Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.2 LAccepted-AOC 1573 JOYRAMPUR JALA ROAD 76 HEMANTA MUKHERJEE ROAD KOLKATA 700060 | KOLKATA | KOLKATA | WEST BENGAL | 700060 | L1 | Accepted-AOC L1 | |
| 2 | L2₹8.2 L+₹2,816.35 (0.34%)Rejected-Finance | L2 | Rejected-Finance Due to not having the lowest bidder | |
| 3 | L3₹10.1 L+₹1.9 L (23.5%)Rejected-Finance 001 SHREE HARSIDDHIKRUPA VADODARA MADANZAPA ROAD MADANZAPA ROAD VADODARA GUJARAT 390001 | VADODARA | GUJARAT | 390001 | L3 | Rejected-Finance Due to not having the lowest bidder |
Tender Value
₹8.2 L
EMD Value
₹16,460
Closing Date
16 May 2025, 10:00 amClosed
Divisional Manager
Barrackpore Division, WBSEDCL
3rd call for drawl of New feeder by laying 11kV 3CX300sqmm XLPE UG cable from Belghoria SS under Barrackpore Division, WBSEDCL.
2025_WBSED_839092_1
DM/BKPD/TECH/NIT/2025-26/03
Open Tender
MISC ELECTRICAL WORKS
Item Rate
30 days
Belghoria Substation
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹16,460
4 Jun 2025
30 Apr 2025
19 May 2025
30 Apr 2025
16 May 2025
30 Apr 2025
Amount
Survey of cable route as per instruction of site Engineer
Fixing of Pin Insulator 11KV
Microtunnelling work with laying of HDPE pipe as per instruction of site Engineer and as per site condition including supply of HDPE pipe as per IS: 4984 : 1995 including preparation and submission of As built drawing with 160mm Dia HDPE pipe, PE 80, PN-6.
Excavation of soil for formation of trial hole having minimum size 1.1 x 0.5 x 1.2 M in total cable route as per specification and direction of the site Engineer
Excavation of soil (METAL ,ASPHALT ,NORMAL SOIL) for formation of cable trench and reinstatement of the cable trench with the excavated soil after completion of laying and dressing of 1 nos 11KV 3x300 SQMM XLPE UG cable and cable protection work as per specification and direction of the site Engineer. Size of cable trench should be at least 900x500 mm and the depth must not be less than 900 mm with 75 mm sand level at the base filling the space between cable and bricks with yellow sand and protection on sides and top by 24 Nos. good quality bricks per meter and the rest space should be filled up with excavated soil as per specification and direction of the site Engineer.
Excavation Of Soil
supply of kiln burnt brick
Laying of bricks
Laying And Dressing Of 01 Nos. Cable 12Kv Gr., 3C X 300 Sq.mm XLPE Cable In Excavated/Pucca Trench/HDPE pipe
Arrangement for termination joint/St.Joint. Jointing kit for end termination joint will be supplied by WBSEDCL and the work of jointing will be done by WBSEDCL’s own personnel or other agency. But necessary arrangements for properly covering top and all sides of jointing pits with tarpaulin/ Polythene sheet has to be made at the time of jointing. Also required manpower is to be provided to help the cable jointer for straightening the cable at the joint location and re arrangement of cable loops until completion of jointing and necessary lighting arrangement is to be done if required
Supply & fixing of GI pipe as per ISI of the 150MM dia for cable protection as per instruction of site engineer.
Raising of 1 nos 3 x 300 sq. mm. XLPE cable upto 10 metres through 3 mtrs. long medium duty GI pipe of 150 mm. dia and MAKING JOINT ARRANGEMENT BETWEEN ACSR 50SQMM CONDUCTOR TO CABLE END TERMINAL with supply of suitable connectors, Nuts, Bolts & washer with brick protection in between pipe and cable etc.
Installation of 12 KV class gapless LA on the cable termination DP
Making protective duct for Cable Joint complit as per WBSEDCLs Approved Drawing(Ref.Drg.no.PLN(D)/SS/106 Dt.05.05.2015
Erection of Shunt Trip Indoor type 11 kV. 250/350MVA. 400/ 800/1250 Amp. metering /non-metering VCB complete as per WBSEDCL's approved drawing and as per instruction of Site Engineer.
M/S ELECTRO ENGINEERING (BID ID -6389206)
JYOTI ENTERPRISE (BID ID -6390441)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .