Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 LAccepted-AOC VILL PO PIRUMADARA TEH RAMNAGAR DISTT NAINITAL UK | RAMNAGAR | NAINITAL | UTTARAKHAND | L1 | Accepted-AOC Being the lowest bidder | |
| 2 | L2₹26.8 L+₹7.7 L (40.1%)Rejected-AOC | L2 | Rejected-AOC Being other than the lowest bidder | |
| 3 | L3₹32.7 L+₹13.6 L (71.1%)Rejected-AOC | L3 | Rejected-AOC Being other than the lowest bidder |
Tender Value
₹34.5 L
EMD Value
₹69,000
Closing Date
19 Oct 2024, 6:00 pmClosed
GE EAST BAREILLY
Garrison Engineer East Military Engineer Services Shahjahanpur Road Bareilly Cantt
MAINT AND REPAIR/ REPLACEMENT OF CI, GI PIPE LINES, SUBMERSIBLE PUMPING SETS, REWAGE PUMPING SETS, WATER TREATMENT SYSTEM ETC, AT RTS AND DEPOT HEMPUR UNDER GE (E) BAREILLY
2024_MES_675639_1
8370/E8
Open Tender
Civil Works - Water Works
Item Rate
245 days
Hempur
as per NIT
5 documents required · 5 mandatory
₹500
GE EAST BAREILLY
₹69,000
Yes
17 Dec 2024
20 Sept 2024
21 Oct 2024
20 Sept 2024
19 Oct 2024
5 Oct 2024
Amount
Lifting/ taking out defective submersible pump of any capacity alongwith column pipe of any size and submersible cable, dismantling the pump from motor, setting aside for repair /servicing / overhauling including lowering the pump set into bore well replacement of packing and nut bolts (if required) and testing after the completion of repair works in the presence of JE/ Engineer-in-Charge complete all as specified and directed.
Disconnections of electric connection of the starter of 15/25/35 HP pumping set for repairs installed at LT Panel in the pump house, carefully checking the parts throughly & replacement of unserviceable parts such as electronic Motor Protection relay with inbuilt earth fault protection, Over load protection relay ranging 16 -100Amp, MNX-16-100 contractor, NO-NC for starter, (Front add on auxiliary contact block) and electronic timers multi time setting type, 240/415 Volt, 50 Hz of range complete all as specified and directed.
M&L for cleaning of under ground sump of capacity 10000 Glns at RTS & Depot complete with:- (a) Cleaning of water tanks with high pressure water jet with pressure not exceeding 28Kg/Sqcm and remove all masses algae and dirt. (b) Removal of dirty water alongwith sludge using sludge machines and disposal of the same to a safe distance. (c) Scrubbing of floors using industrial vacuum cleaner. (d) Applying of anti bacterial sterilization to walls floors and roofs of tanks. (e) Removing of all vegetation nearby to UG tank and thrown to 50 meters away.
M&L for cleaning of over head Reservoir of capacity 10000 Glns of height up to 21mtr complete with:- (a) Cleaning of water tanks with high pressure water jet with pressure not exceeding 28Kg/Sqcm and remove all masses algae and dirt. (b) Removal of dirty water alongwith sludge using sludge machines and disposal of the same to a safe distance. (c) Scrubbing of floors using industrial vacuum cleaner. (d) Applying of anti bacterial sterilization to walls floors of sump. (e) Removing of all vegetation near by to OH tank and thrown to 50 meters away.
All as per item No 4.00 here-in-before but over head reservoirs of capacity 25000 Glns at RTS & Depot.
Dismantling and taking up or down unserviceable / cracked GI tubing any dia with all fittings including separating the serviceable pipes/ tubes cleaning the same deposit to E/M store yard complete all as specified and directed.
Re-laying, jointing 100 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 80 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 50 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 40 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 25 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 20 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Re-laying, jointing 15 mm bore dia of GI tubing and connections in new or old position including new fittings such as bends, elbows, union, tees, reducers etc; as required at site laid in trenches or on floors complete all as specified and directed.
Supply, Laying, jointing and leakage testing 100 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 80 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 50 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 40 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 25 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 20 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
Supply, Laying, jointing and leakage testing 15 mm bore dia of pipe GI Pipe medium grade including all fittings such as bend, tee, elbow, union, reducer etc, laid in trenches complete all as specified and directed.
S&F 50 mm bore dia of pipe Gun-metal, globe or Gate Valve with iron wheel head, screwed both ends for iron pipe, ISI marked including taking down of unserviceable existing gate valve complete all as specified and directed.
S&F 40 mm bore dia of pipe Gun-metal, globe or Gate Valve with iron wheel head, screwed both ends for iron pipe, ISI marked including taking down of unserviceable existing gate valve complete all as specified and directed.
S&F 25 mm bore dia of pipe Gun-metal, globe or Gate Valve with iron wheel head, screwed both ends for iron pipe, ISI marked including taking down of unserviceable existing gate valve complete all as specified and directed.
S&F 20 mm bore dia of pipe Gun-metal, globe or Gate Valve with iron wheel head, screwed both ends for iron pipe, ISI marked including taking down of unserviceable existing gate valve complete all as specified and directed.
S&F 15 mm bore dia of pipe Gun-metal, globe or Gate Valve with iron wheel head, screwed both ends for iron pipe, ISI marked including taking down of unserviceable existing gate valve complete all as specified and directed.
M&L for dewatering complete trenches manually for repairing 80 mm bore dia DI/GI pipe joints by cocking and inserting spurn yarn and Run lead joint, making good/ leak less the existing joint including necessary excavation and earth work like returning, filling etc for pipes of following bore complete all as specified and directed.
M&L for dewatering complete trenches manually for repairing 100 mm bore dia DI/GI pipe joints by cocking and inserting spurn yarn and Run lead joint, making good/ leak less the existing joint including necessary excavation and earth work like returning, filling etc for pipes of following bore complete all as specified and directed.
M&L for dewatering complete trenches manually for repairing 150 mm bore dia DI/GI pipe joints by cocking and inserting spurn yarn and Run lead joint, making good/ leak less the existing joint including necessary excavation and earth work like returning, filling etc for pipes of following bore complete all as specified and directed.
Supply and laying of 150 mm bore centrifugally cast (Spun) ductile iron pressure pipe with spigot & socket end, class K-9 in any length laid in trenches, conforming to IS-8329/2000 with cement mortar lining with and including rubber gasket jointing conforming to IS-15382/tyton joint complete with all fittings e.g Tee, Bends etc complete all as specified and directed.
Supply and laying of 100 mm bore centrifugally cast (Spun) ductile iron pressure pipe with spigot & socket end, class K-9 in any length laid in trenches, conforming to IS-8329/2000 with cement mortar lining with and including rubber gasket jointing conforming to IS-15382/tyton joint complete with all fittings e.g Tee, Bends etc complete all as specified and directed.
M&L for run lead joint spigot and socketed of 100 mm bore dia of pipes and fittings complete all as specified and directed.
M&L for run lead joint spigot and socketed of 150 mm bore dia of pipes and fittings complete all as specified and directed.
S&F DI fittings for Flanged pipe, DI Bends, connecting pieces, bell mouth pieces, tapers, tee pieces of one end flanged and other end spigot or socket upto 150 mm bore complete all as specified and directed.
M&L for construction of brick masonry valve pit of size 90x90x90cm (internal dimension) one brick thick wall built in CM (1:4) on 100mm thick PCC (1:4:8) type D2 (using 40mm graded crushed stone aggregate) as in foundation, and 15mm thick rendering in cement mortar (1:4) both externally and internally, external plaster shall be up to 15cm below GL, providing valve pit cover made of 3.15mm thick MS sheet/plate, including provision of hinges, handle and locking arrangement including 40 X 40 X 5mm angle iron frame fixed on top of valve pit by means of MS hold fast 40x5mm and 150mm long, embedded in PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) including two coats of anti-corrosive paint over a coat of red oxide zinc Chrome primer and necessary earth work in soft/loose soil including demolition of old unserviceable existing valve pit & pit cover complete all as specified and directed.
S&F 100 mm bore dia of sluice valve class PN-1.6 heavy duty flanged ends drilled ISI marked confirming to IS: 14846 suitable for following bore pipe, wheel operated (Handle) with high tensile stainless steel spindle, including nuts, bolts and jointing with jointing materials etc. including taking out old existing unserviceable sluice valve including making arrangement for safe working complete all as specified and directed.
S&F 80 mm bore dia of sluice valve class PN-1.6 heavy duty flanged ends drilled ISI marked confirming to IS: 14846 suitable for following bore pipe, wheel operated (Handle) with high tensile stainless steel spindle, including nuts, bolts and jointing with jointing materials etc. including taking out old existing unserviceable sluice valve including making arrangement for safe working complete all as specified and directed.
S&F CI non return sluice valve flanged ends of class 1.6 PN, size 100mm bore dia including taking down old existing unserviceable non return valve complete all as specified and directed.
M&L for repair to leaking joints for 150 mm bore dia of CI/ DI pipe, spigot and socket pipes and fittings, of following sizes of bore in water mains, by burning out old lead joints in position including provision of run lead and including necessary excavation and earth work complete all as specified and directed.
M&L for repair to leaking joints for 100 mm bore dia of CI/ DI pipe, spigot and socket pipes and fittings, of following sizes of bore in water mains, by burning out old lead joints in position including provision of run lead and including necessary excavation and earth work complete all as specified and directed.
M&L for repair to leaking joints for 80 mm bore dia of CI/ DI pipe, spigot and socket pipes and fittings, of following sizes of bore in water mains, by burning out old lead joints in position including provision of run lead and including necessary excavation and earth work complete all as specified and directed.
M&L for tapping from existing 150/ 100/ 80mm bore CI water mains by drilling for 15/ 20mm dia furrel and connection with 40/ 50mm bore extension line complete all as specified and directed.
Supply and laying in trenches of 100 bore dia CI pipe centrifugally cast spigot & socketed end of size 150mm dia including taking up existing cast iron water mains including all fittings with spigot & socket ends and lead Joints including burning out joints and recovering lead complete all as specified and directed.
Supply and laying in trenches of 80 bore dia CI pipe centrifugally cast spigot & socketed end of size 150mm dia including taking up existing cast iron water mains including all fittings with spigot & socket ends and lead Joints including burning out joints and recovering lead complete all as specified and directed.
S&F cast iron fittings such as bends, tapers, Tee pieces, Y junction, cross collar, caps and plugs etc of any type as required for bore of pipe up to150 mm dia complete all as specified and directed.
Dismantling the submersible pump assembly capacity 15 HP completely, checking and segregating serviceable / unserviceable parts, cleaning serviceable parts thoroughly by approved method, replacement of worn out parts including necessary lath / machinery work including all new parts as required, re-assembling the pump completely lowering the pump alongwith all accessories to the existing location, overhauling, commissioning, testing and connecting up complete including painting all as specified and directed. Note:- Spare parts shall be measured and paid separately under respective items.
Supply only discharge outlet
Supply only stage casing
Supply only pump shaft
Supply only key for impeller
Supply only key for pump coupling
Supply only bearing sleeve
Supply only stage Bowl bush
Supply only DOL Bush
Supply only nut Stud kit
Supply only NRV
Dismantling, cutting and removing the burnt windings from the submersible motor of capacity 15 HP, rewinding with suitable size / gauge of super enameled / copper conductor and other approved insulating materials, heating, drying and replacement of existing size of submersible cable including varnishing, overhauling, reassembling the motor, installing, commissioning, testing and connecting up complete all as specified and directed. Note:- Spare parts shall be measured and paid separately under respective items.
Supply only oil seal set
Supply only `O` ring set
Supply only motor bearing Bush set
Supply only complete Pad set (Bearing assembly)
Supply only rotor sleeve set
Supply only thrust plate with ferredo lining
Supply only upper/ lower bearing house
Supply only balancing ring
Disconnections of electric connection of centrifugal pump and motor capacity of 25 HP, lifting and removing motor form its existing foundation to the location (in side/outside of building) where directed by the GE. Dismantling the pump and motor of capacity 25 HP, carefully checking, segregating serviceable and unserviceable parts, cleaning the serviceable parts thoroughly by approved method (Pats like stator, rotor, terminal box, bearings shaft, key etc) heating, drying & varnishing including replacement of burnt winding for 25 HP motor with super enameled copper wire of existing gauge and good quality of insulating materials including replacement of unserviceable parts as required including necessary lath / machining work. Reassembling the pump and motor including painting with two coats of synthetic enamel paint after necessary surface preparation, marking of number (SM, MES or srl No) installing to its existing foundation, commissioning, connecting up and testing complete as directed. Note:- Spare parts shall be measured and paid separately under respective items.
Supply only 25 HP Pump Bearing No 6310 or suitable size
Supply only pump bearing seat suitable for 3 ph 25 HP motor
Supply only motor side cover suitable for 3 ph 25 HP motor
Supply only motor connected plate six hole suitable for 3 ph 25 HP motor
Supply only 25 HP Motor Bearing No 6308 or suitable size
Supply only 25 HP Motor Bearing No 6309 or suitable size
Dismantling the sewage pump set up to 5 HP, carefully checking, segregating serviceable and unserviceable parts, cleaning the serviceable parts thoroughly & including replacement of unserviceable parts as required (Block piston, Nozzle, head block, coupling engine parts & Impeller, gland packing, Pump shaft, pump seal Pump parts) including necessary lath / machining work. Reassembling the pump and engine parts including painting with two coats of synthetic enamel paint after necessary surface preparation, marking of number (SM, MES or srl No) & replacement of unserviceable suction & Delivery PVC pipe, flange, clamps, foot valve etc and testing complete as directed.
S&F green & red button operated push type, Star Delta Starter Oil merged with Single Phase Preventer, Type designation BSA, Operating current 18Amp, coil voltage 380 _+15% , 3 phase 415V 50 Hz suitable for 15 HP Submersible Pump and Motor complete with Over load tripping circuit (Max relay (14-20 Amp), Reverse phasing , unbalancing, Low voltage , high voltage upto motor terminal and starting time delay and should be housed in Dust proof, Moisture proof and powder coated sheet metal fabricated box with locking arrangement with extra long life contact with arrangement including taking down of existing starter complete all as specified and directed.
S&F green & red button operated push type, Star Delta Starter Oil merged with Single Phase Preventer, Type designation BSA, Operating current 28Amp, coil voltage 380 _+15%, 3 phase 415V 50 Hz suitable for 25 HP Centrifugal Pump and Motor complete with Over load tripping circuit (Max relay (20-40 Amp), Reverse phasing , unbalancing, Low voltage , high voltage upto motor terminal and starting time delay and should be housed in Dust proof, Moisture proof and powder coated sheet metal fabricated box with locking arrangement with extra long life contact with arrangement including taking down of existing starter complete all as specified and directed.
S&F DOL starter three phase 415 volt 50 Hz push button type suitable for 05/7.5 HP centrifugal pump set with arrangement and making the necessary connection in panel and pump set including taking down of existing starter complete all as specified and directed.
M&L for painting to pipe of pump house rising mains hydrants, sluice valves, pipe, fittings, NRV, discharge head etc after cleaning, scrapping and making the surfaces free from rust of main externally and painting with two coats synthetic enameled paint in black/ blue/ red including marking/ writing on pipe etc complete as specified and directed.
S&F in repair electric shock treatment chart coloured of size 90 x 60 x 6 mm thick plywood with wood frame including covered with plastic laminated sheet complete all as specified and directed.
S&F in repair machinery maintenance chart coloured of size 3 ft x 2 ft & 6 mm thick plywood with wood frame including covered with plastic laminated sheet complete all as specified and directed.
M&L for trimming vegetation or small inequalities clearing all grass vegetation, saplings, shrubs, brushwood, roots, and tree of surroundings area up to 500 sq mtr including cleaning and removing rubbish upto a distance of 50 mtr outside the periphery of the area under clearance of water supply installations complete all as specified and as directed.
S&F in repair for aviation light on OH tank 18/21 mtrs staging (on top of OH tank) with all fittings, fixtures and accessories including 2.5 sqmm wire Three core in 20 mm PVC conduit from light to connection points including 2-way MCB DB with isolator (10 Amp) capacity complete all as specified and directed.
Supplying, Laying, jointing and testing 2.5 Sq mm 2 core, PVC insulated, armoured, heavy duty, Copper conductor cable 1100 volts grade, laid in trenches/ ducts, floors, fixed to pole / walls etc. complete all as specified and directed.
S&F in repair for glow sign board (box type) LED of required size 3600 x 600 x 300 mm made out of MS sheet of suitable size with sheet fixed on front and quality marked with details of Pump House etc on front and rear with different colours including provision of LED power- fittings & fixtures in equal distance to illuminate board including connections with 2.5 sqmm single core stranded copper conductor cable and writing with 10 mm size letters as specified and directed.
S&F in repair 1100 volts grade heavy duty cable PVC insulated aluminum conductor screened served with inner sheathing of PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4mm GI suspension wire, one twin core cables flat or circular of size 10 Sqmm etc complete all as specified and directed.
S&F in repair Off load change over switch 200 Amp, 4 pole, 415 Volts, 50 Hz, complete all as specified and directed.
S&F in repair energy saving and environemntal friendly long life versatile pressure die-cast aluminium IP-65 roadway luminaire 72 W LED fitting with high power LEDs light source and electronic driver etc complete as specified and directed.
S&F in replacement of LED Post top lantern 45 watts made in cast aluminium with innovative glare free indirect lighting distribution and IP65 protection for different applications suitable for mounting on pole dia 50 mm complete all as specified and directed.
S&F in repair GI bracket made out from GI pipe 25/32mm dia, 1.20 m long fixed on wall with and including nut, bolts and GI clamps of size 25x4mm as required & including painting etc complete all as specified and directed.
M&L for replacement of PVC insulated single core multi stranded copper cable of size 1.5 sq mm unsheathed 1100 volts grade drawn through conduit / casing capping on surface / pole / wall concealed and making good of disturbed surface including taking down unserviceable wire etc complete all as specified and directed.
S&F in replacement of LED Bldg Security light fitting 30 Watts, 6500 K, 230 Volts, AC, Outdoor type Street Lights with high pressure die cast aluminium housing and best in class design & Robust heat sink along with class leading IP, IK & Surge protections for long lasting performance including connecting up with driver three core flexible copper conductor cable of suitable size, lamp & IP 65/66 protection complete all as specified and directed.
M&L for earthing complete with using GI earth plate electrode 600x600x6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness off 15 cm all around the plate with using GI Strip 25 x 4mm as earth lead moulded and retrieved to earth plate at one end and connected to main switch / control board at another end with and including 15 mm dia GI light grade from upper end of earth plate upto external face of the wall of the building including 20 mm dia bore GI pipe light grade as water pipe from chamber to upper edge of the plate GI funnel with wire mess fixed on water pipe and provision of PCC 1:2:4 type B-1 (Using 20 mm Dia graded stone aggregate) duly reinforced with mild steel round bar 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handle with and including necessary excavation and earth work including laying the pipe concealed in floor / wall allas per plate NO-3 of SSR Part-I complete all as specified and directed and testing on completion (Note:- If the desired resistance is not found earthing shall be done by the contractor at no extra cost to Govt).
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4mm galvanised iron strip complete all as specified and as directed.
Supply, installation, testing and commissioning of Changeover LT panel, indoor type cubical panel board, made out of 2mm thick CRCA sheet, duly powder coated, CPRI approved compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, free standing floor mounted with copper busbar 630 Amps for phase and neutral mounted on hygroscopic insulators comprising of the following:- INCOMER:- (i) MCCB 4 pole 200A, 415V, 50Hz, 25 kA - 02 Nos. (ii) Changeover switch 415Volt, 50Hz, 4 Pole, 200 Amp - 1 No. OUTGOING:- (i) MCCB 4 pole 160A, 415V, 50Hz, 16 kA - 02 No. (ii) MCCB 4 pole 100A, 415V, 50Hz, 16 kA - 01 No. (iii) MCB TPN 40A, 415V, 50Hz, 10 kA - 02 Nos. (iv) MCB SPN 20A, 415V, 50Hz, 10 kA - 02 No. METERING & INDICATION:- (i) Ammeter, Digital type, 0-200 A with CTs- 01 set. (ii) Voltmeter, Digital type 0-500V with - 01 set. (iii) R-Y-B phase indicating lamps with 3 Nos. - 01 set. (iv) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
S&F in repair of MCB TPN DB 4 Way, (4+12) suitable for flush mounting and surface mounting, conforming to IP 43 - IK 09 with acrylic door with 100 Amp copper bus bar for each phase, complete with din rail, Neutral and earthing bar after taking out the old unserviceable DBs, connection complete and making good the disturbed surfaces complete all as specified and as directed.
S&F in repair of DX3 AC MCB SP, 240 Volt, 6 to 32 Amp, 10 KA, ISI Marked, "C" Curve, IP 20 Protected terminals complete all as specified and as directed.
S&F in repair of DX3 AC MCB TPN, 415 Volt, upto 63 Amp, 10 KA, ISI Marked, "C" Curve, IP 20 Protected terminals complete all as specified and directed.
Supply only calcium based granularhypo chlorite 65% to 70% disinfectant for water treatment, Packing in 45 Kg, plastic drums complete all as specified and directed.
M&L for MCCB 4 pole, 415 Volt, fixed type 125 to 160 amp with breaking capacity 36 kA complete all as specified and directed.
M&L for MCCB 4 pole, 415 Volt, fixed type 160 to 200 amp with breaking capacity 35 kA complete all as specified and directed.
Repair and servicing of powder base dosing plant for smooth functioning including necessary spares as required for rectifying the defects for smooth functioning for the following plants :- Location: - (i) The cost of complete spares, rewinding & repair of mixing motor is deemed to be included in the quoted rate. (ii) All testing equipments to be available in installations.
Taking out connection of Chlorine/ Altoch dosing system, detecting fault and repair /replacement of unserviceable parts and re-fixing same after completion job and connecting dosing system and testing complete all as specified and directed. (NOTE: Spares parts shall be measured and paid separately as Supply only)
S&F in repair rotor assembly with bearing brackets and tolerance rings suitable for decree dosing pump complete all as specified and directed.
S&F in repair pump tube suitable for dosing pump complete all as specified and directed.
S&F in repair injector assembly suitable for dosing pump complete all as specified and directed.
M&L MCCB 4 pole, 415 Volt, fixed type 63 to 100 amp with breaking capacity 16 kA complete all as specified and directed.
S&F in repair weighted suction line stainer suitable for dosing pump complete all as specified and directed.
S&F in repair agitator motor electric driven 230 Volts, 50 Hz, Single phase,120 W, 900 RPM copper wounded complete all as specified and directed.
S&F in repair PVC pressure hose pipe upto 10 to 20Kg/cm2 as per existing size complete all as specified and directed.
S&F in repairs digital multi programmable electronic timer capacity for 24 hrs clock, 3 phase, 415 volts, 50 Hz complete all as specified and directed.
S&F in repair electronic single phase preventer operation on 415 volts 50 Hz complete all as specified and directed.
M&L for grass and weeds killer chemical 5 Ltrs capacity complete all as specified and directed.
S&F LT rubber mat of size 1.0m x 2.0m x 12 mm at water supply installations complete all as specified and directed.
S&F pressure gauge of dial 30 to 60Kg/cm2, suitable for fixing at MS pipe 100/ 150 dia header with all fiting and fixtures etc. complete all as specified and directed.
S&F over load protection relay suitable for 5HP to 25HP monoblock/centrifugal/ submersible motors complete all as specified and directed.
S&F in repair MNX contactor 16Amps to 40Amps, 3 Pole with NO and NC complete all as specified and directed.
S&F in repair MNX contactor 63Amps to 100 Amps, 3 Pole with NO and NC complete all as specified and directed.
S&F in repair spare kit for MNX contactor 16Amps to 100 Amps, 3 Pole complete all as specified and directed.
S&F in repair 15 mm.bore dia bib tap standard of PTMT any colour high pressure screwed for iron pipe and fixed (Minimum weight 15mm-90gms) complete all as specified and directed
S&F in replacement MS ERW column pipe screwed 125 mm nominal bore having wall thickness not less than 7.11 mm electric resistance welded with MS flanged 16 mm thick heavy duty confirming to IS 6392 including 2 mm thick rubber sheet and steel nuts and bolts 10 mm long with washer etc complete all as specified and directed.
S&F in replacement MS ERW column pipe screwed 100 mm nominal bore having wall thickness not less than 7.11 mm electric resistance welded with MS flanged 16 mm thick heavy duty confirming to IS 6392 including 2 mm thick rubber sheet and steel nuts and bolts 10 mm long with washer etc complete all as specified and directed.
Take the water sample from the bore well at PH No.1, 2, 3, 4 & 5 and two consumer end and send it for physical / Chemical / Bacteriological test from any recognized govt agency and provide its report to Engineer-in-charge complete all as specified and directed.
S&F in replacement submersible pump/ motor 15/20 HP, Electric driven, 415 Volts, TP suitable for bore well casing pipe 200/250 mm, Head 70-90Mtr, 2250 LPM, vertical type complete all as specified and directed.
S& F in replacement submersible pump/motor 7.5/10HP, Electric driven, 415 Volts, TP suitable for Open well/Semi UG Sump, Output dia- 80/100 mm, Head 70-90Mtr, 2250 LPM, Horizontal type complete all as specified and directed.
All as per above item No 100 here in before but 5 HP, 415 Volts, TP.
S&F in replacement submersible pump/motor 1.0/1.5 HP, Electric driven, 230 Volts, SP suitable for Open well/Semi UG Sump, Output dia- 20/25 mm, Head 70-90Mtr, 120-150 LPM, Horizontal type, complete all as specified and directed.
S& F in replacement submersible pump/ motor 01/02 HP, Electric driven, 230 Volts, SP, suitable for 25/20mm dia output, bore well casing pipe size 100/150 mm, Head 70-90 Mtr, 100-150 LPM, Vertical type, complete fitting/ fixtures with starter panel complete all as specified and directed.
S& F in replacement Monoblock self priming HI-Flow pump/motor 01/02 HP, Electric driven, 230 Volts, SP suitable for 25/20mm dia output, Head 70-90 Mtr, 120-150 LPM complete fitting/ fixtures with starter panel complete all as specified and directed.
Supply, testing and commissioning submersible cable flat 10.0 sqmm x 3 core PVC insulated and PVC sheathed with multi stranded copper conductor 1100 volts grade fixed to submersible motor column pipe using suitable size of clamps made out of stainless steel flat of size 20x2 mm with steel nuts bolts & washer foe every column pipe of 3 mtr lenght complete all as specified and directed.
All as per item No 105 here-in-before but 6.0 sqmm x 3 core
All as per item No 105 here-in-before but 4.0 sqmm x 3 core
All as per item No 105 here-in-before but 2.5 sqmm x 3 core
Supply, install, testing and commissioning of mild steel chlorine gas cylinder suitable for 100Kg capacity with filling liquid chlorine gas, industrial type as manufacturer recommended pressure for usage of drinking water treatment for improving taste, safety and odour of drinking water, highly reactive, reliable, optimum quality to kill Bacterial organisms at public properties, complete all as specified and as directed.
Supply, install, testing and commissioning of Remote wall/ floor panel mounted Vacuum Chlorinator (regulator) for reduces the gas from a varying supply pressure 10kg- 75kg capacity with safety kit complete set suitable for disinfection of water through gravity feed, Vacuum feed or motor feed chlorination by main water supply/ swimming pools/ sewage water treatment etc, complete all as specified and directed.
M&L for solar street light 45watts, alongwith battery backup complete cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-22 (8.5 metre Long) and applying one coat of steel primer and one coat of aluminium paint and pole ser number as per existing number including Earth work, excavation, foundation, PCC 1:3:6 type C-2 and coping in PCC 1:3:6 type C-1 of pole complete all as specified and directed.
Supply & erection of Water CO2 type Extinguisher 9 ltr capacity in HP Mild Steel Cylinders ISI marked / approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with Foam compound complete in all respects including wall suspension bracket and conforming to IS:15683 complete all as specified and directed.
Supply & erection of ISI marked (IS:15683) Fire Extinguisher seamless construction, carbon-di-oxide type capacity 4.5 Kg flat base including valve, discharge hose of not less than 10 mm dia., 1M long and complete in all respects including initial fill with CO² gas conforming to IS:307-1966 filled to a filling rate of not more than 0.667 and with wall suspension bracket complete all as specified and directed.
Supply & erection of 6 kg capacity ABC (Powder type) Fire Extinguisher in HP Mild Steel Cylinders ISI marked / approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683.
Supply & erection of 9 kg capacity ABC (Powder type) Fire Extinguisher in HP Mild Steel Cylinders ISI marked / approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683.
Supply, installation, Commissioning and testing for Chemical dosing system metering type, capacity to deliver 14- 27 LPH max & adjustable from 10% to 100% through Knob and suitable to inject against 5-10Kg/cm2 pressure duly operated by 240V, Single phase power supply, Chemical Solution preparation tank of 200 Ltrs capacity made out of FRP (made with Biphenyl resins) having port hole on lid for pouring chemical, water inlet connection, overflow and drain with valve, outlet connection with PP ball valve for transferring solution to chemical dosing tank of 100 Ltrs capacity made out of FRP (made with Biphenyl resins) having port hole on lid, inlet connection and tank lid duly mounted with agitator made of Stainless Steel -316 operated with single phase FHP electric motor for dissolution of chemical, dosing pump shall be complete with inlet /outlet check valves, strainer cum foot valve and tubing for suction/delivery injection line including fittings etc. complete all as specified and directed.
Disconnecting, taking out and removing old existing unserviceable underground, 16 Sqm x 4 core LT cable of any description and in any position complete including taking down protection pipe, PCC Cover/ Bricks etc. complete all as specified and directed.
All as per item No 117 here-in-before but 25 Sqmm x 4 core
All as per item No 117 here-in-before but 35 Sqmm x 3.5 core
All as per item No 117 here-in-before but 50 Sqmm x 3.5 core
All as per item No 117 here-in-before but 70 Sqmm x 3.5 core
Supply, laying, jointing and testing of 16 Sqmm x 4 core XLPE cable, PVC insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed.
All as per item No 122 here-in-before but 25 Sqmm x 4 core
All as per item No 122 here-in-before but 35 Sqmm x 4 core
All as per item No 122 here-in-before but 50 Sqmm x 3.5 core
All as per item No 122 here-in-before but 70 Sqmm x 3.5 core
Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope / gradient for laying cables/ pipes etc. all as specified and directed including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers.
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed.
Removal of surplus excavated soil exc. 50 mtr but n. exc. 250 mtr distance and depositing where directed at a level not exceeding 1.5 M above the starting point etc complete all as directed.
Supply and laying new dry river sand laid in trenches 8.0cm below the cable and 15cm above the cable and gently punned to 18.0cm as cable cushioning and covering complete all as specified and directed. (Note:- Only punned 18 CM thick sand cushioning shall be measured and paid)
Supplying & laying sub class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed.
M&L for boring the holes under roads pavements, hard standing by trench less technology, using ultrasound technique and necessary machine including CI Pipe of 100 mm/150 mm bore suitable for 0.4 MPA working pressure complete all as specified and directed.
Demolition for cement concrete/ road in ground floor and paving n. exc 15 cm thickness below or above ground level including removal of rubbish to a distance exc 1.50 KM and n.exc 5.00 KM etc complete all as specified and directed.
M&L for 100 mm thick PCC 1:2:4 type B2 (using 40 mm graded stone aggregate) complete all as specified and directed.
M&L for 40 mm thick PCC 1:2:4 type B1 (using 20 mm graded aggregate) as in floor finishing even and smooth with using extra cement and making impression of expanded metal, whilst concrete making good as per existing surface etc complete all as specified and directed.
S&F display board of outer size 4.1X1.0 mtr made out of stainless steel of thickness 2 mm at square pipe 8X8 cm with back support of 40X5 mm stainless steel plate fitted at 3 feet interval of board backside including writing name of installation and unit as directed with reflecting tape of any colour as directed alongwith legs of size 8X8 cm square pipe upto the height of 14 feet from ground with foundation with stand 26 km/hr air velocity alongwith 02 nos of spot light at suitable place as directed with point wiring complete all as specified and directed.
HASINI ENTERPRISES (BID ID -3137015)
sunder and company (BID ID -3144533)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .