Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹13.1 LAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹13.8 L+₹63,476.39 (4.84%)Admitted-Finance | L2 | Admitted-Finance | ||
| 3 | L3₹14.4 L+₹1.3 L (10.1%)Admitted-Finance | L3 | Admitted-Finance | ||
| 4 | L4₹19.7 L+₹6.6 L (50.3%)Admitted-Finance | L4 | Admitted-Finance | ||
| 5 | L5₹21.6 L+₹8.5 L (64.5%)Admitted-Finance | L5 | Admitted-Finance |
Tender Value
₹25.3 L
EMD Value
₹50,600
Closing Date
16 Mar 2026, 2:00 pmClosed
AGM(EM)
FCI RO DEHRADUN
Improvement of internal lighting by replacing existing old fittings with LED well-glass luminaires, MS panelling for switchboards inside godowns, repair of non-functional high mast tower lights and other allied electrical works
2026_FCI_901539_1
EM/04/2025-26
Open Tender
Electrical Works
Works
60 days
FCI FSD RUDRAPUR
As per tender documents
2 documents required · 2 mandatory
₹0
₹50,600
23 Mar 2026
6 Mar 2026
17 Mar 2026
6 Mar 2026
16 Mar 2026
6 Mar 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI- EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | |||||
| 1.1 | 100 watt | - | Each | 2,543 | - |
| 2Supplying, installation, testing & commissioning of following rating LED Well Glass Light with vertical surface mounting pressure die-cast aluminium housing, with rated voltage 240 V, frequency 50 Hz, internal surge protection of 5 kV for driver and external surge protection of 10 KV, THD ≤10%, P.F. ≥ 0.95, IP-66, IK-07/08, CRI ≥ 70 ,with under-voltage and over-voltage protection, and a viewing angle of 120°, having a minimum 50,000 burning hours with CCT 5700 K, with replaceable driver for maintenance. Maximum power consumption should not exceed the specified rating, and the fixture shall be of relevant BIS standards, complete in all respects including external connections with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable and earthing, etc., as required, with a minimum 5-year OEM warranty. System lumen efficacy shall be ≥120 lm/Watt output. LM-79 & LM-80 test reports and all testing required for LED fixtures as per BIS shall be submitted. Shape, size shall be as approved by the Engineer-in-Charge as per requirement. | |||||
| 2.1 | 40 watt | 34 | Each | 3,775 | ₹1,28,350 |
| 2.2 | 70 watt | - | Each | 6,650 | - |
| 3LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | |||||
| 3.1 | 200 watt | 6 | Each | 4,550 | ₹27,300 |
| 4 | Supply , Installation, Testing & Commissioning of loop in loop out box made of PVC sheet 195x 135x90 mm having suitable size 2 nos. terminals and 1 no. SP MCB 5/6A detachable gland plate, interconnection etc are required. | 59 | Each | 1,581 | ₹93,279 |
| 5 | Supply of Control panel Housing comprising of suitable MCB, timer- contractor circuit for automatic ON/Off of lights. | 1 | Each | 29,037 | ₹29,037 |
| 6 | Supplying and fixing of 32 mm dia X 1.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts,bolts and washer, painting the flat iron with primer and finish paint etc. as required. (conforming to IS-1239 part 1 (2004) or equivalent) | 24 | Each | 1,248 | ₹29,952 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.77 MB
BOQ_947605.xls
BOQ • 0.27 MB
mtfrdp1.pdf
Tender Documents • 1.87 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .