Registered Society & Registered Trust: (i) A copy of Certificate of Registration (ii) A copy of Memorandum of Association of Society/Trust Deed (iii) A copy of Power of Attorney in favour of the individual to sign the tender documents and create liability against the Society/Trust. (iv) A copy of Rules & Regulations of the Society (v) All other documents in terms of Para 10 of the Tender Form (Second Sheet) above.
The tenderer shall be required to submit the Bid Security with the tender for the due performance with the stipulation to keep the offer open till such date as per Clause No.5 of PART -1 of The GCC, April 2022.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Guntakal Division- Replacement of OH Line with LTUG Cables Covering Service Buildings/Colonies in Guntakal Section for Improving the Power Supply Reliability.
GTL-EM-36-2026-27~SCOR
GTL-EM-36-2026-27
Open
Works - General
6 Months
Anantapur, Andhra Pradesh
₹0
₹11.6 L
13 Aug 2026
13 Aug 2026
21 Aug 2026
97 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 5,81,86,756.42 | ||
| for details. | Item Breakup | — | — | ||
| Supply, laying and termination of 1.1 KV Grade 4 core 240 Sq,mm LT XLPE UG aluminium cable, 1100 Volts as per IS:7098/Pt.I/1988 or latest with suitable lugs and glands complete. | — | — | — | 50,64,000 | |
| for details. | Item Breakup | — | — | ||
| Supply and laying of HDPE pipe of PE-80 Grade, PN-4 outer dia of HDPE pipe 110 mm as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 29,08,500 | |
| for details. | Item Breakup | — | — | ||
| Supply, Laying, Testing and Termination of 4 core 120 sq.mm XLPE insulated underground armoured aluminium cable as per IS 7098(Part 1)1988 with latest amendments with necassary lugs and terminations complete. | — | — | — | 43,64,470 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of HDPE pipe of 75 mm of PE-100, PN6 class as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 9,95,500 | |
| for details. | Item Breakup | — | — | ||
| Supply, Laying, Testing and Termination of LTUG 4 core 25 sqmm XLPE insulated PVC sheathed Aluminium armoured cable as per IS 7098 (Part 1) 1988 with latest amendments and with necassary lugs and terminations complete. | — | — | — | 18,49,320 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of HDPE pipe of 50 mm outer dia of PE-100,PN6 class as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 7,20,000 | |
| for details. | Item Breakup | — | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 16 sqmm XLPE insulated PVC sheathed Aluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necassary lugs and terminations complete. | — | — | — | 12,11,080 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of HDPE pipe of 40 mm of PE 63 grade, PN8 as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 8,55,000 | |
| for details. | Item Breakup | — | — | ||
| Supply, laying and termination of HT UG 3 core 240 sq.mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. The cost includes proper storage, handling, transportation etc. The cable shall be supplied along with the test certificate of manufacturer etc. | — | — | — | 1,10,96,235 | |
| for details. | Item Breakup | — | — | ||
| Supply and erection, testing, connecting and commissioning of HT 11KV grade out door type cable end termination kits of heat shrinkable type cable termination kits suitable for 240 Sq.mm 03 core XLPE/PVC earthed system cable complete with suitable jumpers, bolts, nuts,washers,lugs etc. Make/Brand DENSONS/Raychem/REPL/XICON/M-seal brand of Mahindra Engg. & Chemicals | — | — | — | 2,99,852.16 | |
| for details. | Item Breakup | — | — | ||
| Excavation of cable trench in all types soils of size 400mm wide x 1 mtr. deep, and making good of the same to its original form and shape after complete including all connected materials and works up to the satisfaction of the Engineer at Site and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013 The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 33,69,900 | |
| for details. | Item Breakup | — | — | ||
| Excavation of cable trench in rocky soil of size of size 400mm wide x 1 mtr. deep, and making good of the same to its original form and shape after complete including all connected materials and works up to the satisfaction of the Engineer at Site and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013 | — | — | — | 62,424 | |
| for details. | Item Breakup | — | — | ||
| Excavation of cable trench in cement concrete bed flooring by using power drill to a depth of 1.0 Mtr and a width of 0.3mtr. After laying the pipe and refilling the trench with excavated earth and undertaking cement concrete bed flooring to its original shape as was prevailing earlier to the satisfaction of Railways site Engineer and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013.The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 21,44,448 | |
| for details. | Item Breakup | — | — | ||
| Excavation of cable trench of size 400mm x 1 mtr deep track X-ing/Road X-ing and making good of the same to its original form and shape completely including all connected materials and works to the satisfaction of Railways site Engineer and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013.. .The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 13,01,962 | |
| for details. | Item Breakup | — | — | ||
| Supply and laying of 8 SWG GI wire with 40 GSM ZinC coated, conforming toIS:280- 2006 or latest, it is to be laid with armourd cable for earth continuity. | — | — | — | 3,48,000 | |
| for details. | Item Breakup | — | — | ||
| HT/LT Cable laying by horizontal boring below track etc by pushing method-Drilling for horizontal bore below track by pushing method by suitable means for laying of GI pipes/ HDPE pipe etc of various sizes, the bore shall be of 200 mm dia & shall be done at a depth of 3000 mm from ground level, it also includes insertion of pipe. | — | — | — | 4,31,400 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of HT/LT Power cable route indicators with all connected materials and works as per Drawing No.DEE/CN/BZA/2001/23. | — | — | — | 1,23,676.6 | |
| for details. | Item Breakup | — | — | ||
| Supply of material, fabrication and erection of H Pole (Double Pole) with I section MS beam ISHB 150, size 150 mmx 150 mm of length 10 mtrs. With required foundation and painting etc. as per specification. | — | — | — | 2,96,405.84 | |
| for details. | Item Breakup | — | — | ||
| "Supply Erection, testing & commissioning of 11KV, 200A gang operated AB switch (Vertical type) complete of reputed make." | — | — | — | 74,494.16 | |
| for details. | Item Breakup | — | — | ||
| Supply, Erection, testing & commissioning o of 11KV 50A/60A capacity expulsion type dropout fuses complete. | — | — | — | 26,725.2 | |
| for details. | Item Breakup | — | — | ||
| SITC 11KV Disc Insulator complete with hardware | — | — | — | 11,485.68 | |
| for details. | Item Breakup | — | — | ||
| SITC 11KV Pin Insulator complete with hardware. | — | — | — | 4,153.44 | |
| for details. | Item Breakup | — | — | ||
| Preparation and submission of completion drawings in A3 size with all relevant details and measurements of executed installations, cable routings, lighting arrangements etc. The drawings shall be submitted in 1 (Soft Copy)+ 3 (Hard Copy) duly signed by the concerned Supervisor, contractor, controlling officer and to be furnished along with bills. | — | — | — | 44,124 | |
| for details. | Item Breakup | — | — | ||
| Supply, Transportaion, Erection & commissioning of 5mtr long hot dip galvanised Octagonal pole (IS 875) with 130mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet (S 355 JO steel plate for shaft), along with base plate IS 2062 of size 200x200x12mm, M16x600 long J type EN8 grade foundation bolts, 1000mm long single/ Double arm bracket Including the Supply of Suitable bolts with Bakelite Sheet with MCB (for mounting inside the base compartment of pole) including Erection & commissioning of 5 mtr. octagonal pole including RCC foundation & plinth in hard soil including excavation of soil, tamping of concrete, grounting and supply of other required materials and accessories complete. | — | — | — | 18,37,360 | |
| for details. | Item Breakup | — | — | ||
| Service connection to the fitting from the junction box of 5 mtrs Octogonal pole by means of PVC insulated copper conductor of 3 core 1.5 Sq.mm with necessary lugs at the juction box and necessary termination at the luminaire complete. | — | — | — | 73,000 | |
| for details. | Item Breakup | — | — | ||
| "Dismantling of Poles (tubular) / Rail Poles/Octogaonal poles and handing over the SSE stores." | — | — | — | 45,556 | |
| for details. | Item Breakup | — | — | ||
| Excavation of pit for octagonal pole/poles of suitable size in all type ofsoils as per the direction of engineerat site. | — | — | — | 1,02,990 | |
| for details. | Item Breakup | — | — | ||
| Provision of RCC foundation and constructing the plinth for erection of octogonal poles as per the directions of engineer at site Including the anchor plates. | — | — | — | 1,23,680.7 | |
| for details. | Item Breakup | — | — | ||
| Supply and fixing of LED street light fittings of 48W with suitable driver with all connected materials (The supply includes accessories such as clamps, ties extenstion wires etc for fixing) conforming to IEC 60598-1 as per attached railway specification. | — | — | — | 7,05,000 | |
| for details. | Item Breakup | — | — | ||
| Supply, running, Connecting of 1 core 4 Sq.mm FRLS, PVC insulated Copper conductor cable with necessary accessories like cable ties etc. IS 694 (2010) with latest amendments. | — | — | — | 76,000 | |
| for details. | Item Breakup | — | — | ||
| Supply, running, Connecting of 1 core 6 Sq.mm FRLS, PVC insulated Copper conductor cable with necessary accessories like cable ties etc. IS 694 (2010) with latest amendments. | — | — | — | 2,48,000 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection SMC Junction Box of Size 295 x 195 x 100mm of Model No. Sintex GSJB-3020 Complete with 4-Way connector complete with SS bolts and nuts . (Fixing should be required as per instruction of site supervisor). Suitable clamps for fixing (MS Clapms 02 Sets for each Box with necessary bolts and nuts as per site condition for GI channels/poles as per the directions of Site engineer). | — | — | — | 4,42,860 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of SMC junction Box of Size 530 x 450 x 175 mm of Model No: Sintex GSJB 5345 to fixing of 4-Pole MCCB and termination of cable to extend supply. | — | — | — | 6,18,845 | |
| for details. | Item Breakup | — | — | ||
| Supply and concealed laying of 25 mm dia 2mm thick PVC pipe (ISI MARK) heavy mechanical stress FRLS with all required accessories including masonary work and labour charges etc. | — | — | — | 74,000 | |
| for details. | Item Breakup | — | — | ||
| Supply and running of 32 mm dia, Ivory colouredPVC conduit of wall thickness not less than 2 mm with junction boxes, bends and all accessories etc. as required as per site requirement. Running of conduit, fixing with suitable clamps and nuts in groove / open /shelter. | — | — | — | 1,18,540 | |
| for details. | Item Breakup | — | — | ||
| Cutting of groove in the wall, Plastering of surface to the original for concealing of the conduit in the wall (Laying and fixing of conduit will bepaid separately). | — | — | — | 16,800 | |
| for details. | Item Breakup | — | — | ||
| Removal of feeders of OH lines including guarding and areal earth, cross arms and insulators etc and surrendering the same to concerned supervisor. (other additional fixtures such as lights etc are also to be dismantled where ever applicable.) | — | — | — | 8,49,040 | |
| for details. | Item Breakup | — | — | ||
| Supply and fixing of RCCB 2P 25A 30mA with metal enclosure. RCCB conforming to IS 12640 (Part 1) : 2024 with 10 kA short circuit withstand capacity as advised by the site supervisor with all necessary accessories complete | — | — | — | 5,43,780 | |
| for details. | Item Breakup | — | — | ||
| Excavation of earth for one pit in any soil and refilling as per Drg. No ETI/OHE/P/7021 and RDSO specification No.RDSO-TI0LKO(PSI@41&47@2020 dt.25.08.2021. | — | — | — | 79,039.2 | |
| for details. | Item Breakup | — | — | ||
| Supply and erection of Earth Elecrode as per RDSO Drg No.ETI/OHE/P/ 7021 (REV.A) or if any latest. Earth electrodes shall be procured fromCORE approved sources only , List ofCORE approved sources is enclosed asAnneux-CORE List). | — | — | — | 4,05,038.4 | |
| for details. | Item Breakup | — | — | ||
| Supply and erection of Charcoal. | — | — | — | 1,20,744 | |
| for details. | Item Breakup | — | — | ||
| Supply and erection of Salt. | — | — | — | 83,496 | |
| for details. | Item Breakup | — | — | ||
| Provision of RCC earthpit hollow box of size300 mm x 300 mm x300mm with 50 mmwall thickness as per Drg. no.SDO/RDSO/E&B/001 byusing M20 Grade precast RCC. It includes fixing of earth pits at various locations (All the required men, materialand transportation are to be arranged by contractor). Inspection by Consignee. | — | — | — | 1,31,968.8 | |
| for details. | Item Breakup | — | — | ||
| Supply and Erection of RCC precast slabs with hook to cover Earth pits of dimensions as shown in IRSEM drg no 19-D6. All the required materials for this work i.e. stones, cement, iron and sand etc. are to be supplied by contractor. Inspection by Consignee. | — | — | — | 27,972 | |
| for details. | Item Breakup | — | — | ||
| Supply of Professional earth resistance tester with measuring range 0-20 ohms & higher. Resolution: 0.01 ohms at 0-20 ohms & 0.1 at 0-200 ohms. Accuracy:+/- 2% Supplied complete with test leads, spikes & simplified measurement probe. Also measures earth voltage up to 200V with accuracy of +/ - 1%. Complies with EN/IEC 61010-1 CATIII 600V. Model Stanlay 521or similar. Inspection by Consignee. | — | — | — | 65,288.84 | |
| for details. | Item Breakup | — | — | ||
| Supply of Electronic earth tester Model No.4680B Meco make orhigher version or similar. The earth tester shall benon - contact type without requirement of auxiliary electrodes and shall have 4 digit 9999 LCD display with ground resistance range from 0.25 to 1500. Inspectionby Consignee. | — | — | — | 2,60,480.8 | |
| for details. | Item Breakup | — | — | ||
| Fabrication and erection of 14 SWG CRCA sheet steel enclosure of suitable size for outdoor feeder pillar with IP 54 protection, plinth mounted with Double Door, including cutting, bending drilling, welding and revetting etc, complete with cleaning with 7 tank process and painting with EPOXY powder coating including cost and conveyance of all materials and labour charges. The MDBs shall be mounted on suitable required size of CC plinth (CC plinth cost will be paid separately)/ wall mounted and secured with bolts, nuts and washers as advised by Engineer at site. The panel comprising of 500A tinned Copper Bus Bar (RYB & N of same size) as per IS 613: 2000 or latest amendment required shape supported with appropriate DMC / SMC barriers and colour coded with heat shrinkable sleeves, LT 3 Phase Digital Multifunction energy meter with 3 lines LCD display for measuring all the parameters (Voltage/ Current/ Power/Frequency/power factor /kw/kwh/ kvar/kvarh) , Current T/Fs, indication lamps for incoming & outgoing feeders. Support insulators, neutral links, Incoming & outgoing terminals, suitable cable termination glands , grommets, lugs, connecting wires and all other accessories suit with the following switchgear and accessories. Suitable busbars has to provided for the incomings of all the MCCB's from main bus bar. The cables should be properly terminated in the switchgears with necessary lugs and all necessary accessories complete. The panel should conform to IS/IEC 61439 in all respects. The panel should comprise of the following Switchgear: 1. Supply and installation of 250 A 4P MCCB, 36 KA, Micro processor based adjustable with LSIG protection communication capable conform to IEC 60947-2 with its latest amendments, model no. 4205 39 of Legrand make or it's equivalent with extended ROM, spreader links (2 sets) - 2 no's., 2. Supply and installation of on load change over switch of 250A of havells model no: IHCNFE0250 or its equivalent Conforms to IS/IEC:60947-3 with its latest amendments - 1 no's., 3. Supply and installation of 160 A 4P MCCB, 36 KA, Micro processor based adjustable with LSIG protection conform to IEC 60947-2 with its latest amendments, model no. 4205 37 of Legrand make or it's equivalent with extended ROM, spreader links (2 sets) - 1 no's., 4. Supply and fixing of C curve FP MCBs of 32 A with all connected accessories -10 no's., 5. Supply and erection of LED indicator lamps on the existing box panel board- 2 sets of RYB. The Fabricator of the LT panel should have the CPRI approval. Prior Approval to be taken before fabrication. | — | — | — | 1,25,20,664 | |
| for details. | Item Breakup | — | — | ||
| Provision of Foundation/Platform for installation of APFC/LT panels. | — | — | — | 10,13,456.6 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
NITIREPSWorks36.pdf
ATTACHMENT
CEGE Technical Circular
ATTACHMENT
ListofLikelySuppliers.pdf
ATTACHMENT
GCC April 22 With Correction Slips
ATTACHMENT
JPO Digging of Cable
ATTACHMENT
EarthingSpecificationMFEandOther.pdf
ATTACHMENT
RITESInspection.pdf
ATTACHMENT
Scopeofworkforwiring.pdf
ATTACHMENT
Technicalspecifications--9-26.pdf
ATTACHMENT
FirepreventionGuideline.pdf
ATTACHMENT
CEGETechnicalCircular07-04-2022_compressed.pdf
ATTACHMENT
GCC_April-2022WithCorrectionSlips._compressed.pdf
ATTACHMENT
RlyBd-JPO-DiggingofCables2013-Re-Circulatedin2022-LATEST.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].