GE 871 EWS
GE 871 EWS, c/o 56 APO
REPAIR/MAINT OF LT CABLE, MCCB AND OTHER MISC E/M CONNECTED WORKS IN ZONE-I and Zone II AREA AT JOSHIMATH UNDER GE 871 EWS.
2024_MES_653127_1
8813/E8
Open Tender
Civil Works
Item Rate
120 days
JOSHIMATH
AS PER NIT
8 documents required · 8 mandatory
₹500
GE 871 EWS
₹48,000
15 Oct 2024
9 May 2024
19 Jun 2024
9 May 2024
11 Jun 2024
23 May 2024
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 mtr in depth for foundation. (Laying of under ground cables) in hard/dense soil and getting out all as directed.
Excavation in trenches not exceeding 1.5 m wide and exceeding 1.50 M depth but not exceeding 3.0 mtr in depth for foundation. (Laying of under ground cables) in hard/dense soil and getting out all as directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 mtr in depth for foundation. (Laying of under ground cables) in hard rock and getting out all as directed.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed.
Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L local sand dry, filling in trenches around under ground cable complete all as specified and directed.
M&L for providing of new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable complete all as specified and directed.
Material and labour for laying DWC (Double wall corrugated ) pipe conforming or IS 16205 (electric cable use) of nominal outer dia 50 mm and inner dia 38mm for laying electrical cables under trenches / under road/ wall complete all as specified and directed.
M&L for cutting of PCC/Hard standing/WBM road not exceeding 45 cm in width & not exceeding 60 cm in depth for passing of cable and making good of disturbed surface to match with the existing surface complete all as specified and directed .
M & L for PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete including necessary frame work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
Supply and fix in replacement of light grade Galvanised mild steel pipe 80mm bore complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed as for cable proction . (Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule ):- Make :- Jindal/TATA/Prakash surya
Ditto- all as per Item No 11 here-in-before but of size 50 mm bore
Ditto- all as per Item No 11 here-in-before but of size 40 mm bore
M&L Coping for, steel tubular poles new and old (1:2:4) Type B-1 using 20 mm graded aggregate for coping of poles including necessary farm work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
Supply and fix laying & testing of aerial bunched cable 1100 volt grade stranded and aluminium conductor 4 core x 70 Sqmm,(three phase and one nuetral), 50 Sqmm (insulated messenger) , electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor including all fittings such as anchor clamp,suspension clamps,inline connector,cable protection and dead construction, in cluding taking down unserviceable cable all as per IS , specified & directed.
Supply and fix in replacement, laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 120 sqmm 3.5 core all as per IS , specified & directed.
Ditto- all as per Item No 16 here-in-before but of size 95 Sqmm 3.5 core
Ditto- all as per Item No 16 here-in-before but of size 70 Sqmm 3.5 core
Ditto- all as per Item No 16 here-in-before but of size 50 Sqmm 3.5 core
Ditto- all as per Item No 16 here-in-before but of size 35 Sqmm 3.5 core
Ditto- all as per Item No 16 here-in-before but of size 25 Sqmm 4 core
Ditto- all as per Item No 16 here-in-before but of size 10 Sqmm 4 core
Ditto- all as per Item No 16 here-in-before but of size 16 Sqmm 2 core
Ditto- all as per Item No 16 here-in-before but of size 10 Sqmm 2 core
S&F in replacement of cable jointing kit for 1100 volt grade cable for straight through termination heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5/4 core.
All as per item No 25 but for 25 to 50 Sqmm size.
All as per item No 25 but for 70 to 150 Sqmm size.
S&F in replacement of Off Load Change Over Switch (Manual change over in sheet enclosure) with sheet steel enclosure fixed over wall / panel etc. of rating 200 Amps, 415 Volts, 4 pole with complete with sheet steel enlcosure all as specified and directed by Engineer in Charge.
Taking out under ground, LT cables, different sizes, by excavation and earth work in any type of soil, removing bricks or PCC tiles of any size, re-laying in the same trenches or re-routing after rectification of fault as required complete all as specified and directed NOTE:- (i) Joints & Jointing materials, new cable, additional bricks/PCC Covers, sand shall be measured & paid for separetely. (ii) Retrieved serviceable bricks or PCC cable cover/Bricks and sand shall be re-laid on the cable & the cost for the same is deemed to be included in the unit rate.
Receiving and attending External Electric/Street Lights complaints from Complaint Section / JE / Engr-in-charge by any mode of communication & attending the same within 24 hours. This item is inclusive of all the preliminary work like opening of connections, checking for supply, transportation of necessary tools and labour, assessing the nature of complaints, rectifying minor issues including removing carbon deposits (if any), cleaning of lugs/glands etc., meggering of cables, making temporary connections (as required), removing soil and restoring back the power supply all as directed at site. Note:- 1. The occurance of fault if any, will be communicated to the contractor and the contractor shall rectify the same within 24 hrs of reporting, failing to which a recovery @ Rs 500/= per complaint per day and the same will be add further . 2.Record of Complaint slip shall be submitted along wth claim for payments. 3.Transporation of depolyed Electrician by contractor to Zone-I will be included in quoted rates. 4.Any type of Ladder requied for electric work on pole at any height shall be arranged by the contractor.5. Complaint slip book, complaint register and ladder and T & P shall be provided by the contractor
Supply and fix in replacement of 1100 Volts grade heavy duty cable PVC insulated aluminum conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 10 mm suspension wire, one twin core cable flat or circular of size of aluminum conductor 10 sq mm stranded conductor all as specified and directed.
Supply and fix in replacement, errecting of steel tubular poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide complete all as specified and directed. Make : India Co. Ltd Jamshedpur/Fabrico(India) Pvt Ltd Meerut/National Tubing Co. Kanpur Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
M & L in replacement of ACSR conductor of size 6/1 x 2.59 (Weasel) and 6/1 x 2.11 (Squirrel) ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of cradles, hexagonal/rectangular, fabricated with galvanised steel wire 4 mm dia as in repairs complete all as specified and directed.
Supply and fix in replacement of mild steel cross arms, bracings, supports, clamps, and back plates fabricated from structural steel sections as ordered including necessory nuts, bolts, washers , welding, bending, cold or hot , drilling holes for bolts , in any shape or size as indicated or directed with and including preparations of new steel surfaces & applying two coats of aluminium paint over one coat of red oxide Zn Chrome primer complete all as specified.
Supply and fix in replacement of Pin type insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 1100 volt grade.
Supply and fix in replacement of Insulator shackle type porcelain vitreous, white brown or green 100mm height and 115 mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 1100 volt grade complete.
Supply and fix in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm, Complete all as specified and directed.
M&L for Earthing complete with GI earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.5 Mtr below normal ground level connected to GI strip 32 x 6 mm size drawn through 40mm GI light grade pipe and including providing 15mm bore GI pipe medium grade as water pipe with suitable size funnel ,as earthing lead filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC(1:3:6) type C1 using 20mm graded stone aggregate and PCC cover made with PCC (1:2:4) type B1 using 20mm graed stone aggregate reinforced with 8mm TMT bar @ 100mm c/c alongwith lifting handle of 833 dia steel bar complete all as shown and specified in electrical plate no.3 of SSR Part-I (2009) all as directed. (Note:GI strip upto 7.5 m length in included in unit rate quoted by contractor).
M & L for cutting, trimming of branches along the OH conductor of LT/ HT line within 2 mtr distance along both side of line and strictly all branches in one place as directed by Engineer-in-Charge.
M & L for Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors and adding new length( if required) in place of old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire all as specified. ( Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge) . Note:- Five lines together will be measured as one span from pole to pole.
M & L for Painting to poles (9/11 mtr long) including cross arms, 'V' brackets, 'D' clamps, nuts, bolts, complete including painting with five strips of 30cm each black and white paint in alternate strips from the base of pole upto 1.5mtr height complete, spray painting with two coat of synthetic enamel paint of first quality silver paint over a coat of red oxide primer after and including complete removal of old paint by scratching, rubbing complete all as specified and directed
Supply,installing, testing and commissioning Outdoor type LT feeder piller box of size not les than 1200x1200x400mm, padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, double door, front side openable, type IP 54 protection made of CRCA sheet 3.15 mm thick of size as per IS and having proper locking arrangement in front side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including cable glands of suitable size for incoming and outgoing cables and comprising with and including following accessories and mounted on PCC Plat form min 45 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.5 m all round the panel board including dismantling old unsv LT feeder piller box / busbar chamber etc complete with the following items housed in :- BUSBAR :- 400 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite / DMC insulator bus bar support (Square / round) insulators of suitable size and good insulation resistance (Busbar to MCCB shall be connected through suitable size of copper busbar). INCOMING:- (i) 4 pole MCCB of capacity 400 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 35/36 KA with thermal megnatic release type - 01 No. (ii) Digital multifunctinal meter V, A, F, kW- 01 No. (iii) Indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (iv) CT (200/5A) -03 Nos OUTGOING:- (a) 4 pole MCCB of capacity 200 Amp, breaking capacity 25 KA with thermal magnetic release - 02 Nos a) 2 pole MCCB of capacity 100 Amp, breaking capacity 25 KA with thermal magnetic release, adjustable type e - 03 Nos.
S&F of Bus bar chamber with door type of size 400 x 380 x 190 mm made out of MS sheet 3mm thick with Copper bus bar three phase & neutral each 320 x 20 x 6 mm of size fixed on insulators and fixing on steel pole with proper clamps, nuts , bolts & washers of required size and making connection of LT cables with thimbles, glands and making good the disturbed surfaces incl water proof PVC sticker like danger mark all as required at site.
Supply and fix in replacement of aluminium strip 25 x 3.15 mm with saddles and fixing screws, insulators rawal plugs etc for conductor for roof and fixed on wall upto test point all as specified.
Supply and fix in replacement of galvanized iron strip 32 x 6 mm fixed with saddles & fixing screws, PVC dash fastners, insulators fixed from test point to earth on walls or burried in ground /drawn into hume pipe. NOTE : Excavation & earth work shall be measured and paid for seperately under relevant item of schedule. complete all as specified and directed.
Supply and fix in replacement of wooden block heavy weight of size 30x30x30 cm with hole of 20 cm for fixing of air termination rod of any size incl dismantling and taking down old existing unserviceable wooden block complete all as specified and directed.
Supply and fix in replacement of GI tubes light grade, galvanised, 20 mm bore including necessary GI fittings, laid in trenches or under floor or fixed with poles/walls for fixing of air termination incl dismantling and taking down old existing unserviceable GI tubes light grade complete all as specified and directed.
Supply and fix in replacement of five pointed air termination Aluminium rod 12mm dia, 300 mm long complete all as specified and directed.
Supply and fix in replacement of Test point terminal block made of gun metal or phosphorous bronge 75 x 75 x 25mm of 6mm thickness drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws including box of size 90 x 90 x 90mm made of 1.6mm plain sheet and screwed to wall for protection of test point completed all as specified.
Supply, fix in replacement, connecting and testing of MCCB 100 Amps and 25 KA 4 pole.
Supply, fix in replacement, connecting and testing of MCCB 63 Amps and 25 KA 4 pole.
Supply, fix in replacement, connecting and testing of MCCB 315/320 Amps and 36 KA 4 pole.Make
Supply, fix in replacement, connecting and testing of MCCB 250 Amps and 36 KA 4 pole.
Supply, fix in replacement, connecting and testing of MCCB 200 Amps and 36 KA 4 pole.
Supply, fix in replacement, connecting and testing of MCCB 160 Amps and 25 KA 4 pole.
Supply and fix in replacement cable lug suitable for 10 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed..Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 16 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed..Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 25 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed. Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 35 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 50 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 70 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 95 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 120 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed. Make: Dowells/AXIS/INDIAN
Supply and fix in replacement cable lug suitable for 150 Sqmm cable with made of copper including nut,bolt and washer complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement HT tape roll 10 mtr long x 5 cm wide complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement LT tape roll 10 mtr long x 5 cm wide complete all as specified and directed.Make:Dowells/AXIS/INDIAN
Supply and fix in replacement Anchor clamp suitable for 70 Sqmm to 95 Sqmm cable as per site requirment complete all as specified and directed.Make:Sintex/Hansel/Legrand
Supply and fix in replacement Suspension clamp suitable for 70 Sqmm to 95 Sqmm cable as per site requirment complete all as specified and directed.Make:Sintex/Hansel/Legrand
Supply and fix in replacement inline connector suitable for 70 Sqmm to 95 Sqmm cable as per site requirment complete all as specified and directed.Make:Sintex/Hansel/Legrand
Supply and fix in replacement cable protection suitable for 70 Sqmm to 95 Sqmm cable as per site requirment complete all as specified and directed.Make:Sintex/Hansel/Legrand
Supply and fix in replacement dead construction suitable for 70 Sqmm to 95 Sqmm cable as per site requirment complete all as specified and directed.Make:Sintex/Hansel/Legrand
Supply and Replacement in repair of Stay assembly complete with accessories i.e stay plate 300mm x 300mm x 6mm, galvanized thimbles, G.I. stay wire 7/4 SWG, loop type insulators, vitreous porcelain, white brown or green of large size with overall dimensions 90mm x 140mm, clearance of hole 25.5mm, etc and all other accessories as shown in electrical plate No.1 on Ser Page No.19-47 of MES Schedule Part-I complete. Note : Stay clamp, excavation and earth work and concrete for stay pit and insulator shall be measured and paid for separately.
Repair, maint and of broken doors for LT panel and bus bars by welding and incl fixing of new hinges and other material as required at site complete all as spfd and directed.
M&L in replacement copper bus bar rating 200 Amps 25/3mm including making whole suitable for panel with tape insulation of suitable colour in Phase RYB & neutral in Black colour complete all as specified and as directed by Engr-in-Charge,
M&L in replacement aluminium bus bar rating 200 Amps 25/6 mm including making whole suitable for panel with tape insulation of suitable colour in Phase RYB & neutral in Black colour complete all as specified and as directed by Engr-in-Charge,
Supply and fix in replacement of High power LED street light 60 Watt IP 66 Energy saving & environmental friendly long life Versatile pressure die-cast aluminium roadway luminaire with high power LEDs as light source and electronic driver fixed on pole/wall along with service bracket as per sample, clamps as directed, nuts, bolts, and washers as directed incl electric connection with 1.5 Sqmm multistranded twin core alum cable PVC insulated from junction box to street light by laying in bracket/ pipe/ pole complete all as spfd. Make : Havells/Surya/Bajaj
Supply and installation, connecting eclectically & commissioning in replacement of LT feeder pillar box outdoor type of size 0.90 x 0.60 x 0.50 Mtr size factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of size 0.30x0.30x0.50 mtr- 04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 200 amps rated copper bus bar suitable for 3 phase 4 wire supply system duly drilled holes and making all cable connection with proper thimbles mounted on epoxy based post insulators and one MCCB 200 Amps 4 pole 415 Volt, 35/36 KA.
Bedi Refrigeration Works
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .