| 1 | | Dismantling & Shifting of PAPI
Installation, Testing and Commissioning of�AMA�make PAPI unit along with base plate i/c grouting of checking stick base plate with foundation bolts with 1/2/4 cement concrete of suitable size, ground calibration,alignment with other PAPI units,installation of Isolating Transformer, making connection with secondary lead including fixing & crimping of ESNA connector etc complete as required and to be carried out by specialized agency in time bound manner as per direction of EIC( 1 Job for 4 PAPI units shifting for approx 30 mtr). | 1 | Job | electrical_vaks | 45 |
| 2 | Installation of Transformer Housing Box | Installation of M.S Type transformer housing box on the shoulder of PAPI units etc withh 1/2/4 ratio cement concrete of 100mm thickness all round the box and bottom i/c excavation of bitumenous surface, leveling, aligning the box, making pedestal of suitable�size with desire slope around the box etc as required as per instruction of Engineer-In-Charge. | 12 | Each | electrical_vaks | 45 |
| 3 | | PAPI siting back Calculation and ground-�calibration of re-installed PAPI units with check stick and submission of reports to meet CAR requirements. | 1 | Job | electrical_vaks | 45 |
| 4 | SITC of Runway end inset light | SITC of Inset type Runway End cum Threshold Light (�bidirectional high intensity combined threshold and runway end light) suitable to fit on existing base plate equipped with three 105 W 6.6A halogen pre-focused reflector lamps | 12 | Each | electrical_vaks | 45 |
| 5 | SITC of isolating transformer | SITC of 300W 20/6.6A isolating transformer | 12 | Each | electrical_vaks | 45 |
| 6 | | Supply of Suitable Secondary leads with premoulded to provide supply to the above installed bi-directional Runway end, Threshold inset type lights. | 500 | Meter | electrical_vaks | 45 |
| 7 | | Kerf cutting with machine in runway bituminous surface of suitable depth and width for secondary and earth cable laying in GI pipe and refilling the same by suitable sealing material etc complete as required. | 300 | Meter | electrical_vaks | 45 |
| 8 | Shifting of Apron edge lights | Dismantling and Shifting of Existing�Apron Edge Lights to the desired position along with provision of new CI Transformer Housing boxes with 1/2/4 ratio cement concrete of 100mm thickness all round the box and bottom i/c excavation of bitumenous surface, leveling, aligning the box, making pedestal of suitable�size with desire slope around the box etc as required as per instruction of Engineer-In-Charge. suitable to fix�AMA�make LED taxiway light fixtures | 4 | Each | electrical_vaks | 45 |
| 9 | C.I. transformer housing box | Supply of C. I. isolating transformer housing box, water tight round type, metal container of outside parameter size 330mm height 450mm made of 10mm thick cast iron moulding all round expect top surface, which is 15mm thick, cast iron moulding suitable to receive light fitting base plate on the top & under ground housing associated with transformer power cable & having a clear hole center at one site surface center 75mm above button surface suitable to receive one no./two nos. of 50mm dia B class GI pipe and including check nuts as required and another hole at 175mm from the button of C. I. box to receive one no. 15mm dia, B class, GI pipe and check nut as required. The box should have two SS earth bolts of M10 x 30mm tapped inside near the hole (4 inch away from the hole centre) and having a drain hole at the bottom suitably tapped to receive 15mm dia, B class GI pipe and having clear opening of 220mm at the top surface and 6 nos. M10 tapped hole at the hole centre 260mm to receive fitting base plate and bolts as required as per the drawings. | 16 | Each | electrical_vaks | 45 |
| 10 | | Supply of 1x6 Sq. mm PVC insulated & PVC Sheathed Stranded copper conductor single core airfield lighting cable of 5 KV grade conforming to IS 1554 Part-II with upto date amendments as required and conforming to particular specifications. | 420 | Meter | electrical_vaks | 45 |