Provision of Lifts at SUD, TETA, BOE, KANKI, AUB, DLK, KNE & ADINA Stations in Connection with Development of FOBs along with Other Anciliary Works.
45_2026
45_2026
Open
12 Months
West Siang, Arunachal Pradesh
₹0
₹3.1 L
6 Jul 2026
6 Jul 2026
16 Jul 2026
1-PART-A (Under Jurisdiction of SSE/Elect./P/IC/BOE) (Station - SUD,
2-PART-B (Under Jurisdiction of SSE/Elect./P/IC/KNE) (Station - KKA, AUB,
3-PART-C (Under Jurisdiction of SSE/Elect./P/IC/MLDT) (Station - ADF)
Item Breakup - 1-PART-A (Under Jurisdiction of SSE/Elect./P/IC/BOE) (Station - SUD, TETA & BOE)
Supply, wiring, testing & commissioning of Numbers 165.00 concealed point wiring by FR PVC insulated and unsheathed 1.5 sq mm, single core multi strand copper wire with earth continuity wire by PVC insulated and unsheathed 1 sq mm , single core multi strand copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia heavy duty including all types of joints and bends as required, complete with 6 amps flush type controlling modular switch to be mounted on modular GI inner plate and modular mounting frame of suitable module as per requirement complete to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material. a) FL Point/LED Tube Point/LED Recess Light Point with c/rose
b) Lamp Point with angle holder
Supply, wiring, testing & commissioning of Numbers concealed plug point on separate board complete with 2 x 6 Amp modular socket and 6/10 amps modular switch to be mounted on modular GI inner plate 6M and 6M modular mounting frame with GI box to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material.
Supply, wiring, testing & commissioning of Numbers concealed 6/16 amps power plug point on separate board complete with modular 16 amps switch (with indicator) and 6/16 amps 3 pin combined shuttered socket to be mounted on modular GI inner plate 4M or suitable size with modular mounting frame to be concealed in wall as per instruction of Engineer Incharge at Site.
Supply, fixing, connection & testing of 40 Watt Numbers LED Tubelight, Surface/ Pendent mounting LED Battens in Extruded aluminium housing as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers 15 Watt Recess mounted downlighter with pressure die-cast aluminium heat sink & PC diffuser with integrated driver as per instruction of Engineer Incharge at Site. (Round Type)
Supply, fixing & testing and commissioning of Numbers LED 12 W B22 CDL INVERTER BULB V2 as per instruction of Engineer Incharge at Site.
Supply, wiring & testing of main wire by 2.5 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 4 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, wiring & testing of main wire by 6 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 120.00 10 watt LED Bulkhead luminaires, IP65 as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 200 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 66, Luminous efficacy 120 lm/watt with heat sink feature, surge protection etc including wire connection as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Metre Hot Dipped Galvanized Wire Mesh Cable Tray of size (Depth- 54 x Width- 150) mm, made of carbon steel (ASTM A510, Grade-1008 specified) finished by electrozinc plating (ASTM B 633 specified) alongwith all accessories like suitable type of splices, locking tab, divider coupler, preclick, SWK, clamp, Tee, bend, bracket, nut, bolts etc. Trays should comply standard EN ISO 1461: atleast 550 h of SST. Assemblies with specific fire resistant properties must have an E30-E90 certificate. Rod-dia must be from 3.9 mm to 5.9 mm or higher and as per site site requirement and as per instruction of engineer incharge at site.
Design, manufacture, display of wall /hanging / Square floor mounting type LED illuminated sign / Foot direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4- 8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD- II/22/07/02 Date. 15.05.2023) KATIHAR DIVISION-ELECTRICAL/N F RLY
Erection and installation of wall / hanging / floor Square mounting type LED illuminated sign / direction Foot boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD-II/22/07/02 Date. 15.05.2023)
Supply, laying, commissioning & testing of GI pipe Metre 100 mm medium guage with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt etc. (For protection of cable) as per instruction of Engineer incharge at site.
Supply, laying, commissioning & testing of HDPE Metre pipe 50 mm dia, PN-6 grade to be laid partly along the p o l e / w a l l with suitable fixing arrangement by MS clamp made of MS flat of size 50x6 mm and suitable size nut , bolt, washer etc as per instruction of Engineer Incharge at site.
Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers long (3.6 mm thickness) GI pipe, 32x6 mm GI strip- 5 Mtrs, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal, soldered end terminal etc. and construction of earth pit covered with RCC cover slab12.7 mm thickness and watering pipe as per Drg. No.- PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as per instruction of Engineer Incharge at site.
Supply, fixing, testing & commissioning of 20 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P) & MCB DP 20 amp. as per instruction of Engineer Incharge at Site.
Supply, fixing, testing & commissioning of 63 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P/5P) & MCB DP 63 amp. as per instruction of Engineer Incharge at Site.
a) Supply, installation, testing & commissioning of Set 12 way SPN Distribution Board, Flush/Surface mounting, IP 43 grade protection with copper bus bar, fully shrouded neutral bar, earth bar, cable ties, metal double door as per IS 8623 - III with supply and fixing of following RCBO/MCB's as per instruction of Engineer Incharge at Site.
b) MCB DP 63 amps, C-curve, 2 module, 10 kA, Numbers conforms to IS/IEC 60898:2002
c) MCB DP 16-32 amps, 2 module, 10 kA, Numbers Conforms to IS/IEC 60898 - 1:2002
d) MCB SP 6-32 amps, 1 module, 10 kA, C-curve Numbers Conforms to IS/IEC 60898 - 1:2002 KATIHAR DIVISION-ELECTRICAL/N F RLY
a) commissioning & painting of floor mounted powder coated cubicle panel board (Modular look) of suitable size (neither big nor small) ), outdoor type with double door made of suitable size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x 6 mm, 14 SWG MS sheet/Powder coated CRCA sheet with provision of weather proof,rust proof,dust proof,water proof having internal rubber gasket with supply and fixing of following ACB/MCCB/Bus bar/Meter etc. (Connections to be made by copper strips, glands should be provided at cable entry and exit, components should be compartmentalized, Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for each compartment. Panel board drawing approval must be obtained with clear indication of make of items of components):-
b) MCCB FP 100 amps, 25 kA, Ics= 100% Icu
c) MCCB FP 63 amps, 25 kA, Ics=100% Icu
d) Copper bus bar 100 amps made of electrolytic Set grade copper consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar should have insulation cover)
e) Digital voltmeter (0-500) amps and Digital Set ammeter (0-500) amps with s/switch and CTs
f) LED Indication Lamp RYB
Laying, commissioning & testing of HT/LT Metre XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway)
Cutting of Road/Pucca/Hard Soil below (0.3 x 1) Metre mt from ground level and make it good as original with supply & execution of CC work (1:3:6) as per instruction of Engineer incharge at site. Total 5891869.00
Item Breakup - 2-PART-B (Under Jurisdiction of SSE/Elect./P/IC/KNE) (Station - KKA, AUB, DLK & KNE)
Supply, wiring, testing & commissioning of Numbers 220.00 concealed point wiring by FR PVC insulated and unsheathed 1.5 sq mm, single core multi strand copper wire with earth continuity wire by PVC insulated and unsheathed 1 sq mm , single core multi strand copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia heavy duty including all types of joints and bends as required, complete with 6 amps flush type controlling modular switch to be mounted on modular GI inner plate and modular mounting frame of suitable module as per requirement complete to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material. a) FL Point/LED Tube Point/LED Recess Light Point with c/rose
Lamp Point with angle holder KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, wiring, testing & commissioning of Numbers concealed plug point on separate board complete with 2 x 6 Amp modular socket and 6/10 amps modular switch to be mounted on modular GI inner plate 6M and 6M modular mounting frame with GI box to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material.
Supply, wiring, testing & commissioning of Numbers concealed 6/16 amps power plug point on separate board complete with modular 16 amps switch (with indicator) and 6/16 amps 3 pin combined shuttered socket to be mounted on modular GI inner plate 4M or suitable size with modular mounting frame to be concealed in wall as per instruction of Engineer Incharge at Site.
Supply, fixing, connection & testing of 40 Watt Numbers 100.00 LED Tubelight, Surface/ Pendent mounting LED Battens in Extruded aluminium housing as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers 120.00 15 Watt Recess mounted downlighter with pressure die-cast aluminium heat sink & PC diffuser with integrated driver as per instruction of Engineer Incharge at Site. (Round Type)
Supply, fixing & testing and commissioning of Numbers LED 12 W B22 CDL INVERTER BULB V2 as per instruction of Engineer Incharge at Site.
Supply, wiring & testing of main wire by 2.5 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 4 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 6 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 160.00 10 watt LED Bulkhead luminaires, IP65 as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 200 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 66, Luminous efficacy 120 lm/watt with heat sink feature, surge protection etc including wire connection as per instruction of Engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, installation, testing & commissioning of Metre Hot Dipped Galvanized Wire Mesh Cable Tray of size (Depth- 54 x Width- 150) mm, made of carbon steel (ASTM A510, Grade-1008 specified) finished by electrozinc plating (ASTM B 633 specified) alongwith all accessories like suitable type of splices, locking tab, divider coupler, preclick, SWK, clamp, Tee, bend, bracket, nut, bolts etc. Trays should comply standard EN ISO 1461: atleast 550 h of SST. Assemblies with specific fire resistant properties must have an E30-E90 certificate. Rod-dia must be from 3.9 mm to 5.9 mm or higher and as per site site requirement and as per instruction of engineer incharge at site.
Design, manufacture, display of wall /hanging / Square floor mounting type LED illuminated sign / Foot direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4- 8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD- II/22/07/02 Date. 15.05.2023)
Erection and installation of wall / hanging / floor Square mounting type LED illuminated sign / direction Foot boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD-II/22/07/02 Date. 15.05.2023)
Supply, laying, commissioning & testing of GI pipe Metre 100 mm medium guage with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt etc. (For protection of cable) as per instruction of Engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, laying, commissioning & testing of HDPE Metre pipe 50 mm dia, PN-6 grade to be laid partly along the p o l e / w a l l with suitable fixing arrangement by MS clamp made of MS flat of size 50x6 mm and suitable size nut , bolt, washer etc as per instruction of Engineer Incharge at site.
Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers long (3.6 mm thickness) GI pipe, 32x6 mm GI strip- 5 Mtrs, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal, soldered end terminal etc. and construction of earth pit covered with RCC cover slab12.7 mm thickness and watering pipe as per Drg. No.- PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as per instruction of Engineer Incharge at site.
Supply, fixing, testing & commissioning of 20 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P) & MCB DP 20 amp. as per instruction of Engineer Incharge at Site.
Supply, fixing, testing & commissioning of 63 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P/5P) & MCB DP 63 amp. as per instruction of Engineer Incharge at Site.
a) Supply, installation, testing & commissioning of Set 12 way SPN Distribution Board, Flush/Surface mounting, IP 43 grade protection with copper bus bar, fully shrouded neutral bar, earth bar, cable ties, metal double door as per IS 8623 - III with supply and fixing of following RCBO/MCB's as per instruction of Engineer Incharge at Site.
b) MCB DP 63 amps, C-curve, 2 module, 10 kA, Numbers conforms to IS/IEC 60898:2002
c) MCB DP 16-32 amps, 2 module, 10 kA, Numbers Conforms to IS/IEC 60898 - 1:2002
d) MCB SP 6-32 amps, 1 module, 10 kA, C-curve Numbers 128.00 Conforms to IS/IEC 60898 - 1:2002
a) commissioning & painting of floor mounted powder coated cubicle panel board (Modular look) of suitable size (neither big nor small) ), outdoor type with double door made of suitable size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x 6 mm, 14 SWG MS sheet/Powder coated CRCA sheet with provision of weather proof,rust proof,dust proof,water proof having internal rubber gasket with supply and fixing of following ACB/MCCB/Bus bar/Meter etc. (Connections to be made by copper strips, glands should be provided at cable entry and exit, components should be compartmentalized, Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for each compartment. Panel board drawing approval must be obtained with clear indication of make of items of components):-
b) MCCB FP 100 amps, 25 kA, Ics= 100% Icu
c) MCCB FP 63 amps, 25 kA, Ics=100% Icu
d) Copper bus bar 100 amps made of electrolytic Set grade copper consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar should have insulation cover)
e)Digital voltmeter (0-500) amps and Digital Set ammeter (0-500) amps with s/switch and CTs
f) LED Indication Lamp RYB KATIHAR DIVISION-ELECTRICAL/N F RLY
Laying, commissioning & testing of HT/LT Metre XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway)
Cutting of Road/Pucca/Hard Soil below (0.3 x 1) Metre mt from ground level and make it good as original with supply & execution of CC work (1:3:6) as per instruction of Engineer incharge at site. Total 6781428.00
Item Breakup - 3-PART-C (Under Jurisdiction of SSE/Elect./P/IC/MLDT) (Station - ADF)
Supply, wiring, testing & commissioning of Numbers concealed point wiring by FR PVC insulated and unsheathed 1.5 sq mm, single core multi strand copper wire with earth continuity wire by PVC insulated and unsheathed 1 sq mm , single core multi strand copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia heavy duty including all types of joints and bends as required, complete with 6 amps flush type controlling modular switch to be mounted on modular GI inner plate and modular mounting frame of suitable module as per requirement complete to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material. a) FL Point/LED Tube Point/LED Recess Light Point with c/rose
b) Lamp Point with angle holder
Supply, wiring, testing & commissioning of Numbers concealed plug point on separate board complete with 2 x 6 Amp modular socket and 6/10 amps modular switch to be mounted on modular GI inner plate 6M and 6M modular mounting frame with GI box to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material.
Supply, wiring, testing & commissioning of Numbers concealed 6/16 amps power plug point on separate board complete with modular 16 amps switch (with indicator) and 6/16 amps 3 pin combined shuttered socket to be mounted on modular GI inner plate 4M or suitable size with modular mounting frame to be concealed in wall as per instruction of Engineer Incharge at Site.
Supply, fixing, connection & testing of 40 Watt Numbers LED Tubelight, Surface/ Pendent mounting LED Battens in Extruded aluminium housing as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers 15 Watt Recess mounted downlighter with pressure die-cast aluminium heat sink & PC diffuser with integrated driver as per instruction of Engineer Incharge at Site. (Round Type)
Supply, fixing & testing and commissioning of Numbers LED 12 W B22 CDL INVERTER BULB V2 as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, wiring & testing of main wire by 2.5 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 4 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 6 sq mm, Metre Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 10 watt LED Bulkhead luminaires, IP65 as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers 200 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 66, Luminous efficacy 120 lm/watt with heat sink feature, surge protection etc including wire connection as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Metre Hot Dipped Galvanized Wire Mesh Cable Tray of size (Depth- 54 x Width- 150) mm, made of carbon steel (ASTM A510, Grade-1008 specified) finished by electrozinc plating (ASTM B 633 specified) alongwith all accessories like suitable type of splices, locking tab, divider coupler, preclick, SWK, clamp, Tee, bend, bracket, nut, bolts etc. Trays should comply standard EN ISO 1461: atleast 550 h of SST. Assemblies with specific fire resistant properties must have an E30-E90 certificate. Rod-dia must be from 3.9 mm to 5.9 mm or higher and as per site site requirement and as per instruction of engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Design, manufacture, display of wall /hanging / Square floor mounting type LED illuminated sign / Foot direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4- 8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD- II/22/07/02 Date. 15.05.2023)
Erection and installation of wall / hanging / floor Square mounting type LED illuminated sign / direction Foot boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD-II/22/07/02 Date. 15.05.2023)
Supply, laying, commissioning & testing of GI pipe Metre 100 mm medium guage with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt etc. (For protection of cable) as per instruction of Engineer incharge at site.
Supply, laying, commissioning & testing of HDPE Metre pipe 50 mm dia, PN-6 grade to be laid partly along the p o l e / w a l l with suitable fixing arrangement by MS clamp made of MS flat of size 50x6 mm and suitable size nut , bolt, washer etc as per instruction of Engineer Incharge at site.
Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers long (3.6 mm thickness) GI pipe, 32x6 mm GI strip- 5 Mtrs, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal, soldered end terminal etc. and construction of earth pit covered with RCC cover slab12.7 mm thickness and watering pipe as per Drg. No.- PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as per instruction of Engineer Incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, fixing, testing & commissioning of 20 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P) & MCB DP 20 amp. as per instruction of Engineer Incharge at Site.
Supply, fixing, testing & commissioning of 63 Set amp Industrial plug & socket DB (CRCA/SS made) complete with metal Plug, socket (3P/5P) & MCB DP 63 amp. as per instruction of Engineer Incharge at Site.
a) Supply, installation, testing & commissioning of Set 12 way SPN Distribution Board, Flush/Surface mounting, IP 43 grade protection with copper bus bar, fully shrouded neutral bar, earth bar, cable ties, metal double door as per IS 8623 - III with supply and fixing of following RCBO/MCB's as per instruction of Engineer Incharge at Site.
b)MCB DP 63 amps, C-curve, 2 module, 10 kA, Numbers conforms to IS/IEC 60898:2002
c)MCB DP 16-32 amps, 2 module, Conforms to IS/IEC 60898 - 1:2002
d) MCB SP 6-32 amps, 1 module, 10 kA, C-curve Numbers Conforms to IS/IEC 60898 - 1:2002
a) commissioning & painting of floor mounted powder coated cubicle panel board (Modular look) of suitable size (neither big nor small) ), outdoor type with double door made of suitable size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x 6 mm, 14 SWG MS sheet/Powder coated CRCA sheet with provision of weather proof,rust proof,dust proof,water proof having internal rubber gasket with supply and fixing of following ACB/MCCB/Bus bar/Meter etc. (Connections to be made by copper strips, glands should be provided at cable entry and exit, components should be compartmentalized, Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for each compartment. Panel board drawing approval must be obtained with clear indication of make of items of components):-
b) MCCB FP 100 amps, 25 kA, Ics= 100% Icu
c) MCCB FP 63 amps, 25 kA, Ics=100% Icu
d) Copper bus bar 100 amps made of electrolytic Set grade copper consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar should have insulation cover)
e) Digital voltmeter (0-500) amps and Digital Set ammeter (0-500) amps with s/switch and CTs
f) LED Indication Lamp RYB
Laying, commissioning & testing of HT/LT Metre XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway)
Cutting of Road/Pucca/Hard Soil below (0.3 x 1) Metre mt from ground level and make it good as original with supply & execution of CC work (1:3:6) as per instruction of Engineer incharge at site. Total 2940515.00 KATIHAR DIVISION-ELECTRICAL/N F RLY