Additional Chief Engineer (P&C)
Supply, Erection, Testing and Commissioning of 2 nos. of 220KV Feeder Bays on EPC basis excluding civil works at 220KV Virpore SS under Navsari Circle for Virpore-Navapura TSS line 1 & 2 for deposit work of M/s Western Railway under Open Access (Option-1A)
268464
ACE(P&C)/Contract/220kV FB at 220KV Virpore S/S/E-423
Open
Electrical
Works
Vadodara
28 documents required · 21 mandatory · 7 optional
₹11,800
Gujarat Energy Transmission Corporation Limited.
₹3 L
5 Feb 2026
5 Feb 2026
5 Feb 2026
26 Feb 2026
5 Feb 2026
complete the job shall be included and shown in technical bid.
2)*Ethernet switches shall have as many spare ports as utilized ports.
3) ** PLCC / FOTE BCU shall have sufficient I/Os as per given list considering future lines also.
4) Contractor shall be responsible for necessary co-ordination with FOTE and OPGW supplier & erection agency
to establish remote connectivity and over all operation from Master Control Centre through SCADA system.
5) @ Communication channel between C & R Panel Relays and FOTE Panel ports with required LIUs in both
Panels is in scope of bidder. Separate Armoured F.O. cable for each relays shall be laid between C & R Panel
and FOTE Panel.
PROTECTION BOQ - under deposit work for erection of 02 Nos. of 220kV TSS Feeder Bay at 220kV
Sr. Erectio Supply
Particulars of Item Unit
No. n Qty. Qty.
Supply, Erection, Testing and Commissioning of Protection equipments and materials as per
A respective technical specifications and relevant special conditions and suitable for One Main and
One Main cum Transfer Bus system on 220kV side
Control & Relay Panels (having IEC 61850 compliant IEDs) for 220kV Bays (Control Voltage - 220V DC )
as per tech specifications with following break up
1) Control & Relay panel for line with Distance protection relays as Main-I & Main-II Set 2
2) Control & Protection panel for Transformer with Differential Set 0 -
3) Control & Protection panel for TBC Set 0 -
4) Control & Protection panel for BC cum TBC Set 0 -
Busbar Protection Augmentation Augmentation of existing Numerical Busbar
protection scheme Siemens Make 7SS522 by providing 02 Nos. of Busbar Bay units (Siemes Make
7SS523 compatible with existing CU & PU) along with all required accessories and installation, testing
commissioning of complete Busbar protection scheme in all respect.
[CU is mounted in one of the existing bay control & protection panel while PUs shall be mounted in
respective bay control and protection panels as shown in panel GA drawing]
3 GPS based Time Synchronising Unit (IEC 61850 compatible) Set 0 -
GETCO/E/2S-250/220kV VIRPORE SS/BOQ/R0, DT-22.07.2024 Page 3 of
SWITCHYARD BOQ FOR 220KV VIRPORE SUBSTATION:- (FOR 2 NOS.220KV NAVAPUR-TSS BAYS)
SCOPE OF WORK:-
1) 2 NOS. 220KV NAVAPUR-TSS FEEDER BAYS ADDED OF M/S WESTERN RAILWAY BY OVERHEAD LINE i.e 1 NO. BAY ADDED IN EXISTING
220KV BUS ARRANGEMENT AT ADJOINING OF EXISTING 220KV ACCHALIYA LINE-1 BAY & 1 NO. BAY ADDED BY 220KV BUS EXTENSION .
2) PROP. LINE FLYOVER FOR 220KV FUTURE LINE-1 .(i.e- 3 Phase bay cosider )
Sr. Erectio Supply
Particulars of Item Unit
No. n Qty. Qty.
Supply, Erection, Testing and Commissioning of Protection equipments and materials as per
B respective technical specifications and relevant special conditions and suitable for Two Main Bus
system on 66kV side
Control & Realy panels for 66kV Bays ( Control Voltage - 220V DC ) as per tech specifications with LED
type Semaphore & suitable for AIS switchgear modules with following break up
1) Control & Relay Panel for 66kV lines Set 0 -
2) Control & Relay Panel for Transformer With Differerential Relay (For 66/11kV Transformer) Set 0 -
3) Control & Relay Panel for Transformer W/O Differerential Relay (For 220/66kV TRF) Set 0 -
4) Control & Relay Panel for BC Set 0 -
5) Control & Relay Panel for Capacitor bank Set 0 -
6) Under Frequency Panel** Set 0 -
Supply, Erection, Testing & Commissioning of General purpose equipments and materials as per
C respective technical specifications and relevant special conditions and suitable for Two Main and
One Main cum Transfer Bus system on 220 kV side and Two Main Bus system on 66kV side
1 DCDB-220 V with 35 Feeder No. 0 -
2 DCDB-220 V with 20 Feeder No. 0 -
3 DCDB-220 V with 20 Feeder No. 0 -
4 LTPB (SCADA compatible) No. 0 -
Supply, Installation, Testing and Commissioning of materials/item for Power Cable and Control
Cable including preparation of wiring schedule
Supply and Laying of 1.1 kV PVC armoured copper/Aluminium control/LT power cable in trench including
binding/clamping of cable with PVC lockable wire tie as per requirement including supply and fixing of
identification tags at both ends and at distance of every 100mtr.
(Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type)
1) 2c x 2.5 mm2, armoured copper control cable # Mtr. 350
2) 2c x 4 mm2 , armoured copper control cable # Mtr. 400
3) 4cx2.5 mm2, armoured copper control cable # Mtr. 650
4) 4c x 4 mm2 , armoured copper control cable # Mtr. 800
5) 7c x 2.5 mm2, armoured copper control cable # Mtr. 150
6) 12c x 2.5 mm2, armoured copper control cable # Mtr. 280
7) 12c x 4 mm2, armoured copper control cable # Mtr. 400
8) 19c x 2.5 mm2 , armoured copper control cable # Mtr. 650
9) 27c x 2.5 mm2, armoured copper control cable # Mtr. 100
10A) 1 x 50 mm2 , armoured copper cable Mtr. 0 -
10B) 4C x 10 mm2 , armoured copper control cable Mtr. 0 -
11) 4 x 10 mm2 , Al. armoured LT cable Mtr. 0 -
12) 3.5 x 25 mm , Al. armoured LT cable# Mtr. 150
13) 3.5 x 50 mm2 , Al. armoured LT cable Mtr. 0 -
14) 3.5 x 120 mm2 , Al. armoured LT cable Mtr. 0 -
15) 1C x 150 mm2 , Al. armoured LT cable Mtr. 0 -
16) 1C x 240 mm2 , Al. armoured LT cable Mtr. 0 -
17) 1C x 300 mm2 , Al. armoured LT cable Mtr. 0 -
18) 3.5 x 300 mm2 , Al. armoured LT cable Mtr. 0 -
Termination of the Control and Power cable at panel / MK box/equipment including PVC binding, dressing,
shaping, drilling of holes in panels for glands nuts, providing of glands for following size. The work also
includes looping in Panel and MK box by using crimping type lugs of suitable size with ferruling (machine
2 printed) with proper size of copper cable wire. The loops should be bunched by using button tape and proper
1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size# No. 150 -
2) cables above 7 core # No. 100 -
Laying of 1.1kv PVC/XLPE armoured Al. LT power cable in ground by digging trench of suitable width and
450 mm depth with providing and fixing of brick and sand layer covering the cable in any type of soil and
Laying of 1.1kv PVC armoured copper control cable in heavy duty PVC pipe of suitable size buried in
3 ground by digging trench of suitable width and 450 mm depth in any type of soil including supply and fixing
of Pipe and identification tags at distance of every 100 Mtrs for following size
1) Control Cables upto 7 core # Mtr. 200 -
2) Control Cables above 7 core and all LT cables # Mtr. 350 -
GETCO/E/2S-250/220kV VIRPORE SS/BOQ/R0, DT-22.07.2024 Page 4 of
SWITCHYARD BOQ FOR 220KV VIRPORE SUBSTATION:- (FOR 2 NOS.220KV NAVAPUR-TSS BAYS)
SCOPE OF WORK:-
1) 2 NOS. 220KV NAVAPUR-TSS FEEDER BAYS ADDED OF M/S WESTERN RAILWAY BY OVERHEAD LINE i.e 1 NO. BAY ADDED IN EXISTING
220KV BUS ARRANGEMENT AT ADJOINING OF EXISTING 220KV ACCHALIYA LINE-1 BAY & 1 NO. BAY ADDED BY 220KV BUS EXTENSION .
2) PROP. LINE FLYOVER FOR 220KV FUTURE LINE-1 .(i.e- 3 Phase bay cosider )
Sr. Erectio Supply
Particulars of Item Unit
No. n Qty. Qty.
“Supply, Erection, Testing and Commissioning of Modular Variable-diameter Cable sealing system as per
respective technical specification and relevant special conditions wherever the electrical / instrumentation /
communication / LT Power cable underground and over-ground enter or leave bay kiosks / control room of
substations / cable trench / basement.
Nos. of Module to be supplied per cable entry in yard kiosk as well control room shall be as mentioned in
tender drawing No. GETCO / E / 2S-250 / P-033.*
Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control
cable of CT/PT/CVT etc. equipments including fixing with structures up to plinth level as per instruction of
Engineer-in-charge.
2) 220 kV Switch Yard Mtr. 50
3) 66 kV Switch Yard Mtr. 0 -
4) 11kV Switch Yard Mtr. 0 -
Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control
cable of CB, Isolator, Earth Switch etc. equipments including fixing with structures up to plinth level as per
instruction of Engineer-in-charge.
2) 220 kV Switch Yard Mtr. 50
3) 66 kV switch yard Mtr. 0 -
4) 11kV Switch Yard Mtr. 0 -
5 Providing and fixing bay MK as per tech spec No. 2
Providing and fixing Yard LT ACDB as per tech spec -with 20 OG feeders (to be provided in 220 kV & 66 kV
7 Providing and fixing Yard LT ACDB as per tech spec -with 12 OG feeders No. 0 -
8 Providing and fixing of CT-PT/CVT JB as per technical specification
1) PT JB (220kV - 2 no., 66 kV - 2 no., 11kV Yard - 1 no.) No. 0 -
2) CT JB (66 kV - 12 no., 11kV Yard - 1 no.) No. 0 -
3) CVT JB (For 400 kV Line) No. 0 -
1.# The quantities of control and power cables shown in the BOQ are based on typical cable philosophy. Hence, the
2. All the cables shall be laid through minimum possible route and accordingly the quantity of cables shall be calculated and
3* The cable sealing system Module quantity & Frames are standadized as per O.N.No : GETCO/CE(Engg)/V/C /O-006881
FOTE BOQ for requirement of 2 x 25kV, 3- Pahse Power Supply for existing Navapur TSS at 220kV system instead of
Line Detail: 220kV Virpur ( GETCO S/S) to Navapura, overhead line with OPGW of 36 KM length
Sr.N Description Unit
SDH FOTE - STM-1 system with following configuration, Approved Make: 1) ABB India Ltd, Package
(A) FOTE: FOX 615 & Teleprotection: NSD 570 and 2) GE T&D India Ltd, FOTE : e-
terragridcom e-DXC & Teleprotection: e-terragridcom DIP
19" Rack with dual power input & 8 Ports of 10/100 BaseT Fast Ethernet with L2 switch Nos
1 functionality & interface for 8 E1 ports with engineering order wire phone.(Make & Model: Matrix
2 Power Supply card(-48VDC)
2a 220V DC to -48V DC Converter (Depending on sub-station Voltage) Nos
2b 110V DC to -48V DC Converter (Depending on sub-station Voltage)
3 Control Card with alarm cables and terminal Nos
4 4 Port STM-1 OLTE Nos
Optical SFP ( i.e S1.1, L1.1,L1.2,U1.2, V1.2/X 1.2 etc including other SFPs which require to meet
4a configuration & confirming to ITU-T standard) ,Optical Boosters, Optical wave length translator,
Pre amplifier etc.
GETCO/E/2S-250/220kV VIRPORE SS/BOQ/R0, DT-22.07.2024 Page 5 of
SWITCHYARD BOQ FOR 220KV VIRPORE SUBSTATION:- (FOR 2 NOS.220KV NAVAPUR-TSS BAYS)
SCOPE OF WORK:-
1) 2 NOS. 220KV NAVAPUR-TSS FEEDER BAYS ADDED OF M/S WESTERN RAILWAY BY OVERHEAD LINE i.e 1 NO. BAY ADDED IN EXISTING
220KV BUS ARRANGEMENT AT ADJOINING OF EXISTING 220KV ACCHALIYA LINE-1 BAY & 1 NO. BAY ADDED BY 220KV BUS EXTENSION .
2) PROP. LINE FLYOVER FOR 220KV FUTURE LINE-1 .(i.e- 3 Phase bay cosider )
Sr. Erectio Supply
Particulars of Item Unit
No. n Qty. Qty.
5 Optical Fibre Patch cords (10 mtrs) Nos
Stand alone Teleprotection equipment with 8 Nos. Tx & Rx independent command inputs &
6 outputs (4 commands/card) for interconnecting with Relay of DPS along with suitable interface Nos
for integrating with multiplexure on E1 port of interface at SDH level.
7 8 Port 10/100 BaseT Fast Ethernet Card + 1 GbE+ L2 switch Nos
8 Fully Wired Cabinet for FOTE with engineering order wire phone Nos
(B) Mandatory Spares for FOTE Sets
1 Power Supply card(-48VDC) Nos
220V DC to -48V DC Converter or 110V DC to -48V DC Converter (Depending on sub-station Nos
2 Control Card with alarm cables and terminal Nos
3 4 Port STM-1 OLTE Nos
Optical SFP ( i.e S1.1, L1.1,L1.2,U1.2 including other SFPs which require to meet our
4 configuration & confirming to ITU-T standard) ,Optical Boosters, Optical wave length translator,
Pre amplifier etc.
5 Optical Fibre Patch cords (10 mtrs) Nos
Stand alone Teleprotection equipment with 8 Nos. Tx & Rx independent command inputs &
6 outputs (4 commands/card) for interconnecting with Relay of DPS along with suitable interface Nos
for integrating with multiplexure on E1 port of interface at SDH level.
8 Port 10/100 BaseT Fast Ethernet Card + 1 GbE+ L2 switch
C Erection, Installation, testing & Commissioning of FOTE No.
Make & Model of FOTE Equipment at both Sub-station end shall be same.
(1) LCT (Local Craft Terminal- Laptop) with EMS software shall have to be supplied by Manufacturer free of
cost for local as well as remote configuration of FOTE equipment.
OEM will have to submit confirmation in written for following.
(1) The bidder shall furnish the copies of valid type test reports for the offered equipment from NABL
accredited Laboratory or KEMA type tested.
(2) The bidder should have to confirm for guarantee of 5 years from the date of receipt of equipment in store
in good condition or three years from the date of commissioning of offered FOTE (Operational for
Speech+DATA+Protection + Remote SCADA over OPGW) at respective Sub-station which ever will be
(3) The bidder should have to confirm the service and spares support for at least 10 years after the
guarantee period.
(4) Make & Model of FOTE Equipment at both Sub-station end shall be same.
GETCO/E/2S-250/220kV VIRPORE SS/BOQ/R0, DT-22.07.2024 Page 6 of
SWITCHYARD BOQ FOR 220KV VIRPORE SUBSTATION:- (FOR 2 NOS.220KV NAVAPUR-TSS BAYS)
SCOPE OF WORK:-
1) 2 NOS. 220KV NAVAPUR-TSS FEEDER BAYS ADDED OF M/S WESTERN RAILWAY BY OVERHEAD LINE i.e 1 NO. BAY ADDED IN EXISTING
220KV BUS ARRANGEMENT AT ADJOINING OF EXISTING 220KV ACCHALIYA LINE-1 BAY & 1 NO. BAY ADDED BY 220KV BUS EXTENSION .
2) PROP. LINE FLYOVER FOR 220KV FUTURE LINE-1 .(i.e- 3 Phase bay cosider )
Sr. Erectio Supply
Particulars of Item Unit
No. n Qty. Qty.
(3) The bidder should have to confirm the service and spares support for at least 10 years after the
guarantee period.
(4) Make & Model of FOTE Equipment at both Sub-station end shall be same.
Description of Material Unit n qty
1 220kV ,4400PF CVT (having two windings with VA burden 50 & 50 and
accuracy of 0.2 & 3P class for metering & Protection core respectively.The
arrangement of metering core shall be provided in seperate sealable
compartment with locking facility. Clamp/connectors, porcelain insulator & nos 2
supporting structure shall also be supplied.
GETCO/E/2S-250/220kV VIRPORE SS/BOQ/R0, DT-22.07.2024 Page 7 of
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Public Procurement Circular of GOI.pdf
5. SD cum PBG Format.pdf
TS SS STR R11 22.06.2022.pdf
AL59 ZEBRA and MOOSE GETCO- R3 Print copy.pdf
EARTH WIRE - R4 - Print copy.pdf
EARTH WIRE ACCESSORIES 7-3.15 PRINT COPY.PDF
G.I. EARTHING STRIPS.PDF
HW and ACCS AL59 CONDUCTOR PRINT COPY R2 JULY 2022.pdf
LT Control and Power Cable Print COPY.PDF
MQP SUPPLIER COPY.PDF
MS PLAIN and TOR BAR.PDF
R1 - STEEL DRUM .pdf
R5 - Silicon Rubber Insulator - Print Copy.pdf
SS HW 220 and 400KV SS PRINT COPY.PDF
WEDGE CONNECTORS R1 July-22.pdf
220 132 KV and 66kV CB (R5) with FDN plan.pdf
220 kV CT and PT R10 Jun -22.pdf
400 220 132 66 KV BPI R4 June-22.pdf
400 220 132 kV LA R6 June 22.pdf
400 220 132 kV DB Tandem Isolator R6 June 22.pdf
Terminal Connectors R2 June 22.pdf
220 KV CVT with HPI- R5 Jun 22.pdf
Typical 220kV Line (AIS).pdf
Typical 220kV Single Line Diagram (AIS) SLD.pdf
Typical BUSBAR Monitoring View for 400-220kV Substation With SCADA .pdf
Typical Kiosk Monitoring View for 220kV AIS-HYBRID Substation With SCADA .pdf
(AC) POWER CABLE BLOCK DIAGRAM -Model.pdf
(DC) POWER CABLE BLOCK DIAGRAM -Model.pdf
220kV PSLD.pdf
Board Formation and Panel Arrangement in Yard Kiosk-DT. 29.10.2024.pdf
SCADA FO NETWORK R0-DT. 29.10.2024.pdf
TYP.CABLE BLOCK DIAGRAM (220 KV )-Model.pdf
Addendum - I - SAS and SAS Equipments - R9 Jan 25.pdf
Addendum - I to C And P Panel spec R7.pdf
Final TS - SAS And SAS Equipments - R9 Jan 2025.pdf
TS - AC System for Kiosk - R1 June 22.pdf
TS - Bay Control and Protection Relays (IEDs) R2.pdf
TS - Bay MK - R2 June 22.pdf
TS - Cable Sealing System Specification.pdf
TS - FOC - R2 June 22.pdf
TS - General Technical Requirement of YARD KIOSK - R2 June 22.pdf
TS For 765 400 220 132 66 33 And 11 kV Control And Protection panel - R7 April-25.pdf
R1-LAYOUT SECTION OF 220KV VIRPORE SS DT 22.7.24-Model.pdf
R1-SLD OF 220KV VIRPORE SS R1 DT. 22.07.24-Model.pdf
R4-PART LAYOUT PLAN - 220kV VIRPOR(VYARA) DT22.07.24-R4-PART LAYOUT.pdf
Connection Of Four Electrode Method Of Measuring Soil Resist.pdf
DETAILS OF EARTHING FOR D.P.STRUCTURE-Model.pdf
DETAILS OF PANEL EARTHING-Model.pdf
EARTHING NOTES-Model-3.pdf
EARTHING NOTES-Model-4.pdf
MAINTENANCE FREE EARTHPITS R3 29.05.20-Normal Soill.pdf
MAINTENANCE FREE EARTHPITS R3 29.05.20-Rocky Soill.pdf
MEASUREMENT OF EARTH RESISTIVITY-Model.pdf
R1 Lightning Arrestor DT 070916.pdf
R1 TYPICAL EARTHING ARRANGEMENT FOR CVT-PT DT 070916 .pdf
R1 Typical Earthing Arrangement for Power Tran DT 070916.pdf
SLIDING GATE-Model.pdf
Standard Earthing Philosophy of GETCO R1 010708.pdf
Standard Guideline for Earthing of EHV SS- GETCO R3 250517.pdf
TS-Maintenance Free Earthpit 040615.pdf
TYPICAL ARRANGEMENT OF EARTH TEST PIT(CHEAK PIT)-Model.pdf
Typical Arrangement of Riser for Earthing System-Model.pdf
Typical Arrangement of Welding Joint(NEW)-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR BMK-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR BPI-Model.pdf
Typical Earthing Arrangement for Circuit Breaker-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR CT-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR EQUIPMENT OF CAPACITOR BANK.pdf
TYPICAL EARTHING ARRANGEMENT FOR ISO.-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR LM-Model.pdf
Typical Earthing Arrangement for Switch Yard Gate-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR TOWER WITH PEAK-Model.pdf
TYPICAL EARTHING ARRANGEMENT FOR TOWER WITHOUT PEAK-Model.pdf
TYPICAL EARTHING ARRANGEMENT OF CABLE TRENCH-Model.pdf
TS Cable Tray.pdf
TS General Erection R1.pdf
TS ILLUMINATION- R9 25.07.22.pdf
TS-Insulating Mat 270312.pdf
TS-Maintenance Free Earthpit 04.06.15.pdf
BOQ For Ref..pdf
Breakup BOQ For Ref..pdf
Form for Networth Annual turnover LA (3).pdf
1. Form of LD undertaking 1A (2).pdf
2. Form of LD undertaking 1B (2).pdf
2. Part 1 E-423 for 220KV Navapura FB at Virpore SS.pdf
3. Ammendment -1 of E-423 for 220KV Navapura FB at Virpore SS.pdf
PP-220kV VIRPORE SS.pdf
1. Tender Notice E-423 for 220KV Navapura FB at Virpore SS.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .