| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹34.2 LAdmitted-Finance UDAYPUR P O KAMAJORA DIST UTTAR DINAJPUR PIN 733130 | RAIGANJ | UTTAR DINAJPUR | WEST BENGAL | 733130 | +6.88% | ₹34.2 L | L1 | Admitted-Finance |
| 2 | L2₹34.9 LAdmitted-Finance LABPUR COLLEGE PARA LABPUR WEST BENGAL INDIA 731303 | LABPUR | BIRBHUM | WEST BENGAL | 731303 | +9.00% | ₹34.9 L | L2 | Admitted-Finance |
| 3 | L3₹35.2 LAdmitted-Finance | +9.86% | ₹35.2 L | L3 | Admitted-Finance |
| 4 | Rejected-Technical 1ST FLOOR OPP GURUDWARA GURUDWARA ROAD BENACHITY DURGAPUR 713213 | DURGAPUR | PASCHIM BARDHAMAN | WEST BENGAL | 713213 | - | - | - | Rejected-Technical Technically Rejected. |
| 5 | Rejected-Technical DARJEE PARA P O KRISHNAGAR DIST NADIA PIN 741101 | KRISHNAGAR | NADIA | WEST BENGAL | 741101 | - | - | - | Rejected-Technical Technically Rejected. |
Tender Value
₹32.0 L
EMD Value
₹64,053
Closing Date
24 Feb 2026, 5:00 pmClosed
S.E. AND R.M., DAKSHIN DINAJPUR REGIONAL OFFICE.
Office, of the Regional Manager, Dakshin Dinajpur, W.B.S.E.D.C.L., Regional Campus, Balurghat, W.B.S.E.D.C.L., P.O. - Beltala Park, P.S. - Balurghat, Besides S.P. Residence Campus, Balurghat, Dakshin Dinajpur - 733103.
Construction, of a (new) Temporary Sub-Station, along-with the (1X6.3) M.V.A. P.T.R., and the (other) allied Work(s), at the Mouza - Gandharbapur, in the Banshihari Block, under the Buniadpur (D) Division, in the District, of the Dakshin Dinajpur.
2026_WBSED_1002982_1
DDRO/E-TENDER/E/ 2025-26/15, Dated - 10.02.2026.
Open Tender
CIVIL AND ELECTRICAL WORKS
120 days
Gandharbapur, Banshihari, Dist. - DakshinDinajpur.
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹64,053
Balurghat, Dist. - Dakshin Dinajpur.
11 Mar 2026
11 Feb 2026
27 Feb 2026
11 Feb 2026
24 Feb 2026
11 Feb 2026
17 Feb 2026
A. Civil Work(s).
Surface Dressing of the ground in any kind of soil including removing vegetation inequalities not exceeding 15 cm depth and disposal of the rubbish within a lead upto 75 m as directed.
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches. leveling, dressing and ramming the bottom. bailing out water as required complete. Depth of excavation not exceeding 1,500 mm..
Filling in foundation or plinth by silver sand in layers not exceeding 150 mm. as directed and consolidating same by thorough saturation with water ramming complete, including the cost of supply of sand. (Payment to be made on measurement of finished quantity).
Earth work in filling in compound, tank, low land, ditches etc. with good earth, in layers not exceeding 150 mm. including breaking clods and consolidating the same by ramming and dressing complete. (Payment will be made on profile measurement before and after the work) With carried earth arranged by the contractor within a radius exceeding 3 km. but not exceeding 5 km. including the cost of carried earth.
Earth work filling in land (Area- 300 sq Mtr. and depth of filling 2 Mtr.) with low resistivity of soil 30 Ohm-Mtr. @ Rs 512.63 per CuM as per PWD schedule rate for Building works effected from 01.11.2017.
Earth work in filling in foundation trenches or plinth with good earth, in layers not exceeding 150 mm. including watering and ramming etc. layer by layer complete. (Payment to be made on the basis of measurment of finished quantity of work). With earth obtained from excavation of foundation.
Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand.
(I) Cement concrete with graded stone ballast (40 mm size excluding shuttering) (B) With N.B. Variety stone metal. (a) 1:3:6 proportion In ground floor.
Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm.nominalsize) excluding shuttering and reinforcement, if any, in ground floor as per relevant IS codes. River Bazree.
Ordinary Cement concrete (mix 1:1.5:3) with graded stone chips (ii ) River Bazree in g.f..
Brick work with 1st class bricks in cement mortar(1:6) In foundation and plinth.
Brick work with 1st class bricks in cement mortar(1:6) In superstructure, ground floor.
125 mm thick brick work with 1st class bricks in cement mortar (1:4) a) in ground floor.
25 mm to 30 mm shuttering without staging in foundation.
25 mm to 30 mm thick wooden shuttering as per decision & direction of Engineer-In-Charge.
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars stirrups, binders etc. including supply of rods, initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every inter- section, complete as per drawing and direction. For works in foundation, basement and upto roof of ground floor/upto 4m. Tor Steel/Mild Steel. OTHER MANUFACTURERS NOT SPECIFIED.
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (ground floor). (Excluding cost of chipping over concrete surface). With 1:4 cement mortar 10 mm thick plaster a)In Ground floor.
Plaster ( to wall, floor, ceiling etc ) with sand and cement morter 20 mm thick plaster. with (6: 1) cement mortar.
Neat cement punning about 1.5 mm. thick in wall, dado, window, sills, floor, drain etc. Note: cement 0.152 cum. Per 100 sqm..
Applying Interior grade Acrylic Primer of approved quality and brand non plastered or cencrete surface old or new surface to receive Distemper/ Acrylic emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer's specification and as per direction of the EIC. (In Ground Floor) (a) One Coat i) Water based interior grade Acrylic Primer.
Applying Acrylic Emulsion Paint of approved make and brand on walls and ceiling including sand papering in intermediate coats including putty (Two coats) i) Standard Quality.
Applying Exterior grade Acrylic Primer of approved quality and brand on plastered or concretesurface old or new surface to receive decorative textured (mat finish) or smooth finish acrylic exterior Immersion paint including scrapping and preparing the surface thoroughly, complete as per manufacturer's specification and as per direction of E.I.C In ground floor. One coat on new surface.
Protective and decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer's specification and as per direction of EIC to be applied over acrylic primer as required.The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer. Normal Acrylic Emulsion In ground floor.
Priming one coat on steel or other metal surface with synthetic enamel/oil bound primer of approved quality including smoothening surface by sand papering etc..
(b) On steel or other metal surface With other than hi-gloss of approved quality Two coats (with any shade except white).
Openable steel windows as per IS sizes with side hung shutters and horizotal glazing bars. [The extra rate admissible for the openable portion only].
Supplying, fitting and fixing two point nose steel handle.
steel peg stay 300 mm long including fitting and fixing.
M.S. integrated grill as per approved design integrated with steel window or ventilator, joints continuously welded with M.S. flats and bars.
M.S. structural works in columns, beams etc. with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-in- charge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1956 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 1957, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental chages such as electricity charges, labour insurance charges etc. For structural members of specified sections weighing less than 22.5 Kg./m..
M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor. (i) Grill weighing above 16 Kg./sq.mtr and above (a) In ground floor.
Galvanised corrugated iron sheet work (excluding the supporting frame work) fitted and fixed with 10 mm. dia J or L hook-bolts, limpet and bitumen washers and putty complete with 150 mm. end lap and one corrugation minimum side lap In Roof:- With 0.80 mm thick sheet.
Galvanised iron sheet ridging fitted with necessary bolts, screws, washers etc complete.(225mm end lapping) 300 mm lapping each waY With 0.80 mm sheet.
Fixing post of iron or precast concrete by digging hole in the ground (in all sorts of soil) and embedding the same by packing the hole with cement concrete (1:3:6) (with jhama khoa. For Purulia, Bankura and Darjeeling Hill by Pakur Variety, Local Black Hard Stone & Bazree respectively) and finishing the top surface to regular shape (as directed) with 15 cm cement plaster (1:6) complete, including the cost of concrete, plaster etc.but excluding the cost of the post : (ii) Average dia. of the hole 300 mm. to 400 mm (a) Depth 450 mm. to 500 mm. (Cement- 14..35 Kg/No.).
Double kontted wove wire 2.1 m height (17 bars) vertical 300 mm apart horizontal spacing starting from 88 mm ending 200 mm top and bottom wire 10g and all other intermediate and upright wire 9g with finished border 2 ply twisted fencing complete including tightening and fixing the same to posts with staples at every bar including cost of cutting and of lapping joints in net as necessary including cost of staples and wove wire.
Supplying at site or stackyard or as directed PCC (1 : 2 :4) Fencing Post 215 cm 150 mm X 150 mm section at bottom, 100 mm X 100 mm section at top with T-Base 300 mm X 150 mm X 100 mm, having 4 nos 6 mm dia vertical M.S. reinforcement and 6 mm dia binders @ 200 mm centres, finished smooth etc., complete.
Digging earth in any soil including mixed soil but excluding moorum, laterite sand stone or any other hard stone including spreading or stacking the spoils within a lead of 75 metres as directed bailing out water upto 1 metre depth, shoring etc., when and if required and back filling with fine sand (including cost of sand) on completion of steining works. A) R.C.C. Ring Well i) 1.2 metre diameter of digging for 0.9 metre internal diameter of well ring. a) Upto 3 metre below G.L..
R.C.C. well ring made with cement concrete 1:1.5:3 with stone chips and 0.80% reinforcement (including the cost of shuttering and reinforcement) cast at site fitted and fixed in position after proper curing true to plumb in the well including jointing with cement mortar 1:2 complete as per direction. a) 65 mm thick and 0.9 metre internal dia. cement for joint filling-4 kg/meter.
Supplying, fitting & fixing UPVC pipes A- Type and fittings conforming to IS:13592-1992 with all necessary clamps nails, including making holes in walls, floor etc. cutting trenches in any soil through masonry concrete structures etc if necessary and mending good damages including joining with jointing materails (Spun Yarn, Valamoid/Bitumen/M-Seal etc) complete. (A) UPVC Pipes: (i) 110 mm. Dia..
Supplying, fitting and fixing PVC pipes for underground work of approved make of Schedule 80 (medium duty) conforming to ASTMD - 1785 and threaded to match with GI Pipes as per IS : 1239 (Part - I). with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbo, nipple, longscrew, reducing socket, reducing tee, short piece etc. fitted including cost of all materials ,jointing materials, cutting pipes, making threads ,cutting trenches upto 1.5 metre below surface in all sorts of soil and refilling the same as directed complete in all respect. (Payment will be made on the centre line measurement of the total pipe line including all specials No separate payment will be made for accessories, specials.) (i) 40 mm..
Labour for boring tube well of required dia. by water jet system through any type of soil strata including hire and labour charges for boring pipes, scaffolding, tools and plants as necessary and taking out them and lowering pipes, strainers, blind pipe etc. and fitting and fixing the same complete including bucket washing and other incidental works in the connection. The tube well should have a minimum 50 mm gap in between the outside of the tubewell pipe and the bore. (a) For depth upto 150 metre. (i) 50 mm dia. boring etc..
Supplying PVC strainer of approved make with adapter conforming to I.S.12818 specifications. (i) 40 mm dia..
Supplying, fitting and fixing popular Maya pump no-6 or similar. (i) For 40 mm dia. tube well.
Supplying, fitting & fixing approved patent vent cowl I.C.I. conforming to I.S.S and painting two coats to the exposed surface with approved paint complete. (i) 100 mm dia..
Supplying, fitting and fixing E.W.C. in white glazed vitreous chinaware of approved make complete in position with necessary bolts, nuts etc. (a) With 'P' trap (CERA/HINDWARE make).
Constructing Inspection pit of inside measurement 600mm X 600mm X upto 600mm (depth) with 250 mm thick 1st. class brick work in cement mortar (1:4) on all sides, bottom of the pit consisting of 100 mm thick cement concrete (1:3:6) with stone chips over a layer of jhama brick flat soling, 15 mm thick (1:4) cement plaster to inside walls and out-side walls upto G.L. and 20 mm.thick (1:4) plaster to bottom of the pit, providing necessary invert with cement concrete (1:3:6) with stone chips as per direction, neat cement finishing to entire internal surfaces, top of the pit covered with 100 mm thick R.C.C. slab (1:1.5:3) with stone chips and necessary reinforcements upto 1% and shuttering including 6 mm thick cement plaster (1:4) in all external surfaces of the slab and one 560 mm dia. R.C.C. manhole cover of approved make supplied, fitted and fixed in the slab with necessary fittings, necessary earthwork in excavation in all sorts of soil, filling sides of the pit with earth and removing spoils after work complete in all respect with all costs of labour and materials. (i) With Pakur Variety (SAIL/TATA/RINL).
Any other item not covered in this schedule wiil be applicable as per PWD Schedule of rate w.e.f 01.11.2017 , all Addenda & Corrigenda of SOR, upto 01.11.2019.
B. Electrical Work(s).
S&F Double door SPN MCB DB with IP-42/43 protection, of 2+8 way concealed in wall after cutting the wall & mending good damage to original finish incl. inter-connection with suitable size of copper wire and N-Link & provision for earthing attachment of Legrand Make.
S&F 240V. MCB Isolator on din rail existing DB and necessary connection of 40 Amp. DP..
S&F 240V. 6-32A DP MCB of Breaking capacity 10 KA&C characteristics on din rail of existing DB and necessary connections.
S&F 32 Amp. 240V TPN with L&N Sheet Steel Main Switch (Havells Make) on angle iron frame on wall.
Wiring in 1.1 KV. grade single core stranded FR PVC insulated & unsheathed copper wire of 2x4 sq.mm. + 1x2.5 sq.mm. in 25mm. PVC Casing-Capping (Precision Make) incl. necy. PVC clips fittings etc..
Distribution Wiring in 1.1 KV. grade 2x1.5 sq.mm. single core stranded FR PVC insulated & unsheathed copper wire in suitable size PVC casing-capping (Precision Make) with 1x1.5 sq.mm. single core stranded FR PVC insulated & unsheathed copper wire for Light/Fan point with piano key type switch fixed on sheet steel fabricated switch board with bakelite top cover on wall incl. necy. connection and making earthing attachment. (Average Run 10 mtr.).
DO DO DO for 5A, 3 Pin flush type plug socket with piano key type switch fixed on Switch Board.
Distribution Wiring 1.1 KV. single core stranded FR PVC insulated & unsheathed copper wire in20mm. PVC rigid conduit FR incl. necy. fittings as required by 2x2.5 sq.mm. + 1x1.5 sq.mm. ECC wire from main to S.V. Lights.
S&F 240V. 16A 3 Pin Modular type plug socket with 16A Modular type switch, without plug top on switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu. Wire and earth continuity wire etc..
Earthing with 50mm. dia G.I. Pipe 3.64mm. thick x 3.04 mtr. long and 1x4 SWG G.I. Wire to G.I. Nuts, Bolts, Double Washer incl. S&F 15mm. dia G.I. Pipe protection incl. S&F under the ground level and partly above the ground level.
S&F socket type Fan Regulator ((Make Anchor as per GS )on existing Switch Board with bakelite top cover by screw after making housing for Regulator Knob by cutting bakelite top cover incl. making necy. connections etc..
S&D with fixing 14 SWG heavy duty Fan down rod including delling hole nute bolt & washer complited with 3x1.5 sqmm single core insuleted copper as required.
Supply & Fixing 16" wall bakelite Fan of reputed make complying the necessary ISI standard complete with all accessories as per GS..
Supply & Fixing 9"(225 mm) Exhaust Fan of reputed make complying the necessary ISI standard complete with all accessories as per GS..
Fixing only Exhaust Fan after making hole in wall and making good damage and smooth cement finish etc. as practicable as possible and making connection for Exhaust Fan of 23 cm. diameter.
Supply & Fixing 240 V, 25 A , 3 pin Modular type plug socket (Brand approved by EIC),.
Supply and fixing PVC Rigid conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building work.
c) 8 Mouule.
d) 2 Row12 Mouule.
Supply & fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connection as required.
Supply & fixing 240 V 6 A 5 Pin Modular type plug socket (Brand approved by EIC) without switch and plug top, on existing GI Modular type switch board with top cover plate and making necessary connection with PVC Cu wire and earth continuity wire etc..
S & D with Fixing 100 Watt philips street LED light incl. 1.5 mtr long ms arms backet with saddle on the out side building ( Philips - 100Watt).
Fixing only single/twin/fluorescent light fittings complete with all accessories diirectly on wall etc…
Supply of LED tube light 4 feet 20 w cool white (Make- Philips/Cromption & Grieves/ Orpat).
Supply of 40mm nominal size stone aggregate , from nearest railway yard to proposed location including loading, carriage, unloading, stacking and Spreading per cum ( ref po 5300543685).
Erection of Isolator cum LA Support Structure (PCC 9 Mtr. 4 Pole) with supply of all Nuts & Bolts .
Erection of Isolator Support Structure (PCC 9 Mtr. 4 Pole) with supply of all Nuts & Bolts .
Erection of Bus/Bay support structure (PCC 9Mtr. 4 Pole) with supply of all Nuts & Bolts.
Erection of single rail pole w/o fittings with painting.
Fixing of 33 KV Pin Insulator.
Fixing of 11 KV Pin Insulator.
Fixing of 11 KV Disc Insulator.
Fixing of 33 KV Disc Insulator.
Erection of 33 KV 400A CR type Isolator HL W/O ES..
Erection of 33 KV 400A CR type Isolator HL with ES..
Erection of 33 KV 400A CR type Isolator LL W/O ES..
Erection of 33KV VCB, SCADA compatible.
Erection of 33KV , C&R Panel , SCADA Compatible for individual control of power transformers with differential relay.
Erection of 33KV , C&R Panel with Dirrectional relay, SCADA Compatible for feeder control.
Erection of Switchgear (Shunt trip) with VCB (12KV 350MVA 1250/800A) 4 Panel (1IN +1BC+2OUT).
Erection of 33KV, 200-100/1-1-1A, CT..
Erection of 33KV PT..
Erection, of the C.T. Structure, along-with the supply, of the iron material(s), (i.e., as related, to the C.T. Structure).
Erection, of the P.T. Structure, along-with the supply, of the iron material(s), (i.e., as related, to the P.T. Structure).
Installation, of the C.T. Junction Box, along-with the supply, of the iron material(s), (i.e., as related, to the C.T. Junction Box).
Installation, of the P.T. Junction Box, along-with the supply, of the iron material(s), (i.e., as related, to the P.T. Junction Box).
Supply, Delivery, Fitting, Fixing, Erection, and Commissioning, of the 415 Volts A.C. Distribution Panel, for the 33/11 KV Sub-Station Control Room.
Supply, Delivery, Fitting, Fixing, Erection, and Commissioning, of the 30 Volts D.C. Distribution Panel, for the 33/11 KV Sub-Station Control Room.
Erection, of the cable supporting structure, along-with the supply, of the iron material(s), (i.e., as related, to the cable supporting structure).
Installation of 6.3 MVA, 33/11KV Power transformer.
Erection of RTCC Pannel for 6.3 MVA, 33/11KV PTR..
Erection of ACSR 200 Sq. mm (PANTHER) Conductor (3 Wire) including laying, hoisting, jointing etc..
Supply, of the Isolator Pad to Panther Bi-metallic Connector.
Supply, of the Panther to Panther Tee Connector.
Laying of 11KV, 3X300 sq. mm XLPE cable.
Jointing of O/D type heat shrinkable end termination jointing kit for 11KV, 3X300sq mm XLPE cable.
Jointing of I/D type heat shrinkable end termination jointing kit for 11KV, 3x300sq mm XLPE cable.
Jointing of O/D type heat shrinkable end termination jointing kit for 11KV, 3X185sq mm XLPE cable.
Jointing of I/D type heat shrinkable end termination jointing kit for 11KV, 3x185sq mm XLPE cable.
Supply & fixing of G.I. Pipe 150 mm dia suitable for cable protection. (3M long).
Rising per cable end and clamping it with existing stucture.
Laying of Copper control cable 12C X 2.5 sq mm..
Laying of Copper control cable 8C X 2.5 sq mm..
Laying of Copper control cable 4C X 2.5 sq mm..
Erection of 42 KV LA (3 nos in 1 set).
Erection of 12 KV LA (3 nos in 1 set).
Fixing of Danger Board (33 KV & 11 KV).
Earthing arrangement with supply of earthing materials.
Supply, Delivery, Fitting, Fixing, and Installation, (along-with the (necessary) Wiring Work(s), and the (other) allied Work(s)), of the 10 (Ten) No(s)., of the Flood Light Complete Set 400 W.
Any other item not covered in this schedule wiil be applicable as per PWD Schedule of rate w.e.f 01.11.2017 , all Addenda & Corrigenda of SOR, upto 01.11.2019.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.49 MB
BOQ_2458423.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid