Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 21 KISHORE BHAWAN MALVIYA NAGAR AIR FORCE JODHPUR RAJ 342011 | JODHPUR | JODHPUR | RAJASTHAN | 342011 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | Admitted-Finance |
Tender Value
₹8.6 L
EMD Value
₹17,200
Closing Date
1 Mar 2025, 6:00 pmClosed
AGE (I) R AND D JODHPUR
AGE (I) R AND D DEFENCE LAB JODHPUR
REPAIR AND MAINT OF DG SETS DIFFERENT CAPACITY INCLUDING CONNECTED AMF PANELS IN TECHNICAL AREA AT DEFENCE LAB JODHPUR
2025_MES_692696_2
8626/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
AGE(I) R AND D JODHPUR
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
AGE (I) R AND D JODHPUR
₹17,200
Yes
5 Mar 2025
3 Feb 2025
3 Mar 2025
3 Feb 2025
1 Mar 2025
10 Feb 2025
Amount
M&L , monthly Inspection, maintenance and servicing of DG set including alternator, electric panel board connection to DG set for routine check (A check) of DG set for smooth functioning and carrying out maintanance of any capacity & make of DG Set, completeall as directed as specified by Engineer-in-Charge (a) Servicing/ repair of DG Set shall be carried out by authorised dealer/ agency of manufacturer. (b) Checking engine oil level and topping up as and when required . Note: (i) Note : Spare parts shall be measured and paid seperately (ii) Checking and adjusting the belt for tension and replacement of belt. (iii) Checking of air filter element. (iv) Checking of exhaust system for leakage including rectification. (v) Draining of sediment from fuel filter and fuel tank (vi) Cleaning of air cleaner element (vii) Checking engine alternator coupling, mounting bolts and alignment (viii) Tighting all nuts, bolts, in altenator terminal block (ix) Checking of alternator carbon brush and connections in alternator (x) Checking and tighting of all connection in DC control wiring.
M&L, required for Inspection, maintenance and servicing of DG set including alternator, electric panel board connection to DG set for routine check (B check) of DG set for smooth functioning and carrying out maintanance as directed as specified for the following DG sets. Note:- B-check once in 3 month Or 250 HRs running of DG set whchever is earlier.
S&F in replacement of fuel filter element with 'O' ring as per existing make of any capacity DG Set all as specified and directed by Engineer-in-Charge.
S&F in replacement of lubrication oil filter element with 'O' ring as per existing make of any capacity DG Set all as specified and directed by Engineer-in-Charge.
S&F in replacement of air filter element outer and inner with 'O' ring of as per existing make of any capacity DG Set all as specified and directed by Engineer-in-Charge.
S&F in replacement Fuel water saperator suitable of any capacity DG Set complete all as directed by Engr-in-Charge.
S&F in replacement the old unserviceable AVR (Automatic Voltage Regulator) as per existing make of any capacity complete all as directed by Engr-in-Charge.
S&F of over and under voltage relay for EMF panel of any capacity of DG Sets complete all as specified & directed by Engineer-in-Charge.
M&L for servicing/repair of self starter of any capacity DG set incl replacement of parts such as corban brushes, solonaid, rotor,washer, nut, bolts etc assembling the same and testing complete all as specified and directed by Engineer in charge. .
M&L servicing/ cleaning of MS diesel tank of any capacity DG Set by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including replacement of drain valve, outlet pipe complete all as specified and as directed.
M&L for copper earthing of plate size 60cm x 60cm x 3.15mm thick electrode and 20x3mm earthing strip as earth lead complete all as specified and directed by Engr-in-charge.
M&L for dismantling the radiator and fan from the engine for cleaning of copper tubes and cooling fins by using descaling solution and soldering, patch work including repair of water pump assembly and replacement of defective parts of water pump and re-assembliying,testing complete of any capacity DG set complete all as specified and directed by Engineer in charge.
M&L for rewinding of Alternator of any capacity DG Set including opening of alternator & carrying to workshop for complete rewinding work and placed in its own position and Testing after installation complete all as specified and directed by Engineer-in-charge.
S&F in replacement of unseviceable 1.5 M battery lead with negative & positive brass terminals of suitable size, complete all as specified and directed by Engineer in charge.
M&L for Engine oil 20 W 40 turbo synthetic superior quality engine oil suitable for DG Set complete all as specified and directed by Engineer in charge.
M&L for Coolent complete all as specified and directed by Engineer in charge.
S&F in replacement shunt trip coil for existing LT ACB 1250 Amp complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of 4 pole power contactor suitable for 40 KVA DG set , complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of 4 pole power contactor MCX33, 200 Amp, 415 Volt as per existing make and capacity suitable for 125 KVA DG set, complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of 4 pole power contactor MC-500a/4, 630 Amp, 415 volt as per existing make and capacity suitable for 320 KVA DG set, complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of 4 pole power contactor MCX43/44, 500 Amp, 415 Volt as per existing make and capacity suitable for 250 KVA DG set , complete all as specified & directed by Engineer-in-Charge.
Supply & Fixing in repair HBC Fuse 630 Amp 415 Volt suitable for AMF/LT Panel including taking down old unserviceable, complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of MCCB 4 POLE 25 KA 200 Amps with adjustable thermal and magnetic release in existing panel the make should be of the same of existing MCCB to match with existing holes/surface including taking down old unserviceable complete all as specified and directed by engineer in charge.
All as per item No 49 here in before but 25 KA 125Amp
All as per item No 49 here in before but 36 KA 400 Amp
All as per item No 49 here in before but 25 KA 250 Amp
S&F in replacement of radiator hose as per existing size suitable for any capacity DG set all as specified and as directed.
M&L for opening AMF Panel of DG set, Cleaning of dust by using blower & cleaning agents. Checking/Detecting faults, Removing Faults, Re-wiring of old unserviceable wiring & Testing of Control Wiring complete as reqd and closing of AMF Panel after replacement of unserviceable parts and testing on completion of job on existing load etc complete all as specified & directed by Engineer-in-Charge. NOTE:- Un-serviceable parts shall be measured and paid separatly.
S&F in replacement of old unserviceable Relay any type suitable for any capacity of DG set AMF Panel complete all as specified and directed by Engineer in charge.
S&F in replacement of old unserviceable indicator lamp set RYB for phase indications suitable for panel to match with the existing one complete all as specified and directed by Engineer in charge.
S&F in replacement of old unserviceable Auxillary contractor 3 phase suitable for AMF Panel of DG Set as per existing specification and make, complete all as specified and directed by Engineer in charge.
S&F in replacement of old unserviceable volt meter of existing make, size and type complete all as specified and directed by engineer in charge.
S&F in replacement of old unserviceable Amp meter existing make, size and type complete all as specified and directed by engineer in charge.
M&L for Repair of battery charger of DG set any capacity by replacing / rectifying main transformer of 220/24 volt, battery cut out etc complete all as specified and directed by engineer in charge.
S&F in replacement oil temperature gauge as per existing make suitable for any capacity of DG Set complete all as specified & directed by Engineer-in-Charge.
Supply and fixing in replacement water temperature gauge as per existing make suitable for any capacity of DG Set complete all as specified & directed by Engineer-in-Charge.
S&F in replacement of old unserviceable CT as per existing ratio/specification/rating complete all as specified and directed by Engineer in charge.
S&F in replacement Oil Pressure gauge suitable for existing make of any capacity DG set complete all as specified & directed by Engineer-in-Charge
S&F in replacement STOP EMERGENCY switch, suitable for any capacity of DG Set complete all as specified & directed by Engineer-in-Charge
M&L for Battery water with electrolyte mix complete all as specified and directed by Engineer in charge.
S&F in replacement of V belt of any capacity DG set of suitable size, complete all as specified and directed by Engineer in charge.
S&F in replacement Stop Solenoid switch suitable for any capacity of DG set , complete all as specified & directed by Engineer-in-Charge.
S&F in replacement power controller of DG set of any capacity, complete all as specified & directed by Engineer-in-Charge.
Supply & fix in replacement of unserviceable battery 12 V, 150 AH with maintenance free battery 12 volt initially charged including taking down old unserviceable complete all as specified and directed by Engineer-in-charge.
All as per item No 81 here in before but 180 AH
Supply and fixing in replacement diesel Level Sensor suitable for existing capacity and makeof DG set available at site complete all as specified and directed by Engineer-in-charge.
Supply and fixing in replacement digital display unit suitable for existing capacity and make of DG set available at site complete all as specified and directed by Engineer-in-charge.
Supply only oil soaked cotton waste for cleaning of DG sets complete all as specified and directed by Engineer-in-charge.
S&F sensor circuit borad for any capacity DG Set as per existing make complete all as specified and directed by Engineer-in-charge.
S&F VMR relay for any capacity DG Set as per existing make complete all as specified and directed by Engineer-in-charge
Supply only portable type air blower 650 watt, 16000 RPM, Air Flow of 3.7 m3/min to remove dirt & dust of DG set complete with 30 mtr extension cord of 2 core cooper wire min 6 sqmm all as specified and directed by Engineer-in-charge.
S&F door lock assembly with keys suitable for aqustic enclosure for DG sets of any capacity including all accessories as per existing make complete all as specified and as directed.
Supply only Rotary Barrel hand Pump with dual direction operation heavy-duty cast iron body with 3 mtr PVC pipe complete all as specified and as directed
M&L for cable in trenches or passing through pipe, XLPE LT cable, insulated, heavy duty, galvanised steel strip or wire armoured electric cable with stranded aluminium conductor for 1100 volts grade, cross sectional area 240 sq.mm, 3.5 core complete all as specified and as directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and as directed by Engineer-in-charge.
M& L for spreading clean dry sand(tibba sand) in trenches for cushioning to UG LT cable and punning to provide required cover to UG cable complete all as specified and directed by Engineer-in-charge. Note :- Punned thickness shall be measured for the purpose of payment.
Supply & laying Precast concrete cable cover class LV, Type 1, flat, size 250mm x 150mm x 40mm complete all as specified & directed by Engineer-in-charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in any type of soil complete all as specified and as directed by Engineer-in-charge.
Removing excavated materials to a distance not exceeding 50m depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-charge.
Note:- Schedule of credit as per availabilty at site, Contractor will not claim for the same during execution of work.
Shri Electrical Enterprises (BID ID -3252731)
KALWA TRANSPORTER AND SUPPLIERS (BID ID -3252321)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .