Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹62,376Accepted-AOC 676521 | MALAPPURAM | KERALA | 676521 | 1 | Accepted-AOC lowest | |
| 2 | 2₹62,692.36+₹313.58 (0.50%)Rejected-AOC PALAKKASAR VEEDU POTHRAM PINK THALIYAKAND MALAPPURAM 679339 | MALAPPURAM | MALAPPURAM | KERALA | 679339 | 2 | Rejected-AOC second |
Tender Value
₹62,692
EMD Value
₹1,567
Closing Date
25 Nov 2022, 6:00 pmClosed
ASSISTANT EXECUTIVE ENGINEER
Asst.Exe.Engineer
GENERAL-Pump House, PWD Complex, Perinthalmanna-Renovation of pump house - Replacement and shifting of damaged meter board, main switch and connected power wiring-General Electrical Work
2022_PWD_529202_1
ELSDM-46-2022-23
Open Tender
Electrical Works
Item Wise
60 days
perinthalmanna
Please refer Tender documents.
10 documents required · 10 mandatory
₹555
₹1,567
22 Dec 2022
17 Nov 2022
28 Nov 2022
17 Nov 2022
25 Nov 2022
17 Nov 2022
Amount
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD104440/2022-2023:Supply and fixing 9W LED bulb and giving connection etc as required.
OD104441/2022-2023:Supply, conveyance, installation, testing and commissioning of cast aluminium stove enameled elliptical shaped bulk head fittings directly on wall including cutting necessary holes, giving connections with the extended orginal wiring, making good the damgaes, colour washing etc as required.
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
OD104597/2022-2023:Supplying and fixing 4P sheet steel enclosure on surface/ recess suitable for fixing 4P MCB, RCCB, Isolator etc. as required.
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD104628/2022-2023:Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
OD104629/2022-2023:Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
OD104631/2022-2023:Supply and providing 12X3 mm brass bolt
OD104632/2022-2023:Supply and providing 25x6mm brass bolt
OD104635/2022-2023:Supply and providing and fixing 32A TPN disconnector fuse switch unit in sheet steel enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in frame, making connections, etc. as required.
OD104636/2022-2023:Supplying and fixing 32A, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD104637/2022-2023:Supplying and fixing 32 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
OD104638/2022-2023:Supply & installation of dust and vermin proof, 3 Phase Syntax Meter Board( GS-MB- 6535) and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required.
OD104649/2022-2023:Supply and providing suitable Iron Hook Grouted on wall for binding the service wire
OD104650/2022-2023:Supply and fixing 50 mm dia 6Kgff/cm2 PVC pipe including fixing the pipe with clamp/clips at 60cm spacing. etc as required
SAKKARIYA P
Bidder Name
SHAHUL HAMEED V
SAKKARIYA P
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_764720.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .