| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.3 LAccepted-AOC THEERTHAM NADUVILEMURI PADANILAM POST NOORANAD ALAPPUZHA DIST KERALA 690529 | ALAPPUZHA | KERALA | 690529 | L1 | Accepted-AOC Awarded contract being lowest | |
| 2 | L2₹39.0 L+₹3.8 L (10.9%)Rejected-AOC | L2 | Rejected-AOC Not being lowest | |
| 3 | L3₹41.8 L+₹6.6 L (18.9%)Rejected-AOC | L3 | Rejected-AOC Not being lowest |
| Sl No | Description | Qty | Unit | JM Engineering L3 | TAMS ASSOCIATES L2 | Green Ray Enterprises L1 |
|---|---|---|---|---|---|---|
| 1.00 | S&F as in repairs LT Panel Outdoor type floor mounted free standing dust and vermin proof panel / DB with IP-55 protection, CPRI approved, frame fabricated out of 40mm x 40mm x 4mm angle iron, 3 mm thick CRCA sheet for entire outer panel with single door and locking arrangements & 1.6 mm for inner compartment with 40mmx4mm flat Iron, including Separate cubicle chamber with cable alley not less than 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over 2 coats of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must have thermal magnetic release, busbar chamber and switchgear compartments, Provision in cable alleys for bottom cable entry for incoming & outgoing cables, affixing MV danger plate at suitable intervals / locations including erection, testing and commissioning complete all as specified and directed including the following fixtures amd fitments mentioned against srl 1.01 & 1.02 below.
Busbars:-
TPN- Not less than 400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set. Incoming:- (i) MCCB 200 A, 4 Pole, 36KA with thermomagnetic release- 01 No., (ii) CT's 200/5 -03 No.,(iii)Multifuction meter -01 No.(vi) Phase Indicating lamps -03(vii) Control fuses / MCB -03 Nos | 1 | Each Job | 2,60,000 ₹2,60,000 | 1,25,000 ₹1,25,000 Lowest | 1,64,000 ₹1,64,000 |
| 1.01Outgoing:- Separate cubical chamber with a cable alley not less than 300 mm width for installation/connecting the following switch gear with the main bus bar using aluminium bus link or copper conductor flexible wires suitable to the switch rating and connecting outgoing terminals of the switch gear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles. (i) MCCB, 4 pole 125 A, 25 KA - 02 No (ii) MCB, 4 Pole 63 A - 08 Nos (iii) Manual.auto control switch, duly wind up to terminal block for connecting street light circuits Note:- (i) A clear space of 200 mm shall be kept from floor level for switchgear compartment. (ii) Air ventilation breathers with exhaust fan plastic body 100mm sweep to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided. (iii) Each compartment shall be numbered / lettered as approved by GE. (iv) LT panel shall be fixed in existing location and the disturbed surrounding surfaces shall be made good as per exising specifications. The cost of making good shall be deemed included in unit quoted rate. (v) Contractor shall submit the GA drawings of LT Panel for approval of GE before placing the bulk order | ||||||
| 2.00 | All as per serial item No. 1 here in before but with the following fittings & fixures :-
Busbars
TPN-400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set.
Incoming
(i) MCCB 250 A, 4 Pole, 36KA with thermomagnetic release (with release range 160-200A) -01
(ii) CT's 250/5 -03 No. with 01 selector switch -01 No.
(iii) Multifuction meter -01 No -01 No.
(iv) Phase Indicating lamps -03 No.
(v) Control fuses/MCB 32 Amp SP -03 No.
Outgoing:-
(i) MCCB, 4 pole 100 A, 16 KA - 04 Nos
(ii) MCCB, 4 pole 63 A, 16 KA - 03 Nos
(iii) MCB SPN 20 A - 02 Nos | 1 | Each Job | 2,40,000 ₹2,40,000 | 1,75,000 ₹1,75,000 | 1,54,000 ₹1,54,000 Lowest |
| 3.00 | Supply and fix in replacement of Changeover switch 100 Amp, 415volt front operated with enclosure four pole all as specified and directed | 2 | Each | 15,000 ₹30,000 | 4,800 ₹9,600 Lowest | 8,400 ₹16,800 |
| 4.00 | Supply and fix in replacement of Changeover switch 250 Amp, 415volt front operated with enclosure four pole all as specified and directed | 1 | Each | 17,000 ₹17,000 | 6,000 ₹6,000 Lowest | 20,000 ₹20,000 |
| 5.00 | Supply and fix in replacement of Changeover switch 400 Amp, 415volt front operated with enclosure four pole all as specified and directed | 1 | Each | 2,500 ₹2,500 Lowest | 10,000 ₹10,000 | 32,000 ₹32,000 |
| 6.00 | Supplying and laying synthetic Rubber insulated mats 3 mm thick for voltage upto 1.1 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) IEC/BS EN 61111: 2009 BIS/ERDA/CPRI approved suitable for electrical shock safety all as specified and directed | 25 | RM | 14,000 ₹3,50,000 | 2,000 ₹50,000 | 900 ₹22,500 Lowest |
| 7.00 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exeeding 1.5 m deep, getting out the excavated earth bottom surface to required gradient complte all as specified and directed. | 340 | Cum | 300 ₹1,02,000 | 380 ₹1,29,200 | 290 ₹98,600 Lowest |
| 8.00 | Material and Labour for removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point. | 181 | Cum | 60 ₹10,860 Lowest | 110 ₹19,910 | 260 ₹47,060 |
| 9.00 | Returning filling in, and including spreading and leveling in layers not exceeding 25 cm thick complete all as specified & directed. | 159 | Cum | 50 ₹7,950 Lowest | 100 ₹15,900 | 120 ₹19,080 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
3 Jun 2026, 1:00 pmClosed
GE(MAINT)EZHIMALA
GARRISON ENGINEER (MAINT) MILITARY ENGINEER SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310
AS PER BOQ AND TENDER DOCUMENTS
2026_MES_764828_1
GE MAINT EZHIMALA 8863
Open Tender
Civil Works
Item Rate
180 days
Ezhimala
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MAINT EZHIMALA
₹70,000
Yes
2 Jul 2026
12 May 2026
9 Jun 2026
12 May 2026
3 Jun 2026
27 May 2026
12 May 2026 - 19 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | S&F as in repairs LT Panel Outdoor type floor mounted free standing dust and vermin proof panel / DB with IP-55 protection, CPRI approved, frame fabricated out of 40mm x 40mm x 4mm angle iron, 3 mm thick CRCA sheet for entire outer panel with single door and locking arrangements & 1.6 mm for inner compartment with 40mmx4mm flat Iron, including Separate cubicle chamber with cable alley not less than 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over 2 coats of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must have thermal magnetic release, busbar chamber and switchgear compartments, Provision in cable alleys for bottom cable entry for incoming & outgoing cables, affixing MV danger plate at suitable intervals / locations including erection, testing and commissioning complete all as specified and directed including the following fixtures amd fitments mentioned against srl 1.01 & 1.02 below.
Busbars:-
TPN- Not less than 400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set. Incoming:- (i) MCCB 200 A, 4 Pole, 36KA with thermomagnetic release- 01 No., (ii) CT's 200/5 -03 No.,(iii)Multifuction meter -01 No.(vi) Phase Indicating lamps -03(vii) Control fuses / MCB -03 Nos | 1 | Each Job | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.68 MB
Tender8863.pdf
Tender Documents • 0.71 MB
BOQ_856631.xls
BOQ • 0.90 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .