Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.2 LAccepted-AOC | ₹8.2 L Quoted ₹8.6 L | L1 | Accepted-AOC ACEEPTED BEING LOWEST TENDER |
| 2 | L2₹10.6 L+₹2.0 L (23.5%)Rejected-AOC SHOP NO 5 OPP SHANI MANDIR PROFESSOR COLONY DISTT YAMUNA NAGAR HARYANA 135001 | YAMUNANAGAR | HARYANA | 135001 | ₹10.6 L+₹2.0 L (23.5%) | L2 | Rejected-AOC REJECTED BEING NOT LOWEST TENDER |
| 3 | L3₹11.0 L+₹2.5 L (28.8%)Rejected-AOC | ₹11.0 L+₹2.5 L (28.8%) | L3 | Rejected-AOC REJECTED BEING NOT LOWEST TENDER |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
14 Oct 2021, 6:00 pmClosed
GE I RND DEHRADUN
GE I RND DEHRADUN DEAL RESIDENTIAL COMPLEX RAIPUR ROAD DEHRADUN 248008
REPAIR / MAINT OF LT PANELS , FEEDER PILLAR BOXE AND LT UG CABLES, OH LINES AND CERTAIN ALLIED WORKS AT DEAL UNDER GE (I) R N D DEHRADUN
2021_MES_477179_1
GE(I)RND/9069/E8/21-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DEHRADUN
Class E Category b (i) FOR UNENLISTED CONTRACTOR (i) Enlistment criteria may be seen in Para 1.4 of section of Part I of MES Manual on contracts-2007 (Reprint 2012) as available in all MES formations (ii) Copy of police verification /passport.
6 documents required · 6 mandatory
₹500
GE I R N D DEHRADUN
₹24,000
Yes
2 Nov 2021
23 Sept 2021
16 Oct 2021
23 Sept 2021
14 Oct 2021
30 Sept 2021
23 Sept 2021 - 30 Sept 2021
Amount
Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection covers/ bricks & stacking serviceable bricks for reuse and disposal of unserviceable covers within 50 m all as directed. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection. (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations
M&L for Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed and tested complete all as specified and directed by Engineer-in-Charge.
M&L for Removal of surplus excavated soils not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified.
Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed by Engineer-in-Charge.
M&L for old size sub class `B` bricks, kiln burnt, as in cable protection laid flat with axis of brick perpendicular to the axis of the cable complete all as specified and directed by Engineer-in-Charge.
Fixing / laying only old bricks of any description as obtained from dismantling of the cable complete all as specified and directed by the Engineer-in-Charge.
Disconnecting and taking out old existing unserviceable/ corroded GI tubing of any description and in any position complete all as specified and directed by the Engineer-in-Charge.
Supplying, laying & jointing GI water tubing, 80 mm bore, medium grade as in sleeving etc laid in trenches / ducts etc. complete all as specified and directed by Engineer-in-Charge.(MAKE : TATA/JINDAL/TT SWASTIK)
Supplying, laying & jointing GI water tubing, 50 mm bore, medium grade as in sleeving etc laid in trenches / ducts etc. complete all as specified and directed by Engineer-in-Charge.(MAKE : TATA/JINDAL/TT SWASTIK)
Dismantling & taking out unserviceable steel & iron items from poles and Supply & fixing cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts & bolts , washers , welding bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
Disconnecting and taking out old existing unserviceable/ non- functional LT Cable and Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminum conductor for working voltage upto and including 1100 Volts, cross sectional area of under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe complete all as specified and directed by Engineer-in-Charge. Make:Havells/CCI/ICL/GLOSTER/Incab/Nicco/Polycab/Plaza) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and brick protection shall be measured and paid separately )
(a) 25 Sqmm 3½ core.
(b) 35 Sqmm 3½ core
(c) 50 Sqmm 3½ core
(d) 70 Sqmm 3½ core
(e) 95 Sqmm 3½ core
(f) 120 Sqmm 3½ core
(g) 150 Sqmm 3½ core
(h) 185 Sqmm 3½ core
(j) 240 Sqmm 3½ core
(k) 16 Sqmm 4 core
M & L for cutting chases in hard standing road/path/drain etc for passing cables/pipes etc. size of cutting 100mm wide and 200mm deep and removing the excavated materials and disposal at 50 metre distance and making good the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed.
Dismantling & taking out of old existing unserviceable insulators of any description and in any position from LT poles all as specified & directed.
Supply & fixing pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100mm height and 65mm dia suitable for working pressure upto and including 1100 volts grade complete all as specified for LT lines fixed on poles.
Supply and fixing shackle type porcelain vitreous, white, brown or green insulator for working pressure 1100V of 115mm dia and 100mm high including galvanized mild steel strip 31 x 3mm, insulator bolts 14mm dia washer and nut complete all as specified for LT lines fixed on poles.
Dismantling & taking down of existing worn out / unserviceable aluminium conductor, steel reinforced (ACSR) of any description /size & in any position from existing LT Poles/Lines all as specified & directed.
Material & labour of aluminium conductor, steel reinforced (ACSR) of any size/description on LT poles/lines including stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers, connections etc including connecting, commissioning and testing complete all as specified & directed by Engineer-in-Charge.
Disconnecting & taking down old existing unserviceable MCCB of any description and in any position complete all as specified and directed by Engineer-in-Charge.
Supplying and fixing MCCB, 630 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu100% = 35/36 KA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/Havells
Supplying and fixing MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Ics = 100% of Icu 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/Havells
Supplying and fixing MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder / L&T / Havells
Supplying and fixing MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder / L&T / Havells
Supplying and fixing MCCB, 160 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/Havells
Supplying and fixing MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/Havells
Supplying and fixing MCCB, 63 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/Havells
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete all as specified and directed by Engineer-in-Charge.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of front operated ON Load type changeover switch 4 pole, 415 volts, 630 Amps fixing in existing panels without sheet enclosure complete all as specified and directed.Make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of front operated ON Load type changeover switch 4 pole, 415 volts, 400 Amps fixing in existing panels without sheet enclosure complete all as specified and directed.Cat part No: Make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 400 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0630 of make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 250 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0630 of make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 200 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0320 of make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 160 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0320 of make Havells or equivalent model of specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 100 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0320 of make Havells or equivalent model of specified make as approved by GE.
Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - Near DSC line)
(i) Incoming :- (a) MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size.
(ii) Out Going :- (a) MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (b) MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - between MIC & Dessi Bldg)
(i) Incoming :- (a) On load change over switch, 400 Amps, 4 pole, 415 Volts, AC supply, with suitable enclosure Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size. (ii) Out Going :- (a) MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (b) MCCB, 160 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S (b) MCCB, 63 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 16 KA with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/Havells/C&S
Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - Near JCO line)
(i) Incoming :- (a) MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size.
(ii) Out Going :- (a) MCCB, 160 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (b) MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No.(Make: Legrand/Schneider/Siemens/Havells/C&S
Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - Near JCO line)
(i) Incoming :- (a) MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size.
(ii) Out Going :- (a) MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (b) MCCB, 63 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No.(Make: Legrand/Schneider/Siemens/Havells/C&S
Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Supply and fixing in replacement of following defective parts of existing unserviceable power factor panel (APFC PANEL)installed at different location/capacity for improvement of power factor complete all as specified and directed.
Three Phase power factor meter 96X 96mm digital with acc +/_ 0.01 flush mounted.
Automatic power factor controller relay alongwith connection of 8 stage .
Self healing MPP film heavy duty power capacitor, resin filled 440 volts AC 3 phase supply, of capacity 10 KVAR
Self healing MPP film heavy duty power capacitor, resin filled 440 volts AC 3 phase supply, of capacity 05 KVAR
Capacitor duty Contactor Type IC125, KVAr rating 12.5 @ 415 volts, 3 phase, 50 Hz Ac supply
Dismantling, taking down and removing the old existing un serviceable non-functional / broken hinges of any description and in any position of existing feeder pillar boxes/panel boards/feeder pillar boxes etc and supplying and fixing new cold rolled 50 mm long medium weight mild steel butt hinges in position with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed by Engineer-in-Charge. (Note :- Each hinge point shall be measured as one unit. )
-ditto- but supplying and fixing new cold rolled 100 mm long medium weight mild steel butt hinges in position –ditto-
Taking down unserviceable indication lamp and supplying, fixing, testing and commissioning indication lamp (LED type) with showing red, yellow and green in colour of 22.5 mm dia monitor on LT panel board suitable for 240 V AC supply all as specified and directed. Make : L&T /Binay.or equivalent approved.
Disconnecting, dismantling, taking out & removing unserviceable volt meter and Supplying, fixing, testing and commissioning of digital electronic volt meter 0-500 V range suitable for LT 415 Volts panel flush pattern square type 96mmX96mm with adopter complete with button all as specified and directed. Make : ENERCON/AE Note :- The rate quoted shall be deemed to including the following:- (i) Control wiring for auxiliary supply 230 Volts AC if required. (ii) Cutting the sheet of the panel to suit with existing panel if required. (iii) Calibration and testing the meter.
Demolition of cement concrete (unreinforced) of any description as in ground floors and pavings not exceeding 15 cm thickness (above or below ground floors) complete all as specified and directed.
M&L for cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in cills, steps, copings, holdfast and the like including weathering, slightly rounded or chamfered angles and throating as directed with and including necessary form work complete all as specified and directed.
Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables all as specified and directed by the Engineer-in-Charge. (MAKE : M.SEAL/DENSON/ MAHINDRA CHEMICALS/3M) :-
50 Sqmm 3½ core
70 Sqmm 3½ core
95 Sqmm 3½ core
120 Sqmm to 150 Sqmm 3½ core
185 Sqmmto 240 sqmm 3½ core
M&L for earthing complete for bldg with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected to galvanized earth wire 4.00 mm dia by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish , internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh, 80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 5 of MES SSR Part-I (1991) and specified including provision of earth wire protected by 15mm dia medium grade GI pipe and watering GI pipe shall be 20mm bore medium grade etc complete, all excavation and earth work & connecting the earthing to an earthing test point main switch board as specified and testing on completion complete all as specified & directed by Engr-in-Charge. NOTE : RCC pit cover shall be pre-cast of RCC (1:2;4) type B-1 80 mm thick reinforced with XPM weighting not less than 4 Kgs/Sqm in lieu of CI cover.
Material and labour in replacement of UNSV GI strip of size 32mm x 6mm for laying along the wall/roof on batten or burried in ground or drawn in conduit pipe or fixed to poles or any other situation as directed or as required GI strip of size 32mm x 6mm earth continuity conductor complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor all as specified and directed.
All as per item No.48 here in above but using 4 mm dia galvanised iron or steel wire complete all as specified and directed.
JS CONSTRUCTION COMPANY
Ravi Electrical
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .