Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.2 CrAccepted-AOC | ₹3.2 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹3.6 Cr+₹33.3 L (10.3%)Rejected-Finance 4TH FLOOR VOLTAS HOUSE A BLOCK DR BABASAHEB AMBEDKAR ROAD CHINCHPOKLI MUMBAI MAHARASHTRA 400033 | MUMBAI | MAHARASHTRA | 400033 | ₹3.6 Cr+₹33.3 L (10.3%) | L2 | Rejected-Finance Being L2 Bidder |
| 3 | L3₹3.7 Cr+₹49.0 L (15.2%)Rejected-Finance | ₹3.7 Cr+₹49.0 L (15.2%) | L3 | Rejected-Finance Being L3 Bidder |
| 4 | L4₹3.9 Cr+₹65.8 L (20.4%)Rejected-Finance | ₹3.9 Cr+₹65.8 L (20.4%) | L4 | Rejected-Finance Being L4 Bidder |
| 5 | L5₹4.5 Cr+₹1.3 Cr (39.7%)Rejected-Finance | ₹4.5 Cr+₹1.3 Cr (39.7%) | L5 | Rejected-Finance Being L5 Bidder |
| Sl No | Description | Qty | Unit | VOLTAS LIMITED L2 | ADS ENGINEERS L4 | HVAC Solutions L3 | BRITE INDUSTRIES L5 | TRANSTECH L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | AIR-COOLED SCREW CHILLING UNIT
Supply, installation, testing & commissioning of AHRI Certified Air-Cooled semi- hermetic horizontal twin Screw chiller units required nos. of compressor, evaporator, water- cooled condenser, micro-processor based control panel with starter etc. The chiller will be precharged with CFC/HCFC free R134a Refrigerant gas. The drive motor suitable for 415V +/-5%, 3 phase, 30-50 cycles/sec , drive assembly, guard, etc. The chiller should be insulated as per manufacturers standard. Microprocessor based starters shall be unit mounted with protection for under voltage, over load, earth fault and single phasing etc. The quoted price shall also include necessary vibration isolators. Micro-processor based controls with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet parameters, operating pressures, minimum 1000 event log, fault history etc., Power and control hardware including one point start-stop, protective Main Switch for electric motors, starters, safety features for under-voltage and over voltage, single phase preventer, trip circuit with sensing elements for HP/LP/Anti-freeze, chilled water temperature sensors. Compressor shall be able to unload down upto 25%. COP and IPLV of chiller shall be as per ECBC building code.Actual cooling capacity at designed conditions indicated below : | 3 | NOS | 37,96,700 ₹1,13,90,100 | 28,04,400 ₹84,13,200 Lowest | 40,18,556 ₹1,20,55,668 | 43,16,750 ₹1,29,50,250 | 38,41,038 ₹1,15,23,114 |
| 1.011. Minimum Cooling Capacity : 100 TR Screw - (Actual Capacity @ following Design Conditions) | ||||||||
| 1.022. Type of Refrigerant : R-134A | ||||||||
| 1.033. Chilled Water 'In' : 12 Deg C | ||||||||
| 1.044. Chilled Water 'Out': 7 Deg. C | ||||||||
| 1.055. Chiller Fouling Factor : 0.0001 (FPS) | ||||||||
| 1.066. The electrical panel should be IP55 protected (As per OEM Standard) | ||||||||
| 1.077. Ambient Temperature: 104 Deg F / 40 Deg C | ||||||||
| 1.088. Minimum IKW/TR should be less than equal to 1.46 at design condition (Including Fan Power) | ||||||||
| 1.099. Minimum COP at AHRI Condition not less than 3.0 & IPLV Minm 3.70 at AHRI conditions as per ECBC guideline. | ||||||||
Tender Value
Refer Docs
EMD Value
₹6.4 L
Closing Date
4 Jul 2025, 2:00 pmClosed
EE,NORTH 24 PARGANAS ELECTRICAL DIVISION,PWDte.
OFFICE OF THE EXECUTIVE ENGINEER NORTH 24 PARGANAS ELECTRICAL DIVISION, TOP FLOOR, MECHANICAL COMPLEX,BAGUIATI, KOLKATA 700 059
Construction of G plus 2 storied 50 Bedded Critical Care Block at Barasat Government Medical College and Hospital Campus, Barasat, North 24 Parganas District SITC of Air Conditioning System.
2025_WBPWD_856335_1
WBPWD/EE/N24/EL/e-NIQ- 12/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
Barasat
Please refer Tender documents.
4 documents required · 4 mandatory
₹6.4 L
NORTH 24 PARGANAS ELECTRICAL DIVISION
16 Sept 2026
30 May 2025
7 Jul 2025
30 May 2025
4 Jul 2025
5 Jun 2025
4 Jun 2025
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | AIR-COOLED SCREW CHILLING UNIT
Supply, installation, testing & commissioning of AHRI Certified Air-Cooled semi- hermetic horizontal twin Screw chiller units required nos. of compressor, evaporator, water- cooled condenser, micro-processor based control panel with starter etc. The chiller will be precharged with CFC/HCFC free R134a Refrigerant gas. The drive motor suitable for 415V +/-5%, 3 phase, 30-50 cycles/sec , drive assembly, guard, etc. The chiller should be insulated as per manufacturers standard. Microprocessor based starters shall be unit mounted with protection for under voltage, over load, earth fault and single phasing etc. The quoted price shall also include necessary vibration isolators. Micro-processor based controls with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet parameters, operating pressures, minimum 1000 event log, fault history etc., Power and control hardware including one point start-stop, protective Main Switch for electric motors, starters, safety features for under-voltage and over voltage, single phase preventer, trip circuit with sensing elements for HP/LP/Anti-freeze, chilled water temperature sensors. Compressor shall be able to unload down upto 25%. COP and IPLV of chiller shall be as per ECBC building code.Actual cooling capacity at designed conditions indicated below : | 3 | NOS | 2.25 | ₹6.75 |
| - | 1. Minimum Cooling Capacity : 100 TR Screw - (Actual Capacity @ following Design Conditions) | - | - | - | - |
| - | 2. Type of Refrigerant : R-134A | - | - | - | - |
| - | 3. Chilled Water 'In' : 12 Deg C | - | - | - | - |
| - | 4. Chilled Water 'Out': 7 Deg. C | - | - | - | - |
| - | 5. Chiller Fouling Factor : 0.0001 (FPS) | - | - | - | - |
| - | 6. The electrical panel should be IP55 protected (As per OEM Standard) | - | - | - | - |
| - | 7. Ambient Temperature: 104 Deg F / 40 Deg C | - | - | - | - |
| - | 8. Minimum IKW/TR should be less than equal to 1.46 at design condition (Including Fan Power) | - | - | - | - |
| - | 9. Minimum COP at AHRI Condition not less than 3.0 & IPLV Minm 3.70 at AHRI conditions as per ECBC guideline. | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tenderdocument.pdf
Tender Documents • 0.43 MB
BOQ.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .