Online UPS Online UPS ( 1 ) Technical Specifications Specification Specification Name Values Allowed Values GENERIC Rating in KVA (KVA) 15.0 KVA 15.0 KVA Technology IGBT-PWM with inbuilt isolation transformer MOSFET-PWM with inbuilt isolation transformer
IGBT-PWM with inbuilt isolation transformer
IGBT-PWM without inbuilt isolation transformer Input Power Three phase 300 V - 450V sinewave
50Hz Three phase 300 V - 450V sinewave
50Hz Output power 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz Backup time (Minutes) 60 60 Minimum VAH (VAH) 26000 Warranty for UPS (Years) 2 1
2
3
4
5 Movable trolly for Batteries With With
Without
Without trollery but with rack Warranty for battery 2 1
2 Degree of Protection IP21 IP21
IP20 Cabling 5 meters for With With
Without 1/4 input and out put Paralleling kit for synchronising With With
Without Installation and Commissioning Yes - CONSTRUCTIONAL Minimum thickness of M.S.Sheet Enclosure duly painted (mm) 1.2 - Type of Battery SMF-VRLA conforming to JISC:8702(Pt.I
II&III) - FUNCTIONAL Maximum overshoot and Under shoot of output rated voltage 4 - Voltage Regulation from no load to full load (%) </= 3% - 20% Overload limit for minimum 10 minutes Yes - Overall Efficiency (%) >/=90% - Total Harmonic Distortion(THD) (%) Maximum 3% - 50% Overload limit for minimum 1 minutes Yes - PROTECTION Protection for under voltage at battery terminal at 10.5V per 12 V battery. Yes - Protection of Over voltage
Short Circuit & over load at UPS output terminal Yes - METERING AND INDICATIONS Digital Metering in UPS for AC Input Voltage
Output AC Volt age
Current
Frequency
Battery Voltage and Current Yes - Indicators for mains presence
Battery charging and discharging
Output Over Load
Low Battery Voltage Yes - REPORTS AND CERTIFICATION Damp Heat : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C
two cycles of Yes - 2/4 (12+12) hours each 2007) Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes - Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes - Availability of the Type Test Report from Central Govt. NABL/ILAC Accredited lab covering all technical requirements. Yes - Type Test Certificate No. 1111 - Type Test Certificate date 01-03-2018 - Name of Lab bpe - Address of Lab dELHI - As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes - * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Vijeeshna V 685551