| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹10.8 LAdmitted-Finance | -45.99% | ₹10.8 L | L1 | Admitted-Finance |
| 2 | L2₹12.4 LAdmitted-Finance | -38.20% | ₹12.4 L | L2 | Admitted-Finance |
| 3 | L3₹15.1 LAdmitted-Finance | -24.56% | ₹15.1 L | L3 | Admitted-Finance |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
6 Feb 2026, 1:00 pmClosed
EE PHED CITY DN IV JODHPUR
EE PHED CITY DN IV JODHPUR
Annual Rate Contract for Electrical Maintinance work in all City Sub Division under City division IV Jodhpur
2026_PHCJO_534004_1
EE NIT 55/2025-26
Open Tender
Civil Works - Water Works
365 days
EE PHED CITY DN IV JODHPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
EE PHED CITY DN IV JODHPUR
₹40,000
Yes
13 Feb 2026
31 Jan 2026
6 Feb 2026
31 Jan 2026
6 Feb 2026
31 Jan 2026
PWD electric BSR 2022 1.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 1.1.1 Short point (up to 3 mtr.)
1.1.2 Medium point (up to 6 mtr.)
1.1.3 Long point (up to 10 mtr.)
PWD electric BSR 2022 4.7 P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 4.7.2 2.5 Sq.mm 3 core flat / Round
4.7.3 4.0 Sq.mm 3 core flat / Round
4.7.4 6.0 Sq.mm 3 core flat / Round
4.7.5 10.0 Sq.mm 3 core flat / Round
4.7.6 16.0 Sq.mm 3 core flat / Round
PWD electric BSR 2022 6.1 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 6.1.1 Single pole MCB (With B/C curve tripping Characteristics) 6.1.1.2 6 A to 32 A rating
PWD electric BSR 2022 6.1.2 Double pole MCB(With B/C curve tripping Characteristics) 6.1.2.2 6 A to 32 A rating
PWD electric BSR 2022 6.1.2 Triple pole MCB (With B/C curve trippingCharacteristics) 6.1.3.4 50/63 A rating
PWD electric BSR 2022 8.2 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 8.2.2 Electrolytic grade (Cu-ETP) Tin Coated annealed copper bus bars IACS 100% grade
PWD electric BSR 2022 8.3 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 8.3.1 Single Phase Ammeter
8.3.2 Single Phase Voltmeter
PWD electric BSR 2022 8.14 Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 8.14.1 3 pole Power contactors with following AC 3 Rating 8.14.1.2 13 to 25 Amp
PWD electric BSR 2022 8.18 Providing & Fixing of thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 8.18.2 14 to 23 Amp
8.18.3 20 to 33 Amp
8.18.4 24 to 40 Amp
8.18.5 36 to 60 Amp
8.18.6 45 to 75 Amp
8.18.7 66 to 110 Amp
PWD electric BSR 2022 9.3 SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 9.3.1 3 pole MCCB With Thermal Magnetic release 9.3.1.2 up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
9.3.1.5 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
9.3.1.6 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
9.3.1.8 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
9.3.1.9 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting,
PWD electric BSR 2022 12.4 Supplying and making end termination with heavy duty Copper lugs ( ANY type ) confirming to IS 8337 -1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 12.4.4 6.0 Sq.mm
PWD electric BSR 2022 13.1 Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 13.1.1 3 core 95.0 Sq.mm
13.1.2 3 core 120.0 Sq.mm
13.1.3 3 core 150.0 Sq.mm
13.1.4 3 core 185.0 Sq.mm
PWD electric BSR 2022 18.11 Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 18.11.5 High Power LED Flood Light Minimum lumen output 12400 lm
18.11.6 High Power LED Flood Light Minimum lumen output 14800 lm
18.11.7 High Power LED Flood Light Minimum lumen output 18650 lm
E250216 : Servicing and overhauling of 20" sweep desert cooler including oiling, greasing, painting of tank from inside with rubber paint after properly desmantling each assembly and refixing the same as required.
E250218 : Replacement of cooler pads (heavy) set of 3 no. of size 25" x 27"
E250242 : P & F vertical pump suitable for 20" desert cooler including making connection testing etc. as required. ISI marked vertical pump
E250103 : Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. (New model ceiling fan) 1500 mm sweep (New model ceiling fan)
E250104 : Do ----- All sizes (Old model ceiling fan)
E130433 : Providing & making cold shrinkable type indoor/outdoor/straight through terminations/joint kit of group 1 and approved make suitable for XPLE insulated 11/33 KV cable with required components , prepration of cable ends, testing etc. as required of following sizes. 3 core 120/150/185/225 Sq.mm
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.98 MB
TDNIT55.pdf
Tender Documents • 2.67 MB
BOQ_951515.xls
BOQ • 0.46 MB