| Sl No | Description | Qty | Unit | PERFECT IMAGE SOLUTIONS L1 | MITRA ELECTRONICS L3 | Creative Projects L2 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, testing and Commisioning of Microprocessor based addressable fully networkable fire alarm control panel (VDS/UL/ERTL/LPCB/FM approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha-numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/fault conditions. Further the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its memory as per recommended standards. The panel should have extra loop card slot for expansion of capacity twice. | ||||||
| 1.01 | The panel shall have in built rectifier, provision for external and internal printer (if required), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects in built surge protection facility integral SMF lead acid batteries with scaled cells of 24V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licenced software.
(Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE) | 1 | Nos | 1,55,000 ₹1,55,000 | 90,000 ₹90,000 Lowest | 2,80,000 ₹2,80,000 |
| 2.00 | Supply, Installation, testing and Commisioning of Microprocessor controlled Adressable Multisensor detector IP 42 (VDS/UL/ERTL/LPCB/FM approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note: Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra with out extra cost.) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single/ multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall no damage the detectors.
(Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE) | 205 | Nos | 1,400 ₹2,87,000 Lowest | 1,750 ₹3,58,750 | 1,800 ₹3,69,000 |
| 3.00 | Supply, Installation, testing and Commisioning of Addressable Manual Call Point (VDS/UL/ERTL/LPCB/FM approved) with inbuild short circuit fault isolator as per NFPA style 7 wiring complete as required.(Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE) | 12 | Nos | 2,000 ₹24,000 Lowest | 2,100 ₹25,200 | 2,600 ₹31,200 |
| 4.00 | Supply, Installation, testing and Commisioning of Addressable Loop Powered Hooter (sound output of minimum 90 db)cum strobe (Strength of light 10cd) complete with inbuild short circuit fault isolator. Degree of protection IP65 (VDS/UL/ERTL/LPCB/FM approved) approved (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE) | 20 | Nos | 2,200 ₹44,000 | 3,800 ₹76,000 | 1,500 ₹30,000 Lowest |
| 5.00 | Supply, Installation, testing and Commisioning of Addressable Monitor Modules VDS/UL/ERTL/LPCB/FM approved) for monitoring Flow switches/ Fire exit doors/AHU/Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of input or output including all necessary accessories, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms moudle is oprational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE) | 15 | Nos | 0.5 ₹7.5 Lowest | 2,800 ₹42,000 | 1 ₹15 |
| 6.00 | Supplying, Installation testing and commissioning of LED type Response Indicator (VDS/UL/ERTL/LPCB/FM approved) having 2 Nos red coloured LED lamps including connections etc.
(Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel /System sensor/NOTOFIRE/ Agni Suraksha) | 220 | Nos | 0.5 ₹110 Lowest | 62 ₹13,640 | 1 ₹220 |
| 7.00 | Supply and Laying of 2 core 1.5 sqmm FRLS shielded copper Cable (For Loop) (Make- Finolex/Gloster/RR Kable/Polycab) through 19 mm dia PVC FR type Rigid Conduit pipe including S & Laying of the 19mm dia PVC FR type Rigid conduit pipewith necessary arrangement as per G.S (Make- Precision/AKG/Universal/Polycab) on the surface of the wall. | 2,700 | Mtrs. | 87 ₹2,34,900 | 90 ₹2,43,000 | 43 ₹1,16,100 Lowest |
| 8.00 | SITC of Power Supply 230V Ac to 24V DC with high efficiency long life and high reliability low DC ripple, low operation temperature, Good insulation property including all other accessories. (Meke:- Reputed) | 1 | Nos | 0.5 ₹0.5 Lowest | 3,000 ₹3,000 | 1 ₹1 |
| 9.00 | Supply, Installation, Testing and Commisioning of Microprocessor based Intelligent addressable and network connected Repeater panel (VDS/UL/ERTL/LPCB/FM approved) should have all the controls and monitoring as on the main fire alarm panel, functioning as a controller, shall allow remote command in the system reset, trouble and alarm silence and manual alarm. It shall be programmable to display information for the entire system i.e all panels in the network, having minimum 80 characters LCD display (display system status). The system takes displays shall include: Alarm missing point trouble, System test, service, local system test, extra custom test by polling circuit and address. The repeater pannel should annunciate alarm and trouble conditions in the occation of signal actuation. (Approved Make : Cerberus Pro/Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)) | 1 | Nos | 47,000 ₹47,000 | 42,000 ₹42,000 | 25,000 ₹25,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
9 Oct 2023, 2:00 pmClosed
Superintending Engineer, CEC, PWD.
Office of the SUPERINTENDING ENGINEER, Central Electrical Circle 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Constructions of Proposed 100 Bedded Covid Hospital of Kandi in the Murshidabad District-----SITC of Fire Detection System.
2023_WBPWD_574405_1
WBPWD/CEC/NIT/09/Q/23-24
Open Tender
FIRE FIGHTING ORG
Item Rate
45 days
Kandi
Please refer Tender documents.
5 documents required · 5 mandatory
₹20,000
Office of the Superintending Engineer, CEC, PWD.
9 Sept 2026
21 Sept 2023
11 Oct 2023
25 Sept 2023
9 Oct 2023
29 Sept 2023
27 Sept 2023
Amount
Supply, Installation, testing and Commisioning of Microprocessor based addressable fully networkable fire alarm control panel (VDS/UL/ERTL/LPCB/FM approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha-numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/fault conditions. Further the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its memory as per recommended standards. The panel should have extra loop card slot for expansion of capacity twice.
The panel shall have in built rectifier, provision for external and internal printer (if required), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects in built surge protection facility integral SMF lead acid batteries with scaled cells of 24V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licenced software. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)
Supply, Installation, testing and Commisioning of Microprocessor controlled Adressable Multisensor detector IP 42 (VDS/UL/ERTL/LPCB/FM approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note: Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra with out extra cost.) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single/ multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall no damage the detectors. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)
Supply, Installation, testing and Commisioning of Addressable Manual Call Point (VDS/UL/ERTL/LPCB/FM approved) with inbuild short circuit fault isolator as per NFPA style 7 wiring complete as required.(Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)
Supply, Installation, testing and Commisioning of Addressable Loop Powered Hooter (sound output of minimum 90 db)cum strobe (Strength of light 10cd) complete with inbuild short circuit fault isolator. Degree of protection IP65 (VDS/UL/ERTL/LPCB/FM approved) approved (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)
Supply, Installation, testing and Commisioning of Addressable Monitor Modules VDS/UL/ERTL/LPCB/FM approved) for monitoring Flow switches/ Fire exit doors/AHU/Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of input or output including all necessary accessories, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms moudle is oprational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE)
Supplying, Installation testing and commissioning of LED type Response Indicator (VDS/UL/ERTL/LPCB/FM approved) having 2 Nos red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel /System sensor/NOTOFIRE/ Agni Suraksha)
Supply and Laying of 2 core 1.5 sqmm FRLS shielded copper Cable (For Loop) (Make- Finolex/Gloster/RR Kable/Polycab) through 19 mm dia PVC FR type Rigid Conduit pipe including S & Laying of the 19mm dia PVC FR type Rigid conduit pipewith necessary arrangement as per G.S (Make- Precision/AKG/Universal/Polycab) on the surface of the wall.
SITC of Power Supply 230V Ac to 24V DC with high efficiency long life and high reliability low DC ripple, low operation temperature, Good insulation property including all other accessories. (Meke:- Reputed)
Supply, Installation, Testing and Commisioning of Microprocessor based Intelligent addressable and network connected Repeater panel (VDS/UL/ERTL/LPCB/FM approved) should have all the controls and monitoring as on the main fire alarm panel, functioning as a controller, shall allow remote command in the system reset, trouble and alarm silence and manual alarm. It shall be programmable to display information for the entire system i.e all panels in the network, having minimum 80 characters LCD display (display system status). The system takes displays shall include: Alarm missing point trouble, System test, service, local system test, extra custom test by polling circuit and address. The repeater pannel should annunciate alarm and trouble conditions in the occation of signal actuation. (Approved Make : Cerberus Pro/Johnson Controls/Edward/Secutron/Securiton/Apollo/Morley/Eaton/GST/Ravel/NOTOFIRE))
NOTE:- 1) The Fire Alarm system shall comply with latest requirements of ---- i) National Fire Protection Association (NFPA) Standards, ii) IS 2189. iii) NFPA 70 National Electric Code, iv) NFPA 72 National Fire Alarm and Signaling Code v) Local Statutory Regulation vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS:- 1) The System shall be tested and commissioned by a qualified competent trained engineer or technicial authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults continuity, and insulations and other tests as per applicable Indian/International standards must be done.
Terms & Condition:- The Agency must procure the materials from the Manufacturer/OEM or from their authorised sales channel so that the standard warranty/support of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/ support should be sent from the e-mail of the Manufacturer/OEM / authorized sales channels to the e-mail of Engineer in charge and hard copy of it to be submitted during execution of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Creative Projects
MITRA ELECTRONICS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .