| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-Finance | L1 | Accepted-Finance Ist Lowest | |
| 2 | L2₹7.1 L+₹24,700 (3.60%)Accepted-Finance | L2 | Accepted-Finance 2nd Lowest | |
| 3 | L3₹7.1 L+₹28,230 (4.12%)Accepted-Finance | L3 | Accepted-Finance 3rd Lowest |
Tender Value
₹7.2 L
EMD Value
₹7,500
Closing Date
8 Jun 2020, 4:00 pmClosed
SE ETC I Lucknow
Pareshan Bhawan, Vibhuti Khand, Lucknow
Supply and fixing of main and sub AC Distribution boards and laying of power cables for up gradation of AC Distribution System at 220 KV Substation Chinhat under ETD II Lucknow
2020_UPTCL_461115_1
E-TENDER 02/2020-21
Open Tender
Electrical Works
Piece-work
30 days
Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
A/c No 2408002190005438, IFS PUNB0691100, PNB, Lko
₹7,500
28 Sept 2020
21 Apr 2020
9 Jun 2020
21 Apr 2020
8 Jun 2020
21 Apr 2020
Amount
Following Works are to be carried out at 220 K.V. Sub Station Chinhat as per direction of S.D.O. / J.E. (M) concerned & Technical Specifications, with all cost of men, materials, misc. consumables and T&P etc. required for proper completion of the work :
1) Supply & Fixing the new Main line Distribution based cubical with canopy for outdoor installation with rating of 415 V, 400 Amp, 3 Phase and neutral size 1550X750X600 mm with Ms Sheet thickness 14 SWG duly powder good quality. The respectacles shall be double door (1 No. Front door and 1 no. inside door for operating the MCCB without opening the door) and single door on opposite side of respectacles. Respectacles shall be provided incorporating 4 No. Aluminum insulated bus bar of size 30X10 sq.mm,Ammeter, Voltmeter and Phase Indication and Incoming & Outgoing MCCBs of Schneider/L&T/Indoasian or Equivalent Make as per details given below for 220 KV , 132 KV , 33 KV switch yard each with the Provision of incoming connection with main bus bar with AI insulated strip of 25X10 mm and provision of AI insulated bus bar with of size 25X10 mm on outgoing side for connecting the suitable size of cable for MCCB, Power receptacles shall be weather,dust and vermin proof with proper locking arrangement with stand and phase indicator:
(i) For 220 KV Yard consisting of :
Incoming: 01 No. TPN MCCB of Rating 250A.
Outgoing: 01 No. TPN MCCB of Rating 180A, (For Centrifusing Machine)03 No. TPN MCCB of Rating 100A.
(ii) For 132 KV Yard consisting of :
Incoming: 01 No. TPN MCCB of Rating 160A.
Outgoing: 04 No. TPN MCCB of Rating 63A.
(iii) For 33 KV Yard consisting of :
Incoming: 01 No. TPN MCCB of Rating 250A.
Outgoing: 01 No. TPN MCCB of Rating 180A,(For Centrifusing Machine) 03 No. TPN MCCB of Rating 63A.
2) Supply & Fixing the new Sub Distribution Board with canopy for outdoor installation with rating of 415 V, 100 Amp, 3 Phase and neutral size 800X6500X500 mm with Ms Sheet thickness 14 SWG duly powder good quality. The respectacles shall be double door ( 1 No. Front door and 1 no. inside door for operating the MCCB without opening the door) and single door on opposite side of respectacles. Respectacles shall be provided incorrating 4 No. Aluminum insulated bus bar of size 30X10 sq.mm,Ammeter, Voltmeter and Phase Indication and Incoming & Outgoing MCCBs of Schneider/L&T/Indoasian or Equivalent Make as per details given below for 220 KV , 132 KV , 33 KV switch yard each with the Provision of incoming connection with main bus bar with AI insulated strip of 25X10 mm and provision of AI insulated bus bar with of size 25X10 mm on outgoing side for connecting the suitable size of cable for MCCB, Power receptacles shall be weather,dust and vermin proof with proper locking arrangement with stand and phase indicator:
(A) 02 No. for 220 KV, 132 KV & 33 KV Yard each consisting of :
(i) Incoming: 01 No. TPN MCCB of Rating (63-100A.)
Outgoing: 09 No. TPN MCB of Rating 16-32 A for 220 KV Yard, 11 Nos. TPN MCB of rating 16-32 A. for 132 KV Yard, 21 no. DP MCB of rating 16-32 A. for 33 KV yard.
3) Safe Loading of approx. 250 Meter 3.5C x 50 / 95 Sq. mm Aluminium Power Cable from 132 K.V. Sub Station Awas Vikas / Sahara City Homes (approx. distance 25 Km) to 220 K.V. Sub Station Chinhat including Shifting from storage place, unwinding from Cable Drum, Packing & its Safe Carriage on suitable Vehicle and Unloading & Placing at designated place.
4) Laying of 3.5 X 50/95 sq.mm LT power cable 50 cms below the ground level after excavation and to put the first class bricks and river sand along the side of cable and back filling. The work includes both side termination of cable with crimping of lugs. All labour material T&P etc. required for proper completion of work.(The Power cable shall be provided by the department free of cost).
M/S KALYANI ASSOCIATES
M/S JAI SHREE ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .