Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC HT CLASS CONTRACTOR KALINGA VIHAR CHHEND ROURKELA | KENDRAPARA | ODISHA | 754217 | ₹7.4 L | L1 | Accepted-AOC L1 |
| 2 | L2₹7.8 LRejected-AOC | ₹7.8 L | L2 | Rejected-AOC L2 |
| 3 | L3₹10.1 LRejected-AOC PLOT NO 08 3RD FLOOR MAHANADI VIHAR NUA BAZAR CUTTACK ODISHA 753003 | CUTTACK | ODISHA | 753003 | ₹10.1 L | L3 | Rejected-AOC L3 |
Tender Value
₹8.7 L
EMD Value
₹9,000
Closing Date
31 Jan 2026, 5:00 pmClosed
Divisional Head, Electrical Division, IDCO
Divisional Head, Electrical Division, IDCO, 8th Floor, IDCO Tower, Janpath, Bhubaneswar
SHIFTING OF 11 KV LINE ON IDC FEEDER AT APPROACH ROAD LEADING TO WORKERS HOSTEL AT KALUNGA ROAD BETWEEN RMC ROAD AND WORKERS HOSTEL KALUNGA
2026_IDCO_124931_1
BBSR/ELECT/e-149/2025-26
National Competitive Bid
Electrical Works
30 days
Workers Hostel at Kalunga
Please refer Tender documents.
3 documents required · 3 mandatory
₹4,720
₹9,000
18 Apr 2026
21 Jan 2026
2 Feb 2026
21 Jan 2026
31 Jan 2026
21 Jan 2026
Cost of Material for 11 KV Single Pole Cut Point - 3 Nos
Supply & installation of all reqd. materials for 11 mtr 150X150 RS Joist Pole 34.6Kg/m with excavation of pole pit in all kinds of soil and rock up to depth of 1/6 th of the pole-length/height & with Concreting of poles in ratio 1:1.5:3 (M-20 grade) (500mmX500mmX1500mm) = 0.375Cu.mtr & Couping of poles in ratio 1:1.5:3 (M-20 grade) (500X500X450)= 0.1125 Cu mtr along with curing as required and for supports. complete as required & as per approved technical specification and direction of EIC.
SITC of Earthing of support (Coil Type) complete as per approved technical specification and direction of E.I.C.
SITC of No 8 GI wire for earthing complete as per approved technical specification and direction of E.I.C.
Supply and installation of GI Channel 100x50x6mm,GI Angle 50x50x6mm with Fabrication & Galvanisation complete as per approved technical specification and direction of E.I.C.
Supply and Installation of Fish Plate . complete as per approved technical specification and direction of E.I.C.
SITC of GI Flat 50x6mm .complete as per approved technical specification and direction of E.I.C.
SITC of 11KV Pin Insulator, Polymer complete as per approved technical specification and direction of E.I.C.
SITC of 11kV Disc Insulator B & S (70 KN), Polymer complete as per approved technical specification and direction of E.I.C.
SITC of 11kV H/W Fitting (B & S type)(70 KN) for Disc Insulator complete as per approved technical specification and direction of E.I.C.
SITC of PG Clamp for 100Sqmm AAAC complete as per approved technical specification and direction of E.I.C.
SITC of 11 kV HT Stay Set complete including excavation of stay pit in all kind of soil and rock as required with GI HT Stay Set, Stay Clamp , Stay Insulator & 7/10 GI stay Wire & Stay Concreting ratio 1:1.5:3 (M-20 grade) (500 mm x 500mm x 800mm) = 0.2 Cu.mtr complete with curing as required & as per approved technical specification & direction of EIC.
Supply & fixing of G.I Nut, Bolt & Washers as required.
SITC of Anticlimbing Device using GI barbed wire (3kg per support) with Back Clamp (25X3 mm GI flat, 0.59Kg/Mtr. Flat of 0.510mtr length 4 no's = (4x0.59x0.510)). complete in all respect as per approved technical specification and direction of E.I.C.
Supply and installation of Danger Board using GI Back clamp (Pole-clamp) made of 25x3 mm flat flat, 0.59Kg/Mtr. Flat of 0.510mtr length 1 no's = (1x0.59x0.510). complete in all respect as per approved technical specification and direction of E.I.C.
Cost of Material for 11 KV Single Pole Pin Point - 8 Nos
Supply & installation of all reqd. materials for 11 mtr 150X150 RS Joist Pole 34.6Kg/m with excavation of pole pit in all kinds of soil and rock up to depth of 1/6 th of the pole-length/height & with Concreting of poles in ratio 1:1.5:3 (M-20 grade) (500mmX500mmX1500mm) = 0.375Cu.mtr & Couping of poles in ratio 1:1.5:3 (M-20 grade) (500X500X450)= 0.1125 Cu mtr along with curing as required and for supports. complete as required & as per approved technical specification and direction of EIC.
SITC of Earthing of support (Coil Type) complete as per approved technical specification and direction of E.I.C.
SITC of No 8 GI wire for earthing complete as per approved technical specification and direction of E.I.C.
Supply & installation of 11KV GI V-Cross arm with G.I Back Clamp for V cross arm. complete as required & as per approved technical specification & direction of EIC.
SITC of 11KV Pin Insulator, Polymer complete as per approved technical specification and direction of E.I.C.
Supply and Installation of F Clamp . complete as per approved technical specification and direction of E.I.C.
Supply & fixing of G.I Nut, Bolt & Washers as required.
SITC of Anticlimbing Device using GI barbed wire (2kg per support) with Back Clamp (25X3 mm GI flat, 0.59Kg/Mtr. Flat of 0.510mtr length 4 no's = (4x0.59x0.510)). complete in all respect as per approved technical specification and direction of E.I.C.
Supply and installation of Danger Board using GI Back clamp (Pole-clamp) made of 25x3 mm flat flat, 0.59Kg/Mtr. Flat of 0.510mtr length 1 no's = (1x0.59x0.510). complete in all respect as per approved technical specification and direction of E.I.C.
11 KV Over head Coductor
Supply and stringing of 11 KV 1 core, 100mm2 XLPE insulated AAA conductor (Unarmoured)- 0.35 Ckm .complete as per approved technical specification and direction of E.I.C.
Cost of Dismantling
Dismentling of HT line- 11 KV & return to store.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.66 MB
BID.pdf
Tender Documents • 3.24 MB
BOQ_577110.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid