Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.0 LAccepted-AOC | L1 | Accepted-AOC Since L1 accepted | |
| 2 | L2₹8.5 L+₹43,450.01 (5.41%)Rejected-AOC | L2 | Rejected-AOC Since L2 rejected |
Tender Value
₹7.0 L
EMD Value
₹17,700
Closing Date
22 Aug 2020, 6:55 pmClosed
Executive Engineer, H E Electrical Division
O/o the Executive Engineer, Harbour Engineering Electrical Division, Kamleswaram. Thiruvananthapuram
Thangassery Fishery Harbour _ Upgradation of lighting at Muthakkara _ Thangassery Auction hall and Yard
2020_HED_376602_1
13/HEED/2020-21/S
Open Tender
Electrical Works
Item Rate
60 days
Thangassery
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,860
online
₹17,700
Yes
23 Nov 2020
13 Aug 2020
26 Aug 2020
13 Aug 2020
22 Aug 2020
13 Aug 2020
Amount
Supply of GEO or equivalent make Street light luminaire, 20W LED, IP66 optical & control gear compartment, die cast aluminium painted housing,anti UV Polycarbonate protector with in built lenses, with easily accessible control gear compartment, suitable for horizontal mounting (Ø32- 42mm), System power (including driver loss) of 20W with luminous efficacy > 105 Lumen/W at Ta 25⁰C. Lifetime residual flux @ Tq 35⁰C @ 50,000 hours = 70%, Ta = 50⁰C, in built surge protection of 4kV (in Differential and Common mode), Power Factor > 0.95, Colour Rendering Index > 70 and Cool white light (5700⁰K).
Supplying IP66, IK 10 rated 100W NW flood light luminaire with body of aluminium extrusion having luminaire efficacy >= 120lumen/watt supplied with IP67 rated best in class LED driver. Preffered make:Keselec-K Flood 100W- NW
Supply of surface mounting corrosion resistant industrial lighting luminare IP65,CCT 6500 K ,>=4000 lumen,CRI > or eq to 80 Phillips WT550 C LED 40S CW PSU S1 PC or equivalent
Supplying IP66, IK 10 rated 200W NW flood light luminaire with body of aluminium extrusion having luminaire efficacy >= 120lumen/watt supplied with IP67 rated best in class LED driver. Preffered make:Keselec-K Flood 200W- NW
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required.
Conveyance, installation, testing and commissioning of departmentally supplied flood light/ area light luminaire with lamp to a height upto 15m from ground level.
Conveyance, installation, testing and commissioning of departmentally supplied flood light/ area light luminaire with lamp to a height upto 8 m from ground level.
Fabricating and supplying special clamping arrangement for fixing an asymmetrical beam Integral LED flood light on wall with clamps each made out of 50 x 6mm MS flat and 8x40mm SS nuts and bolts for one luminaire. The clamps are to be linked with 40x6mm MS flat with suitable holes 8mm ,10mm or 12mm size with suitable size SS Bolt& Nut to fix the luminaire. All the items are to be painted with two coats of epoxy based industrial primer of approved quality and two coats of best quaity epoxy paint of approved colour as per drawing.
Supply, fabrication, conveyance and fixing 40 mm dia C class ISI marked GI pipe bent to shape and fixing the same to wall / parapet using 20x3 mm MS flat clamp s painting with 2 coats of epoxy paint over a coat of epoxy primer, making good the damages, colour washing etc as required (for the installation of outdoor light fittings).
Dismounting the SV lamp flood light and control gear from the tubular post of height upto 15m from ground level without any damage and keep at a place as per the instruction of the depatmental officer at site.
Supply and fixing 2 m long tubular pole made out of 65 mm dia Heavy (Class C) GI pipe with ISI MARK on roof slab by cutting slab near to the column,clamping the pipe to the RCC column using MS clamps made out of 25x5 mm MS flat and anchor bolts, filling the space between slab and pole using PCC 1:11/2:3 (M20) , constructing muffing of size 30 cmx30cmx30cm in M20 mix.The top of the pole must be closed with Table E MS flange and dummy flange,bolted with stainless steel nut and bolts and it must have an inverted Y arrangement using 25mm GI medium pipe 10cm long welded to the pole 10 cm below the top flange to take outgoing wire. The tubular post shall be painted with two coats of epoxy primer and epoxy paint of approved make and colour.
Scaffolding charges for painting tubular post
Wiring for light point/ fan point/ exhaust fan/call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required(Group C)
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required .3 x 2.5 sq. mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.4 X 4.0 sq. mm
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing following size / modules, Plastic boxes alongwith modular base & cover plate for modular switches on surface or in recess etc as required.1 or 2 Module plastic box
Supplying and fixing following size / modules, Plastic boxes alongwith modular base & cover plate for modular switches on surface or in recess etc as required. 3 Module plastic box
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
Supplying and fixing surface/ recess mounting, vertical type, 415 volts,Dust and waterproof ,IP66 Hensel make or equivalent FPVN 0412 opaque door 4 way 4 + 12 VTPN distribution board of poly carbonate inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, with provision for MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB's/ MCCB) as required .
Fixing following ways departmentally supplied surface / recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, IP 43 , IK 09, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, with provision for MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB's/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
Supply, conveyance and fixing 40 A, 25 kA (Ics=100%Icu), 3 pole, MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL & SC conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required
Supplying and fixing 40A, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required .Single pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
Supplying and fixing four pole, 415 volts, 40A isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing 0.3 m , 25 mm X 3 mm copper strip on surface or in recess for connections etc. as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size upto 35 sq. mm (clamped with 1mm thick saddle) on wall surface as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
Supply of 4 core 16 sq mm PVC insulated and PVC sheathed armoured aluminum cable
Supply of 2 core 2.5 sq mm PVC insulated and PVC sheathed armoured copper control cable
Supply of 3 core 2.5 sq mm PVC insulated and PVC sheathed submersible copper cable
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4C X 16 sq. mm (28mm)
Supplying and making end termination nickel plated single compression brass cable gland for 2 core 2.5 sq mm PVC insulated and PVC sheathed armoured copper conductor cable 1.1 KV grade, including providing earth clip and superior quality copper cable socket.
Providing and fixing10 SWG copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
Supply of superior quality copper earth socket for the 3.15mm (10 SWG) earth conductor including crimping etc. as required.
Supply and fixing Cable Junction Boxes IP 65 for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm Cape model Abox i025 or equivalent and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required.
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete.
Painting with 2 Coats of Industrial based Epoxy primer of approved brand and manufacture on steel galvanised iron/steel works (2 Coats)
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge.
Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement).
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Providing and fixing B class G.I. pipes with ISI mark complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. 50 mm dia nominal bore
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
SATHEESH KUMAR S
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .