| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC DOOR NO IV 400 NEAR RAMANTHALI GHSS RAMANTHALI PO KANNUR 670308 | KANNUR | KERALA | 670308 | L1 | Accepted-AOC Accepted, being lowest and reasonable. | |
| 2 | L2₹30.8 L+₹3.0 L (10.7%)Rejected-AOC | L2 | Rejected-AOC Not accepted. |
| Sl No | Description | Qty | Unit | Phejays Agencies L2 | SREEKRUPA ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | Material and Labour for prestressed concrete pole 11 metre long, 152mm x 152mm at top and 152 mm x 260mm at bottom class 9 including taking down old unserviceable concrete pole complete all as specified and directed. | 5 | Each | 15,000 ₹75,000 | 11,000 ₹55,000 Lowest |
| 2.00 | Dismantling stay assembly including demolition of concrete and opening of nuts, bolts complete all as specified and directed. | 4 | Each set | 500 ₹2,000 Lowest | 500 ₹2,000 Lowest |
| 3.00 | Supply and fix in replacement stay assembly complete with 20mm dia, 1800mm (min) long GI stay rod with threaded ends and GI nuts with washer, two numbers thimbles MS clamps made out of 40mm x 6mm flat iron including MS nuts, bolts, washers and 300mm x 300mm x 6mm MS stay plate, stay bow of size 40 cm long 14 mm dia, loop type insulator including painting the exposed MS work with 2 coats of aluminium paint over a coat of red oxide primer complete all as shown in electrical plate No 1 complete all as specified and directed.
(Note: Earth work, concrete work, stay strand and clamps shall be measured and paid for separately). | 4 | Each | 4,500 ₹18,000 | 4,000 ₹16,000 Lowest |
| 4.00 | Material and Labour galvanised stay strand, size 7/4.0 mm complete all as specified and directed . | 0.4 | Quintal | 15,000 ₹6,000 Lowest | 18,000 ₹7,200 |
| 5.00 | Material and Labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate including use and waste of form work of concrete for pole and stay foundation complete all as specified and directed. | 0.5 | Cubic Metre | 6,500 ₹3,250 Lowest | 6,500 ₹3,250 Lowest |
| 6.00 | Material and Labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate including use and waste of form work for pole coping/ any description complete all as specified and directed. | 3.1 | Cubic Metre | 7,000 ₹21,700 | 6,000 ₹18,600 Lowest |
| 7.00 | Material and Labour for PCC 1:2:4 type B1 using 20mm graded stone aggregate including use and waste of form work for pole coping/ any description complete all as specified and directed. | 0.5 | Cubic Metre | 7,500 ₹3,750 | 6,000 ₹3,000 Lowest |
| 8.00 | Supply and fix in replacement Danger notice plate for HT of 25 cm x 20 cm x 1.6 mm thick mild steel sheet vitreous enamelled white, with letters, figures and conventional skull and bones and written as "DANGER" in signal red colour and including provisionn and fixed with MS clamps made out of MS flat 25 mm x 3mm , including nuts & bolts, including 2 coats of aluminium paint over a coat of red oxide primer including dismantling complete all as specified and directed.
Note :- Words shall be written in three languages viz. -Malayalam, Hindi and English. | 20 | Each | 450 ₹9,000 | 400 ₹8,000 Lowest |
| 9.00 | Material and Labour Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete all as specified and directed. | 5 | Each | 450 ₹2,250 Lowest | 600 ₹3,000 |
| 10.00 | S & F in repairs Disc type porcelain vitreous, brown or white insulator suitable for 11 KV HT working Pressure of size 145 mm height, 225 mm dia , including. one galvanised mild steel spindle, two galvanised iron washer and one GI nut complete all as specified and directed. | 6 | Each | 500 ₹3,000 Lowest | 800 ₹4,800 |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
18 Nov 2025, 6:00 pmClosed
CWE Wellington
Headquarters Commander Works Engineers Wellington, Barracks Post The Nilgiris PIN 643 231
REP AND MAINT TO TRNSFRMR, DEHYDRATION OF TRNSFRMR OIL, CAPACITORS, PAINTING, HT BUSHING ETC REP TO HT OVER HEAD NETWORK AND REP/ REPLACEMENT OF HT UG CABLE, 4 POLE/ 2 POLE STR, GOD, DO FUSE AND HT POLES, CTS ETC AND CONNECTED WKS AT MIL STN KANNUR
2025_MES_737114_1
87044/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KANNUR
As per NIT
7 documents required · 7 mandatory
₹500
GE (ARMY) TRIVANDRUM
₹56,000
Yes
7 Jan 2026
27 Oct 2025
20 Nov 2025
27 Oct 2025
18 Nov 2025
11 Nov 2025
28 Oct 2025 - 4 Nov 2025
Amount
Material and Labour for prestressed concrete pole 11 metre long, 152mm x 152mm at top and 152 mm x 260mm at bottom class 9 including taking down old unserviceable concrete pole complete all as specified and directed.
Dismantling stay assembly including demolition of concrete and opening of nuts, bolts complete all as specified and directed.
Supply and fix in replacement stay assembly complete with 20mm dia, 1800mm (min) long GI stay rod with threaded ends and GI nuts with washer, two numbers thimbles MS clamps made out of 40mm x 6mm flat iron including MS nuts, bolts, washers and 300mm x 300mm x 6mm MS stay plate, stay bow of size 40 cm long 14 mm dia, loop type insulator including painting the exposed MS work with 2 coats of aluminium paint over a coat of red oxide primer complete all as shown in electrical plate No 1 complete all as specified and directed. (Note: Earth work, concrete work, stay strand and clamps shall be measured and paid for separately).
Material and Labour galvanised stay strand, size 7/4.0 mm complete all as specified and directed .
Material and Labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate including use and waste of form work of concrete for pole and stay foundation complete all as specified and directed.
Material and Labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate including use and waste of form work for pole coping/ any description complete all as specified and directed.
Material and Labour for PCC 1:2:4 type B1 using 20mm graded stone aggregate including use and waste of form work for pole coping/ any description complete all as specified and directed.
Supply and fix in replacement Danger notice plate for HT of 25 cm x 20 cm x 1.6 mm thick mild steel sheet vitreous enamelled white, with letters, figures and conventional skull and bones and written as "DANGER" in signal red colour and including provisionn and fixed with MS clamps made out of MS flat 25 mm x 3mm , including nuts & bolts, including 2 coats of aluminium paint over a coat of red oxide primer including dismantling complete all as specified and directed. Note :- Words shall be written in three languages viz. -Malayalam, Hindi and English.
Material and Labour Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete all as specified and directed.
S & F in repairs Disc type porcelain vitreous, brown or white insulator suitable for 11 KV HT working Pressure of size 145 mm height, 225 mm dia , including. one galvanised mild steel spindle, two galvanised iron washer and one GI nut complete all as specified and directed.
Dismantling insulators any type pin/disc/post/Shackle type, any size from HT pole including opening of nuts, bolts complete for depositing the serviceable insulators to MES stores and unserviceable insulators for taking as per schdedule of credit complete all as specified and directed.
Supply & fix new MS Cross arms, bracing, supports, clamps, anti climbing device and back plates fabricated from structural steel section including nuts, bolts, washers with required mech working/ process i.e. cutting, welding, bending, cold or hot, drilling holes, grinding or bolt in any shape or size including 2 coats of aluminium paint over one coat of red oxide including taking out unserviceable complete all as specified and directed . Note : Unexposed surface shall be given one coat of primer only.
Refixing only Cross-arms, Bracings, Supports, Clamps and Back Plates (serviceable materials i.e. Structural Steel Sections obtained from dismantling) including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed including painting complete all as specified and directed.
Dismantling cross-arms of M.S. channel or angle sections etc. from HT poles by opening nuts, bolts complete and setting aside for re-use within 200mtr or depositing to AGE E/M Sub div Kannur store yard complete all as specified and directed.
Supply and fix in replacement lightening arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 KA rupturing capacity conforming to IS suitable for 11 KV, 11000 Volts, HT over head line complete including nuts, bolts, clamps, bracket etc and connecting with GI earth wire complete all as specified and directed.
Supplying and fix in replacement switch Air break Gang Operated AB Switch assembly (polymer insulators) outdoor type HT 11 KV triple pole, 11000 Volts, 200 Amps, vertical mounting type with fixed contacts and moving contacts of phosphorus bronze with mechanically operated from ground level with polymer insulator on steel frame including suitable length GI pipe 25mm dia bore(medium grade) with handle and locking arrangement with 15 Nos polymer insulators with drop out fuses complete including taking out old unserviceable GO AB Switch all as specified and directed and (clamps/cross arms shall be measured and paid for separately). Make: Jaipuria/ Rashtriya or equivalent make approved by GE
All as per item No 16.00 here in before but for 400 Amps capacity complete all as specified and directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. complete all as specified and directed.
Supply and Fixing Cable Jointing Kit for 11 KV grade earthed cable for indoor termination cold shrinkable joint complete with jointing material, thimble and accessories suitable for XLPE insulated, screened, armoured aluminium conductor cable of size 120 sqm to 185 sqmm 3 core including opening cable connections/ taking down, taking old unserviceable joint kit and re-fixing cable complete all as specified and directed.
Supply and fixing Cable Jointing Kit for 11 KV grade earthed cable for outdoor end termination cold shrinkable joint complete with jointing material and accessories suitable for XLPE insulated, screened, armoured aluminium conductor cable of size 120 sqm to 185 sqmm 3 core including opening cable connections/ taking down, taking old unserviceable joint kit and re-fixing cable complete all as specified and directed.
Supply and fixing Cable Jointing Kit for 11 KV grade earthed cable for straight through cold shrinkable joint complete with jointing material and accessories suitable for XLPE insulated, screened, armoured aluminium conductor cable of size 120 sqm to 185 sqmm 3 core including opening cable connections/ taking down, taking old unserviceable joint kit and re-fixing cable complete all as specified and directed. Note for Serial item No. 19 to 21 :- (i) The rate quoted include any type of Excavation, earth work for taking out loop and returning, filling in any type of soil complete all as specified and directed. (ii) The contractor has to arrange min 50% quantity of the items for Serial item No 18 to 20 within 20 days of start of work and shall handed over to concerned JE E/M to ensure availability without fail at any time.
Supply, laying, jointing and testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 11000 volts grade earthed system of size 95 Sqmm 3 core conforming to IS-7098 (Part-II) 1985 laid in trenches, in floor, in duct, through pipes or along the pole including taking out unserviceable HT overhead conductor complete all as specified and directed
All as per item No 22.00 here in before but cable of size 120 sqmm 3 core complete all as specified and directed
Excavation in trenches n .exceeding 1.5 mtr wide and not exec 1.5 mtr depth and getting out in looses/soft soil complete all as specified and directed
Excavating in trenches n.exc 1.5m wide and n.exc 1.5m in depth in soft disintegrated rock for laying of pipes n.exc 10sqm on plan and getting out, complete all as specified and directed
Excavating in trenches not exceeding 1.5 meter wide and exceeding 1.5 meter and not exceeding 3meter in depth for foundation for erection of poles, stays, laying cables, stays etc and getting out in hard / dense soil complete all as specified and directed
Returning filling in including spreading levelling, watering and well ramming in layer not less than 25 cum each layer complete all as specified and directed .
Removing excavated material to a distance not exc 50M and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed .
Material and Labour filling of dry sand under and around LT cable to provide sand cushioning and in sub station ducts/trenches complete all as specified and directed .
Material and Labour for brick well burnt locally available sub class 'B' laid over sand cushioning to cable in trenches keeping width of brick parallel to the length of cable complete all as specified and directed.
Relaying of existing retrieved bricks/PCC cable cover laid in trenches for cable protection perpendicular to the direction of cable length, adjacent abutting each other complete all as specified and directed.
Material and Labour for coarse aggregate (broken stone or boulders) of size 40 mm in sub - station yard for laying complete all as specified and directed.
Material and Labour for boring hole under the road / pavement / hard standing of any width with the help of trenchless technology using ultra sound technique and necessary machine and including HDPE pipe 150 mm of size not less than one metre below ground level complete all as specified and directed.
Supply and fix galvanised pipe light grade of IS marked 100 mm bore for passing of cable fixed to poles/walls/laid under floor/road complete with and including fittings as required including taking out unserviceable pipe complete all as specified and directed.
All as per item No. 34.00 above but of size 80 mm bore complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI strip 32mm x 6mm upto test point and incl Aluminium strip 25x3.15mm from test point to equipment and including GI pipe 40mm bore light grade as protection pipe (from top of earth plate up to the test point) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300x300x300mm (top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate with 1 nos MS handles of 8mm dia including necessary excavation/ earth work in any type of soil/rock and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.
Supply and Fix 25 mm x 4 mm GI strip as earth continuity conductor including from test point to equipment complete all as specified & directed .
Material and Labour for preparation of old painted surface of PCC HT poles and applying two coats of synthetic enamel paint in alternate yellow & black strips of 30 cm each up to 1.5 mtr height from top of PCC coping and numbering of poles and writing 'MES' complete all as specified & directed .
Labour only for cutting / Pruning of tree branches 2.0 mtr all around the HT 2 pole structure / plinth mounted transformer / overhead Joints & removing the branches to a distance not exceeding 200 mtrs to the entire satisfaction of Engineer-in-Charge complete all as specified & directed .
All as per item No 39 here in before but 4 pole structure complete all as specified and directed.
Material and labour for fixing cable route indicators made of PCC (1:3:6) duly engraved “HT CABLE / HT JOINT” coloured with two coats of synthetic paint in brown of size 150 x 150 x 900 mm fixed 300mm below ground level complete all as specified and directed.
Cutting and cleaning of grass upto 10 Mtr X 10 Mtr area by using manually/cutter machine all around and suitable chemical near 4 pole /2 pole structure area complete all as specified & directed.
Cleaning and preparation of old painted surface and painting with one coat of aluminium paint over a coat of red oxide primer to all steel parts, structure such as channel/brackets, bracing, clamps, anti climbing device, cross arms etc complete all as specified and directed. (on 2/4 pole structure) complete all as specified and directed.
Material and Labour for Locating & pinpointing conductor and insulation faults of low and high resistance, intermittent or flashing nature in XLPE HT underground power cables of the rating 11 KV with the help of Pre-locator with time domain laptop based reflectometer/ electrometer using pulse echo method, impulse current method & decay method, and using DC high voltage surge generator to produce surge to trace route and pinpointing fault with the help of dual channel digital sound system, magnetic & acoustic for location of fault with acoustic transducer (pickup) and the amplifier with headphones, after pinpointing of faut location necessary excavation and taking out of faulty cable for repair/ replacement of joint, relaying of cable/ cover & brick protection, refilling of soil and removal of surplus soil etc at Kannur area complete all as specified & directed . Note: The joint kit shall be measured and paid separately under relevant item. The quantity of item will be executed at different times during currency of contract as directed by Engr-in-Charge. Hence, contractor shall quote his rate accordingly for arranging and executing the items accordingly.
Taking down/ out old HT cable of any sizes from trench & pole including disconnecting all electrical connections and depositing serviceable cable in MES store yard for Re-use at same or other site and removing unserviceable cable from site to take credit. . Note: Unsv HT Cable shall be given to contractor as per schedule of credit and serviceable shall be used for re laying.
Material and Labour for HT jumper made of XLPE insulated aluminium conductor of length 1 metre long with crimped thimbles at both ends complete fixing on 2 pole/ 4 pole structure as required at site complete all as specified & directed .
Material and Labour for HT jumper made of XLPE insulated aluminium conductor of length 2 metre long with crimped thimbles at both ends complete fixing on 2 pole/ 4 pole structure as required at site complete all as specified & directed .
Material and Labour in replacement of male contact (moving contact blade) & female spring loaded contact(fixed contact jaw) made of gun metal phosphorus bronze with arcing horns suitable for GO switch continuous current rating 200 Amps, 11000 volts, including nut, bolts, washers etc and taking out unserviceable old fixed/moving jaw contact blade set complete all as specified & directed .
Dismantling of ACSR or AAC conductors, complete all as specified and as directed.
S&F Aluminium Conductor Steel Reinforced (ACSR) (sizes as ordered) with permissible Sags and providing Jumper, etc., fixing on Electric Poles and binding to Insulators with Aluminium Binding Wire as in OH Conductors including stringing, tightening, etc., complete all as specified and as directed. NOTE : Cost of Binding Wire is deemed to be included in the quoted Unit Rate.
Dehydration and filtration of existing transformer oil of transformers of any capacity on site at different locations without disturbing the power supply system with filtration machine and heating system in order to achieve Di-electric strength of oil 58KV minimum at 2.5 mm gap complete all as specified and as directed. Note:- Power Supply for dehydration machine should be arranged by contractor and rate deemed to be included .
Supply & filling up of transformer oil conforming to IS as in topping up / replacement up to desired level of transformer oil capacity complete all as specified and as directed. [Note: Dielectric strength of oil should not be less than 60KV at 2.5 mm gap complete all as specified and directed.]
Supply and fix in repair for 32 mm dia gun metal drain valve of transformer as per existing one complete all as specified and directed.
Supply and fix for in repair 25 mm dia gun metal drain valve of transformer as per existing one complete all as specified and directed.
Supply and fix in repair 20 mm dia gun metal drain valve of transformer as per existing one complete all as specified and directed
Material and Labour for preparation of old painted steel or iron surfaces of transformer of upto 63 KVA , 11/0.433 KV capacity transformers by scrapping with steel wire brush/scrapper emery paper, etc. and applying two coats of epoxy smoke grey paint over a coat of red oxide primer (painting shall be done by spray machine) including writing of SM No, MES No etc. at prominent place/location of transformer with black synthetic enamel thick paint in white back ground complete all as specified and directed.
All as per item No 56.00 here in before but the capacity 100 KVA complete all as specified and directed.
All as per item No 56.00 here in before but the capacity 160/200 KVA complete all as specified and directed.
All as per item No 56.00 here in before but the capacity 250 KVA complete all as specified and directed.
Supply and fix in repair Earth continuity conductor or Main Earthing lead fixed to wall or batten or recess or chasses or buried in ground or drawn in conduit / pipe or fixed to Poles or any other indicated situation for loop copper strip of size 20mmx3mm connected to test point including brazing complete all as specified and as directed.
Supply and fix in repair Earth continuity conductor or Main Earthing lead fixed to wall or batten or recess or chasses or buried in ground or drawn in conduit / pipe or fixed to Poles or any other indicated situation for loop of size 32x6mm galvanised iron connected to test point including brazing complete all as specified and as directed.
Supply and fix in repair Galvanised Iron Pipe 40mm Bore (dia) ‘Light Grade’ for protection earth continuity conductor complete all as specified and as directed.
Material and labour for Shifting after disconnection of transformer from the existing site and install/commission at proposed site same for outdoor type HT 11KV/433 V 3 phase, 50Hz with off load tapping and slandered fitting upto 250 KVA including connection/testing with proper load balancing as per engineering practice, confirming to IS 2026 including connected panel complete all as specified and as directed. Note :- Crane, manpower, T&P and profit are included in the quoted rate
Supply and fix Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and as directed. Note: Cost of dismantling is deemed to be included in the Quoted Unit Rate.
Repair /servicing to transformer at site of capacity upto 160 KVA installed on Plinth/pole mounted structure by opening top cover & replacing unserviceable spares / components of transformer ,without lifting core assembly reassembling after repair, checking and rectification of transformer leakage , complete all as specified and directed . Note :- (a) Replacement of unserviceable parts like; Bush insulator, brass studs, gasket, breather assembly, tap changer,dehyderation and filtration of transformer oil etc shall be measured and paid separately under appropriate Item of schedule. (b) Renewal of adequate size Nut, bolts & washers of transformer top cover shall deemed to be included in unit rate quoted.
All as per item No 65 here in before but the capacity 200/250 KVA complete all as specified and directed.
Taking down carefully the existing 11KV/ 0.433 KV distribution transformer of capacity 63/100 KVA by disconnecting HT overhead connection/underground cables and earth strips etc. from any substation / locations using suitable capacity by crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the transformer after repairs and testing of transformer; transportation to site and unloading including placing at given position and re-commissioning complete all as specified and directed . Note : All the T&P required for disconnection, connection, loading and loading including necessary petty items like bolts, nuts etc will be arranged by the contractor and rates for the same deem to be included in the quoted rate.
Material and labour for repairs toTransformer step down 11KV/0.433 KV any type of capacity 63 KVA to 100 KVA, after dismantling the transformer body carefully, opening the top cover of Transformer for inspection /repair, drain out the transformer oil from the tank complete, taking out the core and winding assy by disconnecting the internal connections, removing the carbon/sludge deposit in transformer housing core, renewal/replacement of u/s rubber bushes and washers , replacement of silica gel, replacement of worn out nut and bolts, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing gauge, insulating the winding connection by using fire proof sleeve and fire proof tape, warnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, Painting of complete transformer body from outside and inside by weather proof type using spray gun, writing of MES/SM Number etc, replacement of conservator tank glass, re-installing the core and winding inside properly, making the all connection with suitable copper lugs, refilling of dehydrated transformer oil including dehydration, reinstalling the top cover after cleaning , conservator tank, expulsion vent etc, Meggering the LT and HT side of the Transformer and testing complete all as specified and directed by Engr-in-Charge. Note :- (a) Cost for Winding wire, nut bolt washer including labour for making of coils are deemed to included in the quoted rate. (b) All other spare parts will be measured and paid separately.
Supply only Ceramic Bush insulators on LT side as per existing size, shape and specification for capacity upto 200 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only Ceramic Bush insulators on LT side as per existing size, shape and specification for capacity 250 to 315 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only brass stud on LT side as per existing size, shape and specification for capacity upto 200 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only brass stud on LT side as per existing size, shape and specification for capacity 250 to 315 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only cork sheet gasket (set of four) for ceramic bushing on LT side as per existing size, shape and specification complete for capacity upto 200 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only cork sheet gasket (set of four) for ceramic bushing on LT side as per existing size, shape and specification complete for capacity 250 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only Ceramic Bush insulators on HT side as per existing size, shape and specification for capacity upto 200 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only Ceramic Bush insulators on HT side as per existing size, shape and specification for capacity 250 to 315 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only brass stud on HT side as per existing size, shape and specification for capacity upto 200 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only brass stud on HT side as per existing size, shape and specification for capacity 250 to 315 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only top cover gasket set as per existing size, shape and specification complete for capacity 200 KVA , 11/0.433 KV transformers complete all as specified and directed.
Supply only top cover gasket set as per existing size, shape and specification complete for capacity 250 KVA, 11/0.433 KV transformers complete all as specified and directed.
Supply only breather assembly as per existing size, shape and specification complete for capacity upto 200 KVA , 11/0.433 KV transformers complete all as specified and directed.
Supply only breather assembly as per existing size, shape and specification complete for capacity 250 to 315 KVA, 11/0.433 KV transformers complete all as specified and directed.
Overhauling servicing of tap changer and replacement of unserviceable parts as ordered with new and assembling with old serviceable parts for smooth functioning and operation complete as all specified and as directed. Note:- Spare parts to be measured separately under items mentioned below.
Supply only Tap Changer as per existing size, shape and specification complete for capacity upto 200 KVA , 11/0.433 KV transformers complete all as specified and directed..
Supply and replacing silica gel Container of breather clear view type including first fill of good quality silica gel of capacity suitable for 63 KVA to 250 KVA transformer complete all as specified and directed.
Taking down/removing of following unserviceable items from the existing Automatic power factor correction (APFC) panel and refixing new of three phase 415 Volt, 50Hz system of capacity upto 200 KVAR. Testing and caliberating APFC panel and confirming the auto switching of capacitors with different loads complete all as specified and directed.
Supply and fixing Cylindrical capacitors 440 V, 50 Hz, 3 phase, 5 KVAR of any model complete all as specified and directed.
All as per item No. 87.00 above but 10 KVAR complete all as specified and directed.
All as per item No. 87.00 above but 15 KVAR complete all as specified and directed.
All as per item No. 87.00 above but 20 KVAR complete all as specified and directed.
All as per item No. 87.00 above but 25 KVAR complete all as specified and directed.
Supply and fix in replacement of HD harmonic detuned reactor for APFC panel capacity upto 100 KVAr Rated Voltage 440 Vac, F = 50 Hz, P = 7% ( Fr = 189 Hz) / Linearity: L > 0.95 Lr for current up to 1.85 . I1, complete all as specified and directed.
Supply and fix in replacement Intelligent Power Factor Controller IPFC, Three CT Sensing, 08, 12 & 16 Steps LCD display Relay, Size: 144 mm x 144 mm Auxiliary supply 90 Vac- 550 Vac, complete all as specified and directed.
Phejays Agencies (BID ID -3477004)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
CompleteTenderDocuments.pdf
Tender Documents • 1.54 MB
BOQ_825345.xls
BOQ • 2.70 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .