| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹1.5 CrAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹1.5 Cr+₹57,906.69 (0.38%)Admitted-Finance | L2 | Admitted-Finance | ||
| 3 | Rejected-Technical | - | Rejected-Technical non responsive |
| Sl No | Description | Qty | Unit | JAYSHWAL ENTERPRISES L1 | Gitaa Equipment Industries L2 |
|---|---|---|---|---|---|
| 1.00 | Supply of Painted/ Powder coated galvanized steel Flush Fire doors . Fire rating and tested in accordance with IS 3614 Part 2 & BS 476 Part 22 as per prototype tested and certified at CBRI Roorkee or equivalent laboratory. Door frames to be double rebate profile of 143 x 57mm manufactured from 1.6mm galvanized steel sheet, profile to have bending radius of 1.4 mm supplied in assembled form ready to install at site. Door Shutter in 46mm +2 mm thick manufactured from 1.2mm galvanized steel sheets, lock seam jointed at stile edges to form a double skin fully flush shell. Infilled honeycomb insulation material to be provided for structural rigidity & additional reinforcements & sound Insulation, The internal construction of the door should be appropriate for all hardware fixtures (SS Ball BearingHinges-4"x3"X3mmGeze,Door Closer, Dead LockWith 70mm EPC,Handle-300X19mm, Vision Panel,Flush Bolt etc.) as required, vision panel grooves wherever applicable shall be provided as per recommendations with beading and screw. (Hardwares to be paid seperately as per your requirement.) Size: 1800 x 2100mm- Double Leaf | 14 | Each | 45,500 ₹6,37,000 | 45,000 ₹6,30,000 Lowest |
| 2.00Supplying, Installation, Testing & Commissioning of floor mounted dust and vermin proof compartmentalised cubical type main fire pump Control Panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories / switch gear (as per Specf Ch-06 & 08) as below:- complete in all respect. All as per pre approved by Engineer in charge. | |||||
| 2.10Incomer:- 400 Amp. TPN MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 500 Amps FP Alum. Bus bar with with heat shrinkable sleeves. | |||||
| 2.20Out going:- (a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of rating upto 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets | |||||
| 2.30(b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 16 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of 5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set | |||||
| 2.40(c) One no. Diesel Engine Auto Starting kit with Auto Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, DC ammeter & voltmeter | |||||
| 2.50(d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence consisting of relays, timers, sensors, annuciation window for fault indication. | |||||
| 2.60(e) Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. | |||||
| 2.70 | (e) Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. | 1 | Each | 1,50,000 ₹1,50,000 Lowest | 1,85,000 ₹1,85,000 |
Tender Value
₹1.6 Cr
EMD Value
₹3.2 L
Closing Date
2 Sept 2026, 6:00 pmClosed
Executive Engineer Medical and Health SWM
Executive Engineer Medical and Health SWM
SITC of Fire Fighting Fire Detection work for construction of Sub District Hospital at Nainwa District Bundi
2026_MEDIC_589500_2
Nit No. 06/2026-27 Executive Engineer Medical and Health Sawai Madhopur
Open Tender
Electrical Works
Percentage
270 days
Bundi
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
RTGS/NEFT/Any other money Transfer System
₹3.2 L
Yes
23 Sept 2026
17 Aug 2026
3 Sept 2026
17 Aug 2026
2 Sept 2026
17 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H. | |||||
| 1.1 | (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head | - | - | - | - |
| 1.2 | (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal | - | - | - | - |
| 1.3 | (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head | - | - | - | - |
| 1.4 | (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . | - | - | - | - |
| 1.5 | ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. | - | - | - | - |
| 1.6 | (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. | - | - | - | - |
| 1.7 | (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM | - | - | - | - |
| 1.8 | (H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. | - | - | - | - |
| 1.9 | 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM | 1 | Each | 4,18,616 | ₹4,18,616 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 3.30 MB
Tendernotice_2.pdf
PDF • 1.73 MB
Tendernotice_3.pdf
PDF • 1.16 MB
Tendernotice_4.pdf
PDF • 13.10 MB
Tendernotice_5.pdf
PDF • 1.19 MB
Tendernotice_6.pdf
PDF • 0.12 MB
BOQ_1046997.xls
BOQ • 0.41 MB
Condition2.pdf
Tender Documents • 1.17 MB
corrigendum.pdf
PDF • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .