Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.5 LAccepted-AOC | L1 | Accepted-AOC 1st Lowest | |
| 2 | L2₹26.9 L+₹4.6 L (20.5%)Rejected-Finance 7 32 1 PRASANTHI NAGAR GOPALAPATNAM VISAKHAPATNAM 530 027 | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | L2 | Rejected-Finance Not Lowest | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in requisite category |
Tender Value
₹33 L
EMD Value
₹66,000
Closing Date
13 Sept 2022, 6:00 pmClosed
Garrison Engineer P Navy Kalinga Visakhapatnam
Garrison Engineer P Navy Kalinga Military Engineer Services INS Kalinga PO Visakhapatnam 531 163
REPAIR/ MAINTENANCE OF FIRE ALARM SYSTEM MAIN PANEL ALONG WITH ITS ALLIED ACCESSORIES AND CAPACITOR BANK AT INS KALINGA, NAD BHEEMUNIPATNAM AND INS KARNA UNDER GE(P) NAVY KALINGA
2022_MES_545670_1
GE (P)/N/K/8941 OF 2022-23
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer P Navy Kalinga Visakhapatnam
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
Garrison Engineer P Navy Kalinga Visakhapatnam
₹66,000
Yes
21 Oct 2022
16 Aug 2022
15 Sept 2022
16 Aug 2022
13 Sept 2022
30 Aug 2022
Amount
M&L for fixing , testing & commissioning digital Power factor meter with accuracy class 1 suitable for LT 415V panel flush pattern square type & wiring including disconnecting and taking down the unserviceable meters complete all as specified and directed.
Supply & fixing in repair for APFC , calibrating, testing & commissioning of Microprocessor based Automatic Power Factor Controller of any size with Aux supply 100-440V AC 50 HZ, CT input range 1Amps/5Amps , Voltage input range 100-600 V 50 Hz , Minimum 8 Analogue outputs, with following Salient Features 1. 3 CT Input for Current & Voltage Measurement 2. Provision for Dual PF Settings for Mains & DG Application 3. Manual & Automatic Operation 4. Accuracy of +0.8% for Reactive Power, + 0.5% for Current 6 or 12 steps to operate Capacitor Circuits. 6. 2 & 4 Quadrant Operation for Sites with/without Solar Plants 7. Option of LIFO, FIFO & Intelligent Control Mode to choose the best combination of capacitor bank for compensation with minimum switching to achieve the desired power factor 8. Power Quality Information such as Total & Individual I-THD & V-THD up to 31st Order 9. Current & Voltage Angles displayed for ease of troubleshooting 10. PF Display – 3 Steps after Decimal 11. Capacitor Health Check Monitoring 12. Record of Capacitor Step Switching for scheduling of maintenance of your panel 13. Ambient Temperature Monitoring 14. Time stamping of latest 32 Alarms Controller will be with LCD display Make :- L&T etaSMART or equivalent as approved by GE
Supply & fixing in repair of power factor correction (PFC) capacitors of rating 10 KVAR 440V 50Hz , 3-phase capacitor of any type (cylindrical/ rectangular) designed for high-voltage on-load tap-changer (OLTC) applications with Low energy consumption, Capable of withstanding high inrush current, Dry-type, free from oil leakage, Explosion proof feature ,Compact size and light weight.
Supply & fixing in repair of power factor correction (PFC) capacitors of rating 12.5 KVAR 440V 50Hz , 3-phase capacitor of any type (cylindrical/rectangular) designed for high-voltage on-load tap-changer (OLTC) applications with Low energy consumption, Capable of withstanding high inrush current, Dry-type, free from oil leakage, Explosion proof feature ,Compact size and light weight.
Supply & fixing in repair of power factor correction (PFC) capacitors of rating 25 KVAR 440V 50Hz , 3-phase capacitor of any type (cylindrical/rectangular) designed for high-voltage on-load tap-changer (OLTC) applications with Low energy consumption, Capable of withstanding high inrush current, Dry-type, free from oil leakage, Explosion proof feature ,Compact size and light weight.
Supply & fixing in repair of power factor correction (PFC) capacitors of rating 50 KVAR 440V 50Hz , 3-phase capacitor of any type (cylindrical/rectangular) designed for high-voltage on-load tap-changer (OLTC) applications with Low energy consumption, Capable of withstanding high inrush current, Dry-type, free from oil leakage, Explosion proof feature ,Compact size and light weight.
S&F in repair of Control Wiring up to Capacitor bank from outgoing terminals with 1 Core , 2.5 Sq mm copper cable with proper ferules & appropriate Lugs.
S&F in repair of Control Wiring up to Capacitor bank from outgoing terminals with 1 Core , 6 Sq mm copper cable with proper ferules & appropriate Lugs.
S&F in repair of Control Wiring up to Capacitor bank from outgoing terminals with 1 Core , 16 Sq mm copper cable with proper ferules & appropriate Lugs.
S&F in repair of Control Wiring up to Capacitor bank from outgoing terminals with 1 Core , 25 Sq mm copper cable with proper ferules & appropriate Lugs.
S&F in repair of Control Wiring up to Capacitor bank from outgoing terminals with 1 Core , 35 Sq mm copper cable with proper ferules & appropriate Lugs.
Supply and replace Copper lugs suitable for 2.5 Sqmm including nuts, bolts and washers complete all as specified and as directed.
Supply and replace Copper lugs suitable for 6 Sqmm including nuts, bolts and washers complete all as specified and as directed.
Supply and replace Copper lugs suitable for 16 Sqmm including nuts, bolts and washers complete all as specified and as directed.
Supply and replace Copper lugs suitable for 25 Sqmm including nuts, bolts and washers complete all as specified and as directed.
Supply and replace Copper lugs suitable for 35 Sqmm including nuts, bolts and washers complete all as specified and as directed.
Supply and fixing in repair of 3 Pole Power contactor 25A TP 1NO+1NC 220 V AC with Add-on blocks, Conforms to IS/IEC 60947-4-1 & IEC 60947-4-1.
Supply and fixing in repair of 3 Pole Power contactor 50A TP 1NO+1NC 220 V AC with Add-on blocks, Conforms to IS/IEC 60947-4-1 & IEC 60947-4-1
Supply and fixing in repair of 3 Pole Power contactor 110A TP 1NO+1NC 220 V AC with Add-on blocks, Conforms to IS/IEC 60947-4-1 & IEC 60947-4-1
Supply and fixing in repair indication lamp, 230 volts AC, LED type colour of Red, Yellow, Blue, Green, White, Amber complete all as directed.
Supply, fixing, testing and commissioning of CT with primary Current 30A - 120A or as per existing panel ratings, class of accuracy class 1 upto 5 VA, including disconnecting old unserviceable meter, removed from bus bar, fixing new CT to bus bar with suitable clearance, secondary wiring with FRLS insulated copper conductor and lugs with suitable size complete all as directed.
Supply and replace MCCB 3 pole, 415 V, adjustable type 400 Amps with TMD breaking capacity 36 KA including necessary modification in the panel complete all as specified and as directed.
Supply and replace MCCB 3 pole, 415 V, adjustable type 125 Amps with TMD breaking capacity 36 KA including necessary modification in the panel complete all as specified and as directed.
Supply and replace MCCB 3 pole, 415 V, adjustable type 63 Amps with TMD breaking capacity 36 KA including necessary modification in the panel complete all as specified and as directed.
Supply and replace MCCB 3 pole, 415 V, adjustable type 25 Amps with TMD breaking capacity 36 KA including necessary modification in the panel complete all as specified and as directed.
S & F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size all as directed
Decarburizing/ cleaning complete LT 415 Volts 3 phase panel/ bus bar chamber with electrical connections, complete bus bar from the bus bar chamber, cleaning with CTC and ensure proper decarburizing, refixing the same after applying Becktol Red solution to the bus bar insulator & checking all the connections, tightening the nuts, bolts & thimbles of in-coming/out-going system complete including replacement of defective rusted bolts & nuts all as specified and directed.
M&L for taking out the loose or separated Door / canopy / front & back sheet covers from existing LT panel and refixing the same after welding, provn of nut bolts / hinges if required as per site, proper locking arrangement and fixing of proper earth connection etc complete all as specified and directed.
M&L for preparation of external surfaces of LT panels indoor/outdoor type for painting by scraping down old dusted paint by steel brush brooming rubbing and cleaning applying two coats of synthetic enamel paint as approved and marking feeders by Engineer-in-Charge.
M&L for 2mm thick fibre reinforced plastic coating with epoxy paint coat of approved color on the surface of panel board, RMUs after cleaning the surfaces thoroughly complete all as directed & specified.
Supply and fixing in repair of micro processed based master control board with suitable for analogue addressable fire alarm control panel with standards NFPA 72 UL 864 listed, which can accommodate 4 loop cards class A or B , each loop card can operate upto 200 detectors with loop resistance 40 ohms and loop current of 300 mA Board should consists of a) RS 485 communication port and USB 2.0 port b) 3 x programmable relay c) Power Limited Conventional Zone Circuit Class B Style C input d) 24V DC output e) 24v NAC 1 & 2 Outputs f) 4 x loop card terminals g) Display output pin with h) Power supply input 12 pin on board female connector
Supply and fixing in repair of Display unit with 40 x 4 character LCD and touch keypad suitable for analogue addressable fire alarm control panel with control and indications a) Common indicators b) Zone Group indications c) Alphanumeric key pad d) Control keys e) Piezo buzzer f) 40 x 4 character LCD display g) Input pin
Supply and fixing in repair of Power supply unit for addressable fire alarm control panel with battery charging unit with 12 pin output (multiple voltage outputs, grounds etc) primary source 120/220 AC power supply and secondary source 24 V DC (battery source) all as specified and directed by Engr-in-charge.
Supply and fixing in repair of micro processed based master control board with suitable for 4 zone conventional fire alarm control panel with standards NFPA 72 UL listed loop card can operate upto 30 detectors per zone, Board should consists of a) RS 485 communication port and USB 2.0 port b) 4 zone input ports c) Power Limited Conventional Zone Circuit Class B Style C input d) 24V DC output e) 24v NAC 1 & 2 Outputs f) Fire relay NO NC C supervisory ports g) Fault relay h) Piezo buzzer i) Display output 24 pin j) Power supply input 2 pin on board female connector
Supply and fixing in repair of Display unit with 16 x 2 character LCD and touch keypad suitable for 4 zone conventional fire alarm control panel with control and indications:- a) Common indicators b) Zone Group indications c) key pad d) Control keys e) Piezo buzzer f) 16 x 2 character LCD display g) Input pin
Supply and fixing in repair of Power supply unit for 4 zone conventional fire alarm control panel with battery charging unit with 2 pin 24 v DC output (multiple voltage outputs, grounds etc) primary source 120/220 AC power supply and secondary source 24 V DC ( battery source)
Supply and fixing in repair of micro processed based master control board with suitable for 8 zone conventional fire alarm control panel with standards NFPA 72 UL listed loop card can operate upto 30 detectors per zone, Board should consists of a) RS 485 communication port and USB 2.0 port b) 8 zone input ports c) Power Limited Conventional Zone Circuit Class B Style C input d) 24V DC output e) 24v NAC 1 & 2 Outputs f) Fire relay NO NC C supervisory ports g) Fault relay h) Piezo buzzer i) Display output 24 pin j) Power supply input 2 pin on board female connector
Supply and fixing in repair of Display unit with 16 x 2 character LCD and touch keypad suitable for 8 zone conventional fire alarm control panel with control and indications a) Common indicators b) Zone Group indications c) key pad d) Control keys e) Piezo buzzer f) 16 x 2 character LCD display g) Input pin
Supply and fixing in repair of Power supply unit for 8 zone conventional fire alarm control panel with battery charging unit with 2 pin 24 v DC output (multiple voltage outputs, grounds etc) primary source 120/220 AC power supply and secondary source 24 V DC (battery source) all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of UL Listed Analogue addressable smoke cum heat multi detector with 8 digit dip switches address settings, Dual LED indication for 360 degree visibility, shall be polarity insensitive, Insect filter chamber, advanced detection and communication protocol. Operation voltage : 17-28V DC all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of UL Listed Conventional smoke cum heat multi detector with, Dual LED indication for 360 degree visibility, shall be polarity insensitive, Insect filter chamber, easy to install, advanced detection and communication protocol. Operation voltage : 9-33V DC all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of Manual Pull Station is made up of a high quality PVC housing with breakable glass and resettable switch inbuilt operating with 24 V DC power supply and 30 mA operating current suitable for and conventional fire alarm control panel all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of addressable Manual Pull Station is made up of a high quality PVC housing with breakable glass inbuilt 8 way dip switch for addressing and resettable switch inbuilt operating with 24 V DC power supply and 30 mA operating current suitable for addressable fire alarm control panel all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of Sounder / Horn cum strobe are with both audio and visual indication in case of fire and emergency. The horns. Horn output dB level between 80 to 100 db in a meter distance complies NFPA 72 standards with operating voltage 18 to 30V ( 24 v nominal DC) with current less than 100mA built with FR ABS plastic IP 40 Rated all as specified and directed by Engr-in-charge.
Supply, fixing and replacement of 2 x 12 volt 7ah lead acid batteries for secondary power supply backup for fire alarm control panel all as specified and directed by Engr-in-charge.
Supply, laying, testing, saddling and glanding termination of 2 core , 2.50 sqmm twisted pair armoured cable copper conductor, including removing unserviceable old cable complete all as specified and as directed for external usage all as specified and directed by Engr-in-charge.
Supply, laying and testing FRLS flexible copper cable 1100 Volts grade of size 2 core, 1.50 sq mm complete all as specified for internal usage
Supply and fixing of Water proof enclosure accommodating fire alarm control panel with suitable cut-outs , glands , waterproof rubber packing throughout the door and glass provision with proper locking system made out of 16 gauge Mild steel sheet powder coated and provision for panel number marking and glass for complete visibility of panel indications all as specified and directed by Engr-in-charge. Make- Hensel / C&S/ Sintex/ Hager/ L&T or equivalent as approved by GE
M&L for replacement of analogue addressable control module to control 24v operational devices all as specified and directed by Engr-in-charge.
Supply, fix in repair AC Single phase surge protectors for panels to control over power fluctuations and lightning all as specified and directed by Engr-in-charge. Make- Havells/ ABB/ L&T/ Schneider or equivalent as approved by GE
MVV Prasad
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .