Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.9 LAccepted-AOC 11 26 BHAGWANPURA KISHANGARH CHANDIGARH | L1 | Accepted-AOC AOC | |
| 2 | L2₹5.0 L+₹10,810 (2.21%)Rejected-Finance TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L2 | Rejected-Finance Highest | |
| 3 | Rejected-Technical | - | Rejected-Technical Rejected |
Tender Value
₹5.0 L
EMD Value
₹9,940
Closing Date
27 Jan 2022, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Divn. PWD B and R Br. Ambala Cantt.
Const. of Malaria office Bldg. in the Campus of Civil Hospital Sec-6 Panchkula (Pdg. Fire Alarm System).
2022_HRY_204891_1
PWD/Elect-KNL/Elect-AMB/110222
Open Tender
Construction Works
Works
60 days
Ambala Cantt.
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹9,940
Yes
16 May 2022
21 Jan 2022
28 Jan 2022
21 Jan 2022
27 Jan 2022
21 Jan 2022
Amount
Supply of PVC unsheathed s/c stranded ( ISI marked ) copper contuvtor cable 1100v grade in existing pipe excluding cost and erection of pipe but including connection etc. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer – in charge of work MAKE:Plaza/Havells/Finolex (a ) PVC unsheathed copper size 1.5 sq mm single core
Supply and Erection of PVC conduit pipe ISI marked (Medium) on surface including cost of PVC bends, inspection box with all other material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of work.25mm dia
SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 2 Serial Ports. The pane\l shall have a built in power SITC, battery charger maintenance free battery capable of running for a minimum 24 hours operation complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS.Make: Morley ZX5SE,Bosch Avenar 2000, Siemens Cereberus EN.
SITC of Intelligent Analog Addressable type Smoke Detector that combine Photo Electronic and fixed temp thermal with dual LED, hard addressable having rotary decade address switches, with mounting base complete as requried conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of engineer-in-charge of work. Make: Morley HM/PTSE/I + MI/B501AP/IV ,Bosch FAP-425-OT+ MS400B,Siemens OH720 + DB721
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with Back Box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make : Morley HM/MCP/Glass, Bosch FMC-210- DM-G-R, Siemens FDM22.
SITC of Addressable Loop Powered Sounder with Strobe / flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Morley WSO-PR-N05,Bosch FNM-420, Siemens FDS224R
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make Pearl/Giolite/OMEX.
SITC of minimum 1000 Mtr. Range Kheraj / National make SIRON generator provided at the roof of the building with separate Power SITC, relay with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work.
Supply & Installation of ABC Stored pressure TYPE Fire extinguisher 6 KGS capacity (Five year warranty) bearing ISI mark for fire fighting ABC class of fire. The extinguisher will be manufactured stickly as per BIS IS: 15683:2006 bearing IS mark EN3615 approved powder complete in all respect. (Safex/ Minimax/ Ceasefire make).
Supply & Installation of CO2 type fire Extinguisher 4.5 KG capacity made from brand new seamless cylinder as per ISI mark IS: 7285 and CCE approval fitted with discharge hose and horne and squeeze grip /wheel type valve with initial charge as per IS 15683 : 2006 specification bearing ISI marks and EIL approved complete in all respect (Safex/ Minimax / ceasefire Make)
SITC of 1KVA Online UPS with 1 hour backup (Mircotek / Libert / APC Luminous)
Prime Computers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .