| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹21.4 LAccepted-AOC | ₹21.4 L | 1 | Accepted-AOC Awarded |
| 2 | 2₹21.7 LRejected-AOC | ₹21.7 L | 2 | Rejected-AOC Not Awarded |
| 3 | 3₹22.2 LRejected-AOC | ₹22.2 L | 3 | Rejected-AOC Not Awarded |
Tender Value
₹22.3 L
EMD Value
₹23,000
Closing Date
14 Jun 2019, 5:00 pmClosed
S.E., E.T.C., Bareilly
Superintending Engineer Hydel Campus, Near L.I.C. Office Rampur Garden, Bareilly
Improvement AND Strengthening of Lighting Arrangement by Installation of 30 Meter High Lighting Mast alongwith other associated Works at 220/132KV Sub Station Pilibhit under E.T.D. - II, Bareilly
2019_UPTCL_350068_1
E-Tender No. 24 / W / ETC(B) / 2019 - 20
Open Tender
Electrical Works
150 days
Pilibhit
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,360
A/c No 10897666087 IFSC SBIN0000615 S.B.I. Bly
₹23,000
24 Sept 2020
3 Jun 2019
15 Jun 2019
3 Jun 2019
14 Jun 2019
3 Jun 2019
3 Jun 2019 - 14 Jun 2019
Amount
Improvement & Strengthening of Lighting Arrangement by Installation of 30 Meter High Lighting Mast alongwith other associated Works at 220/132/33KV Sub Station Pilibhit, with all Cost of Men, Misc. Consumables, T&Ps etc. Required except the Power Cables, Control Cables and M.S. Flats etc. that shall be Provided by the Department for Satisfactory Completion of the Work as per Technical Specifications & Direction of the Supervising Engineer, as per Details Below : (1) Providing & Installation of 30 Meter High Lighting Mast Manufactured from Hot Rolled Structural Steel (as per BS EN10025 or Equivalent) having 3 Sections of Equal Lengths each duly Hot Dip Galvanized as per BS 729 or Equivalent having Base dia. 532 mm (Approx.) and Top dia. 150 mm (Approx.) with Required Foundation Casting as per Drawing. The High Mast should be of Bajaj / CGL / Havells / SYSKA make and should Consist of following Items Strictly as per Technical Specification (1 Job for each Lighting Mast) : (a) Door Panel on Bottom of the Pole in size of 1000 x 250 mm having Allen Key Locking Arrangement & Wooden Stack Board inside it (b) Base Plate of dia. 740 mm & thickness 32 mm (c) Anchor Plate of size 740 x 740 x 6 mm (d) Template of size 740 x 740 x 4 mm (e) Winch having Double Drum to Bear the Load of Capacity 750 Kg (f) 5 No. High Tensile Wire Ropes of 6 mm dia. (g) Trailing Cable (2.5 mm2 size Flexible Multi Strand Copper Cable)
(2) Providing & Fixing of Lantern Carriage Manufactured from Mild Steel as per IS 2062 having 1200 mm dia., Complete with Rubber Padded Guide Ring between Carriage & Mast (1 Job for each Lantern Carriage).
(3) Proper Earthing of Lighting Mast with 25 x 6 mm size M.S. Flat with due Cutting, Straightening, Bending, Drilling, Welding, Painting etc. (1 Job for Earthing of each Lighting Mast)
(4) Providing & Fixing of 250 Watt LED Flood Light Luminaire Fitting of Philips / Bajaj / CGL / Havells / SYSKA make with PDC Housing & IP 66 Protection, Heat Resistant Tempered Glass for Protection with 5KV Surge Protection, Applicable for Large Area Lighting, complete in all Respect with all Electrical Connections. The 18 No. Light Fittings are to be Fixed on Lantern Carriage of each High Lighting Mast (1 Job for each Light Luminarie Fitting).
(5) Providing & Fixing of 2 x 100 Watt Aviation Light Fitting to be Fixed on Top of the each High Lighting Mast, complete in all Respect with all Electrical Connections (1 Job for each Aviation Light Fitting).
(6) Providing & Fixing of 3ϕ L.T. A.C. Supply Cubical of size 450 x 450 x 200 mm with Hinged Door & Proper Locking Arrangement duly made of 16 SWG M.S. Sheet and Painted with Grey Colour Synthetic Enamel Paint. The L.T. A.C. Cubical should be Fitted with 4 No. 100 Amp. Insulated Aluminum Bus Bar (3 Phase & 1 Neutral), 1 No. 100 Amp. TPN MCCB, 1 No. 15 KW Capacity Contactor for Interlocking System, 2 No. Contactors for Up & Down Lantern Carriage System, 1 No. 24 Hr. Timer Switch for Automatic 'On' / 'Off' of the Lights, 3 No. MCCBs for Outgoing Circuits. The Cubical should also Consist of Cable Glands duly Fitted in Gland Plate Fixed on the Bottom of the Cubical alongwith complete Internal Wiring. (1 Job for each L.T. A.C. Cubical).
(7) Laying of 3½ x 70 / 50 mm2 size L.T. Power Cables, 50 cm below the Ground Level after Excavation of Trench, Putting the 1st Class Bricks & River Sand Along & over the Cable, then Back Filling of the Trench after Laying of Cables. The Work also includes both sides Termination of the Cables with Crimping of Lugs of standard make to be Provided by the Contractor.