Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹37.0 LAdmitted-Fee/PreQual/Technical/Finance | -26.00% | ₹37.0 L | L1 | Admitted-Fee/PreQual/Technical/Finance |
| 2 | L2₹41.4 L+₹4.4 L (12.0%)Admitted-Fee/PreQual/Technical/Finance | -17.11% | ₹41.4 L+₹4.4 L (12.0%) | L2 | Admitted-Fee/PreQual/Technical/Finance |
| 3 | L3₹47.6 L+₹10.6 L (28.5%)Admitted-Fee/PreQual/Technical/Finance | -4.88% | ₹47.6 L+₹10.6 L (28.5%) | L3 | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Not Admitted-Fee/PreQual/Technical/Finance THAYAN KALAROOS SHAH BULDING THAYAN KALAROOS THAYAN KAAROOS KUPWARA JAMMU KASHMIR 193222 UDYAM JK 12 0011118 | KUPWARA | JAMMU AND KASHMIR | 193222 | - | - | - | Not Admitted-Fee/PreQual/Technical/Finance Others-Similar Nature of works not matching with the required condition in the NIT |
Tender Value
₹50.0 L
EMD Value
₹99,982
Closing Date
24 Aug 2026, 4:00 pmClosed
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX RAJ BAGH
Segregation of internal power connection at Mini Secretariat Ganderbal via dedicated LT Panels
2026_PWDJK_319347_1
NIT No.105//2026-27 Dt/04/08/2026
Open Tender
Electrical Works
Percentage
45 days
Ganderbal
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,100
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹99,982
31 Aug 2026
4 Aug 2026
25 Aug 2026
4 Aug 2026
24 Aug 2026
4 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Part I: Segregation of internal electrification of DC Office Building (Ist-floor) at Mini Secretariat Ganderbal | - | - | - | - |
| 2 | Part-A (Panel,Cabling & 100KVA AVR) | - | - | - | - |
| 3 | Design/Supply/Installation/Testing and commissioning of distribution/feeder outdoor panel having a sloped roof (3+1) Al. bus bar of cubical type vermin proper double door lockable outdoor type fabricated out of 14/16 SWG MS Sheets powder coated weather proof, dust proof with IP 65 protection with angle iron 50x50x6mm stand painted in black colour of 2.5 feet height/ground clearance properly grouted in cement concrete of 1:2:4 ratio-filter with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following(Main Panel):
Normal Incoming:-1) MCCB 630 A 50 KA 4P with ROH with extended spreader links of Legrand/Siemens/ABB/LK make = 1 No.
2) 800 Amp TPN Bus bar AL Strips = 1 Set, Voltmeter =1 no, Ammeter = 1 no , CT coils for Ammeter 800 /5A = 1 set & phase indicators =1set
Generator:- 1) 400 A 4Pole,415 V with ROH Changeover Switch of Havells/Legrand/Siemens/ABB/LK make = 1 No.
2):- 250 A 36 KA 4P MCCB of Legrand / Siemens/ ABB /Schinder /L&T make = 01 No.
3):- 400 Amp TPN Bus bar AL Strips = 1 Set,Voltmeter =1 no, Ammeter = 1 no , CT coils for Ammeter 250 /5A = 1 set & phase indicators =1set.
Outgoing:-
1) 200A 36 KA 4P MCCB of Legrand / Siemens/ ABB /Schinder /L&T make = 04 No. (Main)
2) 100 A 25 KA 4P MCCB of Legrand / Siemens/ ABB /Schinder
/L&T make = 04 No. (DG)
3) Bypass Switch 200 A 4Pole, 415V Havells/Legrand / Siemens/ ABB /Schinder /L&T make = 01 No. (For bypassing 100KVA AVR)
Panel shall have provision for entry of cables from the bottom as required.The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 1 | No. | 3,50,000 | ₹3,50,000 |
| 4 | Supply/Laying/Testing and Commissioning of 3.5-Core 240 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/KEI/Paramount Make. The cable shall include end termination lugs with its crimping /taping on Panel side and Al thimbles duly crimped on both sides ie Clamp/ MCCB for connecting MCCB with distribution Panels(From Pole to Main Panel) | 100 | Mtrs | 2,250 | ₹2,25,000 |
| 5 | Supplying and laying of 120 mm dia (OD-120 mm & ID-103 mm nominal) DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. The Job includes Excavation Work and filling back | 80 | Mtr. | 280 | ₹22,400 |
| 6 | Supply/Excavation & Laying of GI Pipe (B-Class) of 06 inches dia with ISI Marked for Road cut and refilling of same with cement concrete. (For Road Crossing) | 150 | Rft | 350 | ₹52,500 |
| 7 | Design/Supply/Installation/Testing and commissioning of Floor/Wall Mounted (Indoor/outdoor subjected to the site)panel Al. bus bar of cubical type vermin proof fabricated out of 14/16 SWG MS Sheets powder coated weather proof, dust proof thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following(DC/ADC/ADDC/CPO Office):
Normal Incoming:-
1) 160 Amp 25 KA MCCB with extended rotary handle, spreader links of Legrand/Siemens/ABB//LK make = 1 No.
2) 200 Amp TPN Bus bar Al. Strips = 1 Set, Voltmeter =1 no, Ammeter = 1 no , CT coils for Ammeter 300 /5A = 1 set & phase indicators =1set
Generator:-
1) 100 A 4Pole,415 V Changeover Switch of Havells/Legrand/Siemens/ABB/LK make = 1 No.
2) 63 Amp 25 KA MCCB with extended rotary handle, spreader links of Legrand/Siemens/ABB//LK make = 1 No.
2) 200 Amp TPN Bus bar Al Strips = 1 Set, Voltmeter =1 no, Ammeter = 400 A 4Pole,415 V with ROH Changeover Switch of Havells/Legrand/Siemens/ABB/LK make = 1 No. , CT coils for Ammeter 100 /5A = 1 set & phase indicators =1set
UPS/Inverter:-
3) 63 A TPN RCCB 100mA, 10kA of Legrand/Siemens/ABB/LK make = 1 No. 200 Amp TPN Bus bar AL Strips = 1 Set, Voltmeter =1 no, Ammeter = 1 no , CT coil for Ammeter 60 /5A = 1 set ,phase indicator =1no.
Outgoing:-
1) 63 Amps 4P MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make = 04 No for normal heating sub main
2) 40 Amps 4P MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make = 04 No for Sub main lighting/AC
3) 32 Amps 4P MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make =04 No for sub main lighting/ UPS/ Inverter.
The Panel manufacturing unit should be CPRI Registered and the Contractor has to submit the test certificate of main switch gear and Drawing of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards) is to approved by Engineer Incharge before manufacturing | 4 | No. | 1,10,000 | ₹4,40,000 |
| 8 | Supply/Laying/Testing and Commissioning of 3.5-Core 95 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/RR-Kabel/KEI Make. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct Partially in ground & Paritally on wall of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(Main Panel to Floor Panel of DC Office) | 50 | Mtr | 1,450 | ₹72,500 |
| 9 | Supply/Laying/Testing and Commissioning of 3.5-Core 70 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/RR-Kabel/KEI Make. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct Partially in ground & Paritally on wall of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(Main Panel to Floor Panel of ADC/ADDC/CPO Office) | 200 | Mtr | 1,150 | ₹2,30,000 |
| 10 | Supply/Laying/Testing and Commissioning of 3.5-Core 50 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/RR-Kabel/KEI Make. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct Partially in ground & Paritally on wall of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(For DG Supply from Main Panel to Floor Panel of ADC/ADDC/CPO Office) | 200 | Mtr | 850 | ₹1,70,000 |
stage.html
html • 0.02 MB
finance_1057410.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.85 MB
BOQ_1057410.xls
BOQ • 2.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .