Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.3 CrAdmitted-Finance | ₹2.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.3 Cr+₹2.0 L (0.87%)Admitted-Finance | ₹2.3 Cr+₹2.0 L (0.87%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | SAINKO SYSTEMS L2 | SHUBHAM TRADERS L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, Installation, testing and commissioning of 400 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, copper wound transformer with ON load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site. | 1 | Nos. | 20,89,700 ₹20,89,700 | 20,65,000 ₹20,65,000 Lowest |
| 2.00 | Design, manufacturing, testing at works, supply of 1 No. 11KV, 630A, 21kA/3 Sec Outdoor type, extensible SF6 gas insulated Ring Main Unit equivalent to Ringmaster RE6C+CE6 with 1 Nos. On Load Cable isolator and 1 No. Vaccum Circuit breaker enclosed in a stainless steel tank with self powered microprocessor based numerical relay and dedicated Ct's for protection of Transformer comple as required and as per specification | 1 | Set | 8,45,975 ₹8,45,975 | 8,45,000 ₹8,45,000 Lowest |
| 3.00 | Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required. | 2 | Each | 310 ₹620 Lowest | 310 ₹620 Lowest |
| 4.00 | Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge. | 4 | Sets | 1,474 ₹5,896 Lowest | 1,474 ₹5,896 Lowest |
| 5.00 | Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd. | 2 | Nos. | 4,377 ₹8,754 Lowest | 4,377 ₹8,754 Lowest |
| 6.00 | supply and fixing of ABC type fire extinguishers capacity 9kg MAP 50 suitable for all kind of fire. | 2 | Each | 16,741 ₹33,482 Lowest | 16,741 ₹33,482 Lowest |
| 7.00 | supply and fixing of Co2 type fire extinguishers capacity 4.5 kg gas based suitable for Electric kind of fire. | 2 | Each | 16,741 ₹33,482 Lowest | 16,741 ₹33,482 Lowest |
| 8.00Supply of 3 core stranded aluminium conductor 11KV grade XLPE (E) (Cross linked Polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cable confirming to IS : 7098 (part II with latest amendments). Make. Kei, Havells, Polycab or Eq | |||||
| 9.00 | 70 sq. mm 3 core | 250 | Metre | 1,950 ₹4,87,500 | 1,944 ₹4,86,000 Lowest |
| 10.00Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required | |||||
Tender Value
₹2.3 Cr
EMD Value
₹4.7 L
Closing Date
26 Mar 2025, 3:00 pmClosed
GM CIVIL BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
External Electrification and Allied works at Sub District Hospital Purola Distt Uttarkashi
2025_BRID3_81470_4
524/BRIDCUL/993/25 Dated 10.03.2025
Open Tender
Electrical Works
Item Rate
540 days
Purola Uttarkashi
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹4.7 L
BRIDCUL Dehradun
28 Mar 2025
17 Mar 2025
26 Mar 2025
17 Mar 2025
26 Mar 2025
21 Mar 2025
20 Mar 2025
Amount
Supply, Installation, testing and commissioning of 400 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, copper wound transformer with ON load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site.
Design, manufacturing, testing at works, supply of 1 No. 11KV, 630A, 21kA/3 Sec Outdoor type, extensible SF6 gas insulated Ring Main Unit equivalent to Ringmaster RE6C+CE6 with 1 Nos. On Load Cable isolator and 1 No. Vaccum Circuit breaker enclosed in a stainless steel tank with self powered microprocessor based numerical relay and dedicated Ct's for protection of Transformer comple as required and as per specification
Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.
Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge.
Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd.
supply and fixing of ABC type fire extinguishers capacity 9kg MAP 50 suitable for all kind of fire.
supply and fixing of Co2 type fire extinguishers capacity 4.5 kg gas based suitable for Electric kind of fire.
Supply of 3 core stranded aluminium conductor 11KV grade XLPE (E) (Cross linked Polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cable confirming to IS : 7098 (part II with latest amendments). Make. Kei, Havells, Polycab or Eq
70 sq. mm 3 core
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required
upto 120 sq. mm
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of, XLPE aluminium conductor cable of 11 KV grade as required
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supply installation testing and commissioning of LT panel Board for the extension of existing panel as per the following specification with proper copper earthing as recommended. The panel should be Designed as per the latest standard IEC 61439. The panel should have Bus bar clearance of 25 mm for Ph to Ph and 19 mm for Ph to neutral, Zero Stray voltage doors and panels, polyester glass support for insulation. The cable alleys should be 300 mm wide and it should be fitted with hinged door that open up to and angle of 95 Deg. The provision of cable entry should be from Bottom. The IP protection of panel should be IP-42 for external and IP2X for internal with 3B as Form of separation. The panel should be equipped with suitable size of CT and display meter for VAF measurement. The panel should be suitable for seismic zone V. Make of panel: L&T (Ti), ABB (ArtuK), Schneider (OkEN)
LT Outgoing should be IP 54 and should have switchgears as below. Make of LV switchgear : L&T (Lauritz & Knudsen), Schneider or Siemens.
INCOMER:-
1 No 630 Amp. 4P MCCB of 35KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 No. CT FOR APFC PANEL
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set 50,50N,51,51N,27,32,49,59,86,95 CT's control.
BUS BARS:-
800 Amps. TP&N aluminium bus bars
OUT GOINGS:-
2 Nos. 250 Amps. FP MCCB thermal magnetic release (25 KA)
2 Nos. 100 Amps. FP MCCB thermal magnetic release (25 KA)
3 Nos. 40 Amps. FP MCCB thermal magnetic release (25 KA)
7 Nos. 32 Amps. DP MCB (10 KA)
2 Nos. Space & Spare
EXTERNAL LIGHTING PANEL
INCOMER:-
1 No 40 Amp. 4P MCCB of 25KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS:-
60 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
4 Nos. 32 Amps. FP MCB
15 Nos. 16 Amps. DP MCB
2 Nos. Space & Spare
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supply of following size of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment. Make:- Kei, Havells & Polycab or Eq.
3.5 x 300 sq.mm.
3.5 x 120 sq.mm
3.5 x 50 sq.mm
4 x 10 sq.mm
2 x 10 sq.mm,
3 x 4 sq.mm,
Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
2 X 6 sq. mm (19mm)
2 X 10 sq. mm (19mm)
3½ X 50 sq. mm (35mm)
3½ X 120 sq. mm (45mm)
3½ X 300 sq. mm (70mm)
4 X 10 sq. mm (25mm)
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
100mm dia
150 mm dia
250 mm dia
300 mm dia
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
90 mm dia (OD-90 mm & ID-76 mm nominal)
SUBHEAD - I :Solar Photovoltaic Power Plant
Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:-
a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years.
b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency.
c) Data Monitoring System complete with accessories.
d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required.
e) Lightning and surge voltage protection.
f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.
SUBHEAD - I :D.G. SETS
Supplying, Installation and commissioning of AMF start silent type 25KVA DG set comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 25 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank capacity made of 2mm thick M.S. sheet complete with M.S. fuel piping, G.M. gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound proof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with with heavy duty doors, lockable arrangement, sound proof insulation with high density rock/mineral polymer/fibre cloth and perforated CRCA sheets, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs. as per CPCB IV norms
AMF Panel Incoming- 250 Amps FP MCCB of 25KA breaking capacity and contactor same rating
Supplying, Installation and commissioning of AMF start silent type 100KVA DG set comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 100 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank capacity made of 2mm thick M.S. sheet complete with M.S. fuel piping, G.M. gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound proof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with with heavy duty doors, lockable arrangement, sound proof insulation with high density rock/mineral polymer/fibre cloth and perforated CRCA sheets, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs. as per CPCB IV norms
AMF Panel Incoming- 125 Amps FP MCCB of 25KA breaking capacity and contactor same rating
Supplying, Installation and commissioning of AMF start silent type 40KVA DG set comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 40 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank capacity made of 2mm thick M.S. sheet complete with M.S. fuel piping, G.M. gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound proof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with with heavy duty doors, lockable arrangement, sound proof insulation with high density rock/mineral polymer/fibre cloth and perforated CRCA sheets, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs. as per CPCB IV norms
AMF Panel Incoming- 100 Amps FP MCCB of 25KA breaking capacity and contactor same rating
SUBHEAD - I: CAMPUS LIGHTING
Supply and fixing of hot dip galvanised steel OCTAGONAL POLE, Height=7m, Top OAF= 70 mm, Bottom OAF-130, Thickness - 3 mm,Base Plate - 220x220x12 mm , PCD - 220 mm
Supply and fixing of foundation accessories for 7 mtr pole set-Each set consists of 4 nos. of M20x700 J bolts plus 10% templates
Supply and fixing of 1000 mm Galvanized SINGLE Arm bracket , Standarad Type made of 48.3/32 mm OD pipe
Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 70Watt. to 80 Watt and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 4000-5000 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70,fitting itself suitable for 60-65mm OD pipe
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Above 6.5 metre and upto 8.0 metre
Supplying,installation,testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.
1 output per phase and suitable for single phase supply
Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required
32 mm dia
SUB-HEAD - I : UPS SYSTEM
Supply, installation, testing & commissioing of 10 KVA UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features.
THD(i) shall be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Single Phase Input and Single Phase Output. ( Input - 220V - 240V, Single Phase, 2 wire. / Output - 220-240 Volt, Single Phase, 2 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells.
Battery shall be external type with rack and suitable for 30 minute backup on 100% load.
Suitable size of copper cable between UPS and battery bank shall be provided
UPS described as above
Supply, installation, testing & commissioing of 20 KVA UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features.
THD(i) shall be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. ( Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells.
Battery shall be external type with rack and suitable for 30 minute backup on 100% load.
Suitable size of copper cable between UPS and battery bank shall be provided
UPS described as above
SUBHEAD - IX : AC Equipment
SITC of 1.5 Ton Hot and Cold Split Air Conditioner Make- Daikin/Mitsubishi/Toshiba
S/F MS Outdoor Stand
S/F 5 KVA Stabilizer copper winding Make- V-Guard/Luminous / Blue Star
S/L 3 x 2.5 Sqmm core flexible Copper Counductor Make- Finolex/Polycab/RR Cable
S/L drain Pipe 25mm with Albow socket
S/L Copper Refrigerent pipe 5/8 and 1/4
SUBHEAD - I : Geyser Equipment
SITC of 25 Ltr. Glass line Geyser with all accessories Make- Havells/Bajaj or Eq
SAINKO SYSTEMS (BID ID -369658)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.17 MB
sbdexternalelectificationsubdistrictpurola.pdf
Tender Documents • 1.78 MB
BOQ_97237.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .