| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | As L1₹14.8 LAccepted-AOC 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | As L1 | Accepted-AOC L1 | |
| 2 | As L3Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | As L3 | Rejected-Finance As L3 | |
| 3 | As L4Rejected-Finance | As L4 | Rejected-Finance As L4 | |
| 4 | As L2Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | As L2 | Rejected-Finance As L2 |
Tender Value
₹23.0 L
EMD Value
₹46,004
Closing Date
7 Aug 2018, 9:00 amClosed
Executive Engineer PWD BDN ELEC DIVN
Room no 1081st fl purta bhawan salt lake kolkata
Proposed Gplus5 storied Administrative Building for WBCHSE and WBCSC at plot No DG 10 by 1 in AA I New town Kolkata SITC of fire Detection system
2018_WBPWD_181048_1
WBPWD/EE/BED/25/e-IT of 2018_19
Open Tender
ELECTRICAL WORKS M/R
Item Rate
30 days
WBCHSE and WBCSC
Please refer Tender documents.
4 documents required · 4 mandatory
₹46,004
Yes
24 Sept 2021
11 Jul 2018
10 Aug 2018
17 Jul 2018
7 Aug 2018
17 Jul 2018
Amount
Supply installation Testing & Commisioning of EN -54 standard VDS/LPCB Approved Microprocessor based 4 Loops expandable up to minimum 6 Loops fire alarm control panel fully networkable with each loop capable of taking atlesast 125 devices and each loop should be connected to a dedicated loop card (even if a loop card supports multiple loop the panel should be provided with 4 nos loop cards and should have provision for accomodating total 6 nos loop card) 1/4 VGA display character alpha numec liquid crystal disply the panel shall be soft addressable type the panel shall be able to ngive pin point location of all fire/fault conditions Further the panel must be ablle to automaticlly switch off respective control switches when ever any alarm is triggered the panel shall have in built rectifier provision for external & internal printer (if required )loop cards , LCD unit to indicate Fire/ Fault Signal with address and analog output complete in all respects, having minimum 1000 event memory interal SMF lead acid batteries with sealed cell of 24V/ 12V with integral battery charger complets required and as per specification (Approved Make:Honeywell/Bosch / Seoutron/ Siemens)
Supply installation Testing & Commisioning of EN -54 standard VDS/LPCB Approved Addressable Multi sensor Detector (optical smoke as well as heat ) with inbulit / additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel with Mounting Base as rqequired with the protection category of IP40 (Approved Make:Honeywell/Bosch / Seoutron/ Siemens)
Supply installation Testing & Commisioning of EN -54 standard VDS/LPCB Approved intelligent Analog Addressable Heat Deetector (Static+ ROR) with inbulit/ additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commuicate 3 danger levels for differentiated alarm activation. Detector should have unquie address for communication and assigned through panel with Mounting Base as required with the protection category of IP 40 (Approved Make: Honeywell/Bosch / Seoutron/ Siemens)
Supply installation Testing & Commisioning of Respones indicator with all other accessories (Approved Make:Honeywell/Bosch / Seoutron/ Siemens)
Supply installation Testing & Commisioning of EN -54 standard VDS/LPCB Approved inteligent addressable manul call point with inbilt /additional isolator suitable for flush or surface mounting call point shall include test key feature without removing the glass Also should have protection category of IP44 and extra acceesories as required (Approved Make:Honeywell/Bosch / Seoutron/ Siemens)
Supply installation Testing & Commisioning of EN -54 standard VDS/LPCB Approved Addressable one input &one output module with inbuilt/additional isolator and shall have the LED indication for Normal. Fault test and activation the module shall have the option for configuration as fail safe operation (Approved Make:Honeywell/Bosch / Seoutron/ Siemens)
Supply & Drawing of 2 core 1.5 sq mm FRLS shieled copper cable( Make. Finolex/ Technoflex/ MEMKEI)
Supply & Laying of 20 mm FR PVC regid conduit pipe on the surface of the wall (Make;Precisson/ Prestoplast Medium)
L.W.C. must be quoted manually @1% on the total quoted value else the total quoted rate shall be treated incl. LWC as per rule. N.B. Rate should be quoted inclusive of GST.
PERFECT IMAGE SOLUTIONS
GLYPTIC
L. N. ENGINEERS CO-OPERATIVE SOCIETY LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .