Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.0 LAccepted-AOC | L1 | Accepted-AOC Lowest Quote | |
| 2 | L2₹24.8 L+₹3.8 L (17.9%)Rejected-Finance | L2 | Rejected-Finance Financially Rejected |
Tender Value
Refer Docs
EMD Value
₹44,558
Closing Date
31 May 2025, 3:00 pmClosed
MANAGING DIRECTOR
MANAGING DIRECTOR,KSFDC Chalachithra Kalabhavan, Thiruvananthapuram.
DESIGN ENGINEERING SUPPLY INSTALLATION TESTING AND COMMISSIONING OF HVAC WORK AT KAIRALI SREE NILA THEATRE KSFDC ARISTO JUNCTION THAMPANOOR TRIVANDRUM
2025_KSFDC_765993_1
2745/T3/24/KSFDC
Open Tender
Electrical Works
Item Rate
KAIRALI SREE NILA THEATRE, THAMPANOOR TRIVANDRUM
Please refer Tender documents.
7 documents required · 7 mandatory
₹4,206
₹44,558
2 Jul 2025
24 May 2025
2 Jun 2025
24 May 2025
31 May 2025
24 May 2025
HIGH SIDE (MACHINES) - NON INVERTER PACKAGED UNIT 22 TR NON INVERTER PACKAGED AIR CONDITIONER Supply, Installation testing and Commissioning of Floor Mounted Type Packaged Units of specified capacities, nominal capacity condensing unit with all standard fittings, safety devices, like HP/LP cutout, single phase preventor, overload relays, R-410A Gas, vibration isolation pads etc. Suitable to work till 50 Deg ambient, Blue Fin Condenser and Corrosion Resistant Body, Wide Voltage Range 360V - 440V, Scroll Compressor-driven. Due to their inherent design characteristics, scroll compressors have very high volumetric efficiency. They are ideal for air conditioning applications where the compression ratio is not very high. Out door unit stand for Ducted machine ,vibration isolation pads etc. complete including all charges Anticorrosive black paint ( 2 coat epoxy painting and 2 coat primer ), Transportation , unloading, leading and positioning etc. complete
LOW SIDE WORK Flexible canvass connection interconnecting indoor and supply air ducts
SHEET METAL WORK Minor alteration of supply / Exhaust air duct near indoor mouth area, modifications, insulations and alignment as per the new Machine requirement
REFRIGERANT PIPING copper refrigerant pipe of size with necessary 19 mm thick nitrile sleeve insulation for suction and 13mm thick for discharge for connecting indoor and outdoor units of suitable sizes - 22 TR Packaged
Commissioning of the system with eco-friendly R-410A gas after necessary pressure holding of nitrogen at 500psi for 24hrs, vacuuming of the system to 600 microns and positive charging
Supply and installation of power cabling between indoor and outdoor
Supply and installation of communication cabling between indoor and outdoor
Supply and installation of cabling between Indoor and isolator (isolators to be provided within 1 mtr radius for Indoor)
Outdoor unit supports alterations
Dismantling & Shifting existing Machines
Supply,Installation,Testing and Commissioning of following size . Insulated PVC drain pipe from unit drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 6 mm thick closed cell class O Nitirile Rubber foam insulation . 32mm dia PVC Pipe
Supply,Installation,Testing and Commissioning of following size . Insulated PVC drain pipe from unit drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 6 mm thick closed cell class O Nitirile Rubber foam insulation . 40mm dia PVC Pipe
bluezone (BID ID -2217208)
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .