XEN ED RAJOURI
OFFICE OF XEN ED, RAJOURI
SITC FOR HT IMPROVEMENT IN SUNDERBANI UNDER UT CAPEX ON TURNKEY BASIS
2022_PDD_194857_1
EDR/62 of 2022-23 Dated 01.11.2022
Open Tender
Electrical Works
Turn-key
60 days
RAJOURI
Please refer Tender documents.
3 documents required · 3 mandatory
₹200
XEN ED RAJOURI
₹9,020
31 Mar 2023
5 Nov 2022
15 Nov 2022
5 Nov 2022
14 Nov 2022
5 Nov 2022
Amount
11 KV (HT) Line (Note: For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, Insurance, Unloading, Carriage, Delivery at Site including handling, preservation and proper storage at site.
PCC Pole 8 Mtr. Long Wl 200kg (As per recommended IS/REC Standard)
30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
GI Channel Cross-arm (75 x 40x6mm) with GI Angle Braces, GI Pole Top Bracket (50x50x6 mm) including GI Back Clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard. (As per recommended IS/REC Standard)
11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
11 kV DISC WITH FITTINGS( 45 KN) (As per recommended IS/REC Standard)
11KV Link Set Complete
Galvanized Nuts and Bolts of sizes.
Erection/Installation, Testing and commisioning of material supplied at Sl. No-1.01
Erection of PCC Pole 8 Mtr. Long Wl 200kg with pit excavation and refilling of pit complete work. (As per recommended IS/REC Standard)
Laying, stringing and binding of 30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
Fixing / Erection of GI Channel Cross-arm (75 x 40x6mm) with GI Angle Braces, GI Pole Top Bracket (50x50x6 mm) including GI Back Clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard. NOTE: Please refer Pole drawings for details (As per recommended IS/REC Standard)
Fixing of 11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
Fixing of 11 kV Disc Insulator with fitting (polymer) with Pins (45 KN) (As per recommended IS/REC Standard)
Fixing of 11KV Link Set Complete
Fixing of Galvanized Nuts and Bolts of sizes.
JAIDEV ENTERPRISES
BN ENTERPRISES
Pritam Chand
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .