| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.7 LAccepted-Finance | ₹25.7 L | L1 | Accepted-Finance Being L1 |
| 2 | L2₹32.1 L+₹6.4 L (25.0%)Rejected-Finance | ₹32.1 L+₹6.4 L (25.0%) | L2 | Rejected-Finance Being not L1 |
| 3 | L3₹33.8 L+₹8.1 L (31.6%)Rejected-Finance | ₹33.8 L+₹8.1 L (31.6%) | L3 | Rejected-Finance Being not L1 |
| 4 | L4₹33.9 L+₹8.2 L (31.8%)Rejected-Finance | ₹33.9 L+₹8.2 L (31.8%) | L4 | Rejected-Finance Being not L1 |
| 5 | L5₹34.2 L+₹8.5 L (33.1%)Rejected-Finance DOOR NO 58 1 236 6 FLAT NO A 104 SAMPATH ENCLAVE NAD KOTHA ROAD VISAKHAPATNAM 530009 | VISAKHAPATANAM | ANDHRA PRADESH | 530009 | ₹34.2 L+₹8.5 L (33.1%) | L5 | Rejected-Finance Being not L1 |
Tender Value
₹45.0 L
EMD Value
₹89,960
Closing Date
28 Nov 2024, 6:00 pmClosed
GE (I) DM, Visakhapatnam
GE (I) DM, Visakhapatnam
SERVICING REPAIRS MAINTENANCE AND REPLACEMENT OF UNSERVICEABLE ACB MCCB INDICATOR METERS CABLES EARTHINGS ETC OF LT PANEL BOARDS INSTALLED AT ZONE 3 AND 4 AND ALLIED WORKS AT NAVAL DOCKYARD, VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM
2024_MES_682836_1
8127/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naval Dockyard Visakhapatnam
As per tender documents
8 documents required · 8 mandatory
₹500
GE (I) DM, Visakhapatnam
₹89,960
Yes
30 Jan 2025
7 Nov 2024
30 Nov 2024
7 Nov 2024
28 Nov 2024
21 Nov 2024
Amount
M&L for dismantling and taking out all cable connection from all switchgear and earthing connection of the indoor /outdoor panel board, removing carefully the complete panel board of size not less than 2.5 M x 2 M using sufficient man power /cranes from base of panel and keeping aside, re-construction of damaged panel foundation as per ground requirement in same place or other specified location with brick-work, plaster, foundation bolt, white wash to new plastered surface, reinstallation of complete panel and necessary cable end connection with suitable size of lugs/glands to respective cable/ switchgears, earthing complete. Note- (i) Relaying of cables due to change of foundation of panel and Brick work/plaster work shall be incl in quoted rate by contractor (ii) Required additional length of cables shall be measured and paid separately, (iii) Cable joints if require will be measured and paid separately, (iv) Required aluminium cable lugs /glands, nuts, bolts and washers, foundation bolts, white wash will be inclusive of quoted rate
S & F Hot dip Galvanised wire mesh cable trays 105 x 300mm complete with tray, coupler, cover and cover clip to support clamps, securing properly to support strcture complete including dismantling existing LT cable of off sizes from building wall more than 3 mtr height form FL and relaying the same in proper alignment complete all as specified and directed. Make :- Legrand or equivalent.
Supply, laying in cable tray/wall & connection PVC XLPE insulated, armoured havey duty electric cable with aluminium conductor, 1100 Volts grade cross section area 10 Sqmm 4 core incl dismantling taking down unsv one from wall, cable tray, trench complete all as specified and directed
All as per item No. 3.00 above, but of size 16 sqmm, 4 core
All as per item No. 3.00 above, but of size 25 sqmm, 4 core
All as per item No. 3.00 above, but of size 35 sqmm, 4 core
All as per item No. 3.00 above, but of size 50 sqmm, 3.5 core
All as per item No. 3.00 above, but of size 70 sqmm, 3.5 core
All as per item No. 3.00 above, but of size 120 sqmm, 3.5 core
All as per item No. 3.00 above, but of size 240 sqmm, 3.5 core
S/F of LT heat shrink straight through cable joint suitable for cable size LT 1100 volts grade, 4 core, 6 to 16 sqmm all as specified and directed. Make :- 3M, cat No MHS/Ox1.1KV(HSLA-1/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No. 11.00 above, but for cable sizes 25 sqmm, 35 Sqmm, 50 Sqmm. Make 3M, cat No MHS/Ox1.1KV(HSLA-2/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No- 11 but for cable sizes 70 Sqmm, 95 Sqmm, 120 Sqmm. Make :- 3M, cat No MHS/Ox1.1KV(HSLA-3/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No. 11.00 above, but for cable sizes 150 sqmm & 185 Sqmm. Make :- 3M, cat No MHS/Ox1.1KV(HSLA-5/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No.11.00 above, but for cable sizes 240 Sqmm & 300 sqmm. Make:- 3M, Cat No MHS/Ox1.1KV(HSLA-5/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No.11.00 above, but for cable sizes 400 sqmm. Make :- 3M, Cat No MHS/Ox1.1KV(HSLA-6/4C) or equivelent of Denson/M Seal/MS Seal/RPG
All as per item No.17.00 above, but of size above 1.5m x 1.5m upto 2.0m x 2.0m
All as per item No.17.00 above but of size above 2.0m x 1.5m upto 2.0m x 2.5m
All as per item No.17.00 above, but of size above 2.5m x 2.5m upto 3.5m x 3.5m
All as per item No.17.00 above, but of size above 4.5m x 4.5m upto 5.5m x 5.5m
All as per item No.17.00 above, but of size above 5.5m x 5.5m upto 6.5m x 6.5m
Servicing, repair, maintinance of Air Circuit Breaker 400 Amps to 1600 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit, decarbonize breaker contracts and checking for any defects due to any flush/loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC, replacement of defective parts and re-fixing ACB, cables completes all as specified and directed. Note: (a) required male/female ACB contacts, trip coils, closing coils, electronic protection unit will be measured as supply only. (b) all cleaning agents are included in the quoted rate.
Supply only fixed contract of ACB 630A to 1250A all as specified and directed. Make- Schneider / ABB or as per existing make
Supply only Moving contract of ACB 630A to 1250A all as specified and directed. Make- Schneider / ABB or as per existing make
Supply Only Electronic protection unit of ACB 630A to 1250A all as specified and directed. Make- Schneider / ABB or as per existing make
Supply Only shunt trip coil of ACB 630A to 1250A all as specified and directed. Make- Schneider / ABB or as per existing make
Supply Only closing coil ACB 630A to 1250A all as specified and directed. Make- Schneider / ABB or as per existing make
Supply only LED Pilot lamps red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 230 V AC supply all as specified and directed. Cat Part No:-1SFA619402R5231/32/33 Make:-Siemens/ C&S/ schneider/ ABB/ L&T/ Selzer
Supply only metering current transformer of 1000/5 Amps, Class-1, 15VA, all as specified and directed. Make:-Rishabh, Cat No- TW-06 or equivelent of Kappa/ AE
Supply only metering current transformer of 800/5 Amps, Class-1, 15VA, all as specified and directed. Make:-Rishabh, Cat No- TW-06 or equivelent of Kappa/ AE
Supply only metering current transformer of 600/5 Amps, Class-1, 10VA, all as specified and directed. Make:-Rishabh, Cat No- TW-06 or equivelent of Kappa/ AE
Supply only metering current transformer of 400/5 Amps, Class-1, 12.5VA, all as specified and directed. Make:-Rishabh, Cat No- TW-05 or equivelent of Kappa/ AE
Supply only metering current transformer of 300/5 Amps, Class-1, 5VA, all as specified and directed. Make:-Rishabh, Cat No- TW-05 or equivelent of Kappa/ AE
Supply only MCCB, 4 pole, 400 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with micrologic 2 trip unit all as specified and directed. Make :- Schneider Cat Part No- LV432677 or equivelent of Legrand/ABB/ BCH
Supply only MCCB, 4 pole, 250 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with micrologic 2 trip unit all as speicified and directed. Make :- Schneider cat Part No- LV431780 or equivelent of Legrand/ABB/ BCH
Supply only MCCB, 4 pole, 200 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic release all as specified and directed. Make- Schneider cat Part No- LV431641 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 4 pole, 63 amps to 100 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic release all as specified and directed. Make- Schneider cat Part No- 429642/40 or equivelent of Legrand/ABB
Supply only MCCB, 3 pole, 400 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with micrologic 2 trip uni all as specified and directed. Make- Schneider cat Part No- LV432676 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 3 pole, 250 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV431630 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 3 pole, 200 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV431631 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 3 pole, 160 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV430630 or equivelent of Legrand/ABB
Supply only MCCB, 3 pole, 100A, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV429630/32/35 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 3 pole, 63A , 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV429630/32/35 or equivelent of Legrand/ABB/BCH
Supply only MCCB, 3 pole, 32 A , 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with thermal magnetic trip unit all as specified and directed. Make- Schneider cat Part No- LV429630/32/35 or equivelent of Legrand/ABB/BCH
Supply and fix copper bus bar off sizes inside busbar chamber with all required nuts-bolts-washers and taking out old unserviceable bus bar all as specified and directed.
M&L for painting of outer surface of complete LT Panel board of size upto 1.5M x 1.5M comprising ACBs/MCCBs/SDFs, busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel spray painting after preparation of surface, providing protection cover to all metering equipment, switchgears, cleaning of all non-metalic surface after completion of painting with paint remover all as specified and directed.
All as per item No.49.00 above, but of size above 1.5m x 1.5m upto 2.0m x 2.0m
All as per item No.49.00 above, but of size above 1.5m x 1.5m upto 2.5m x 2.5m
All as per item No.49.00 above but of size above 2.5m x 2.5m upto 3.5m x 3.5m
All as per item No.49.00 above, but of size above 4.5m x 4.5m upto 5.5m x 5.5m
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe/duct or fixed to poles or any other indicated situation for loop earthling etc. as required of size 25x4mm galvanised iron strip including taking down unserviceable one all as specified and directed.
M & L for earthing complete with steel earth plate eletrode 60cmx60cmx6mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plat not less than 1.5 mtr below ground level connected to GI earth strip 32x6 mm by means of bolts. nuts,check nuts and washers etc including protection pipe 40mm dia up to 7.5m length, provision the earth lead to earth connection in ther main distribution box with lugs and GI nuts, bolts, earthing shall be done all as per shown electrical plate No 3 of SSR part 1 Including neccessary excavation in soft disintergrated rock and provision of 15mm dia pipe with funnel, PCC earth chamber of 100mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing in presence of Engr-in-Charge.
Dismantling of UNSV enclosure box of any size with switchgear, cables and S & F Electro galvanized steel sheet (corrision resistant) enclosure box having minimum thickness 1.0mm , IP 55, IK 08 with multiple knockout and suitable for installation of 4P MCCBs upto rating 200 A mounting on angle iron frame and two legs suitable size of angle iron , properly grouted on floor/wall with anchor fastener including refixing of cables using proper lugs/ glands complete all as specified. (Note: Rate for fixing of MCCBs are incl of contractor quoted rates. MCCB of suitble size will be measured and paid seperately as supply only) Make- L&T / Legrand/ Schenider or equivalent make.
S & F aluminium perforated sheet silver in colour having round holes (Anti corrosive) having thickness not less than 2mm cut to shape incl bending, moulding as per site reqirement, duly fixed with screws/ locking arrangments for securing of cable on wall/ column/beam more than 3 Mtr height from floor level including refixing of existing loose of LT cable of any size with proper saddles/clamps where reqd complete all as specified and as directed.
M&L for taking up MS duct cover from cable duct of depth upto 1.5 m and width not exceeding 1.0m in various shop floors/substations, keeping a side for reuse, taking out all cables from the cable duct, removing unused/dead cables from the trench, cleaning of trench by taking out all silt/debries and deposit to nearest garbage bins and relaying of all serviceable cables all as specified and directed.
Dismantling structural steel work of any description complete all as specified and directed.
S&F for rolled mild steel plain or chequered plates confirming to Fe-290, Gde E-165 welded, riveted, bolted attached to supporting structure of capstan, duct covers, valve pit access platform and working in a confined area including making good the disturbed portion of concrete surfaces with 1: 1 1/2 :3 type A0 using 12.5 mm stone aggregate complete all as specified by Engr-in- Charge.
S&F structural steel framed work such as angle, channel, I beams etc cut to shape, including bending and welding angles as necessary confirming to Fe-290, Gde E-165 as in supporting structure of duct covers, platforms (0 to -3m level) and capstan, ladders framed balusters, walk ways, railing, nosing angle and similar works, including making good the disturbed portion of concrete surfaces with 1: 1 1/2 :3 type A0 using 12.5 mm stone aggregate and all as directed complete all as specified and directed.
M & L for preparation of new steel surface of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of zinc chrome primer complete all as specified and as directed.
M & L for preparation of old steel surface of any description over 10 cm width or girth and applying one coat of synthetic enamel paint complete all as specified and as directed.
M/s.Raghava Enterprises (BID ID -3176115)
GVR ENGINEERING WORKS (BID ID -3174164)
R AND A ASSOCIATES ENGINEERS CONTRACTORS (BID ID -3176372)
M/S EVEREST INFRA (BID ID -3175689)
aswitha engineering works (BID ID -3176260)
EMKAY ENGINEERING CONSTRUCTIONS (BID ID -3175872)
ANAND ENTERPRISES AND ENGINEERS (BID ID -3176344)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .