Providing installation, testing and commissioning of VT pump 20000 GPH discharge x 30MH confirming to relevant ISO with all latest amendments with allied electro mechanical works at pumping station Chainpur Kalakote Kalakote Town.
2020_PHE_91452_1
PHE/MDR/56 of 2019-20
Open Tender
Miscellaneous Works
Item Rate
10 days
RAJOURI
Please refer Tender documents.
3 documents required · 3 mandatory
₹250
revenue head 0215 water sanitation
Yes
20 Feb 2020
29 Jan 2020
12 Feb 2020
29 Jan 2020
11 Feb 2020
31 Jan 2020
Amount
Providing, Installation, Testing and Commissioning of VT Pump Set complete at Filter Plant Chainpur Kalakote Town (The pump set should be of reputed make and should confirm relevant ISO with all latest amendments. The equipment shall also be accompanied with test certificates and performance curves.) along with discharge head, TBH and sole plate of the following specifications:- Discharge – 20000 gallons per hour Head – 30 mtr. Bowl efficiency – 84% Column length as per site requirement. Shut off head – 50mtr. Type of Lubrication – Self Water Lubricated Material of construction Casing – CI IS 210 FG 200 Impeller- CF8M Pump Shaft – SS 410 Line Shaft – SS 410 Column pipe – MS ERW 3.5 mm thick Coupling – SS 410 Discharge Head – CI IS 210 FG 200 Providing & fitting of 4 pole VSS VT motor having 1470 RPM ABB/ KEC/ CEGL/ BBL make. Specifications Voltage : 415 +/- 10% 3 phase AC Frequency (HZ) : 50 Hz +/- 5% Insulation : Class F Duty :- S1- Continuous Ambient Temperature : 0 to 500 C Direction of rotation : ACW looking from top The job includes unloading the material by using heavy duty crane, skilled labour and stacking it near Intake approach bridge. Carriage of material inside the pump room by head load using skilled labour, tools and tackles. Lowering of new pump set by way of lowering pump assembly after fitment of lubrication system. Lowering of linear shaft, column pipes and spider sets. Connecting the column pipes by using superior quality fasterners and lowering all the column pipes and allied material including lubrication pipes. Fitting of top shaft. Fitting of discharge head connecting it to the delivery pipe and providing and fitting of new nuts, bolts and gasket joints. Fitting of new packing box assembly, ratchet assembly, coupling pulley and fixing adjusting nut at the top of the top shaft. Providing and filling of M-Oil in the ratchet assembly, fitting of motor and connecting it with the pump through motor stool and coupling pulley. Fabrication of delivery line out of MS pipe of required dia as per site conditions from the delivery of the pump to the existing rising main Making electric connections and testing on full load. The job also includes fabrication of casing of angle iron /channels for protection of column pipe and pump.
Electrical installation of VT pump set 20000 GPH X 30 MH with motor along with allied works by way of fabrication/grouting of angle iron panel board fitted with 12mm thick ply board covered with good quality mica. Painting of angle iron with one shade of primer & two shades of high quality black paint. Providing and fitting of 200 Amp. 415 volt , 3 phase good quality main switch (H/DUTY) of HRC type of I.S.I make on the Panel board by way of drilling holes providing of nuts, bolts washers etc-01 no. Providing/fitting of Voltmeter 0-500V, Ampere meter 0-200A, Angle holders-3Nos, Bulbs 3No. for phase Indicator, copper wire (approx 30mtr length as per site requirement ). On-Off switch-3No, gang box, insulation tapes, screws, nuts, bolts, washers, baton etc on Switch board. Providing / fitting of aluminium cable-185mm sq from LT pole to 200 Amp 415 V main switch fitted on the panel board with proper thimbling duly crimpled by using crimpling tool & proper insulation. Providing & fitting of 200 Amp,415 Volt,3-phase good quality Bus Bar Box by way of drilling of holes, providing of nuts, bolts, washers etc. P/F of 16 mm sq submersible cable for making connections from main switch to buss bar box. Complete job including cost of material labour & carriage charges.
Providing, fabrication, installation, testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. for operating of VT pump set 20000GPH X 30 MH with motor at pumping station Chainpur Kalakote Town along with allied works. Providing /Fitting of 16 mm square three core sub cable for making of electrical connection from motor to control panel with proper thimbling & insulation. Providing/Fitting of nut/bolts, washers, tapes & sundry items required at site .Complete job includes cost of material, labour charges, carriage charges & complete welding charges at site. Complete job includes checking continuity of complete electrical circuit & testing/ commissioning of pumping machinery.
Testing and commissioning of VT pump motor set & all other allied electromechanical works. Checking of all electrical connections, tapping and tightening all other connections. Plugging of leaking joints if any by way of welding, replacement of gaskets and tightening of nuts and bolts. Checking the alignment of pump and motor sets and testing the machinery on full load. Complete job.
HITECH MECHNICALS
G B Traders
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .