Loading…
Loading…
Tender ID
Tender Value
₹30 L
EMD Value
₹40,000
Closing Date
13 Feb 2026, 6:00 pmClosed
Executive Engineer, RANDER DIVISION
Laying of underground cable network with terminations in the area of DGVCL under Olpad Sub Division under Rander Division on ARC basis under S.I. & D.I.S.S. Scheme.
272122
DGVCLSDPLN/0004/02/2026 Approved Date: 02-02-2026
Open
Electrical - All
Works
Surat
3 documents required · 3 mandatory
₹1,180
SURAT
₹40,000
2 Feb 2026
2 Feb 2026
2 Feb 2026
13 Feb 2026
2 Feb 2026
Schedule-B for ARC for Erection and labour work of supply, laying, testing & commissioning of 11/22 KV
Underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight
through jointing kit (To be supplied by contractor) on ARC basis under S.I & D.I.S.S Scheme for Olpad sub
division under Rander division and if required work to be carried out at other sub division under Rander
Item Code Description Unit FY 2024-25
Labour charge for excavation of cable trench of
400mm width x 1200mm depth, in any type of
soil for laying of cable of size up to 240 mm2
(For additional cable 200 mm additional width
shall be considered i.e. half trench length is to be
Labour charge for excavation of cable trench of
600mm width x 1200mm depth, in any type of
soil for laying of cable of size up to 240 mm2
(For additional cable 200 mm additional width
shall be considered i.e. half trench length is to be
Labour charge for excavation of cable trench of
400mm width x 1500mm depth, in any type of
soil for laying of cable of size up to 240 mm2
(For additional cable 200 mm additional width
shall be considered i.e. half trench length is to be
Labour charge for laying of 11kV / 22 kV XLPE
Cable of size up to 240 mm2 & preparation of
sand layer 100mm thick, in the cable trench &
covering the cable with 150 mm dia (Inner),
thickness 25 mm, 1.0 meter long RCC half
round muffs and providing and fixing of 4inch
width yellow colour polyethylene tape with
printing "CAUTION ELECTRIC CABLE BELOW"
at 0.75 m depth from ground surface after laying
cable in trench. This will provide indication that
electric cable is passing underground so as to
protect cable from mechnical injuries, refilling the
same, as per Instruction of Engineer in Charge
Labour charge for horizontal drilling using
Auger machine without damage to surface road
at max 2.0 mtrs depth & putting of 6.11 kg/cm2
class-4,Green color, 110mm O.D. , 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and
laying of 11KV/22KV XLPE cable of size up to
240 mm2 in HDPE pipe, as per Site Condition
(excluding cost of pipe). The detail map obtained
from HDD machine and excell sheet(hard and
soft copy) indicating the respective depth and
distance from adjacent landmark for each
segment for HDD is must required to be
submitted. HDD to be carried out at depth
mtrs to 2.0 mtrs as per site conditions and as per
instruction of EIC.
Labour charge for horizontal drilling manually
without damage to surface road at max 2.0 mtrs
depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984-1987(3rd revision) and
BIS certification and laying of 11KV/22KV XLPE
cable of size up to 240 mm2 size, as per Site
Condition (excluding cost of pipe). The detail map
and excell sheet(hard and soft copy) indicating
the respective depth and distance from adjacent
landmark for each segment of cable to be
submitted. Drilling to be carried out at depth
Minimum 1.2 mtrs to 2.0 mtrs as per site
conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color,
110mm O.D. , 8.5 mm thickness H.D.P.E. pipe
7 9925000007 confirms to IS 4984 and BIS certification for Meter
laying of underground 11KV / 22KV XLPE cable
up to 240 mm2 size.
Labour work for RCC concreting on disputed
location and repairing of damage portion of road
8 9925000008 crossing for the work carried out for roads CMT
crossing as well as concreting & muffing of
ploes including all materials (1:2:4)
Providing & fixing concrete stone route marker of
300 mm width x 150 mm thick x 650 mm
height embedded in earth at least 300 mm below
& 350 mm above ground level respectively at
distance approx 50 meters along the length of
cable. The RCC concreting (1:2:4)(all necessary
maeterials will be in bidder's scope) of route
marker is to be carried out 300 mm width x
9 9925000009 mm thick x 300 mm below ground level as per No.
instruction of EIC. The route marker should be
with name of company with approved yellow
colour-DGVCL. The distance from marker to
cable and cable depth with feeder name etc.,
marked with arrow sign is to be painted on it.The
route marker is to be fixed at location near to any
fixed permanent location (not necessary to fix
exact on top of cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using
9 / 11 Mtr. RSJ pole with cable connection
arrangement along with fitting of necessary
fabrication for 11KV cable including excavation of
pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 /
Mtr RSJ pole with cable connection arrangement
along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit &
refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Erection of D.P. (double pole) structure using
8.0 Mtr. PSC pole with cable connection
arrangement along with fitting of necessary
fabrication for 11KV cable including excavation of
pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr
PSC pole with cable connection arrangement
along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit &
refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE
cable of size up to 240 mm2 on DP Structure
14 9925000014 with fixing of 02 Nos polymer cleats on top Per Job
and middle part.Polymer cleats, nut bolts etc.
fixing material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984 and BIS certification
on the erected DP structure for the mechanical
protection of cable by inserting the cable inside
15 9925000015 HDPE pipe. The HDPE pipe shall be erected in Per Job
such a way that 300mm shall be below the
ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No
Polymer cleat.All materials including polymer
cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from
80 mm dia class-B GI pipe with pit to be filled
with salt & coke and construction of chamber as
per DGVCL Drg. No. dg /100 for DP and cable.
The earthing pit should be joined with cable by
G.I. strip of size 1” width & 2 mm thick. All
material GI pipe, Coke, Salt etc will be supplied
Supply & fixing of heat shrink type end
terminations (outdoor) for upto 11kV 3C x
mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end
terminations (outdoor) for upto 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat shrink type end
terminations (indoor) for upto 11kV 3C x
mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end
terminations (indoor) for upto 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat shrinkable straight
21 9925000021 through joint for upto 11kV 3C x 185 mm2 size No.
XLPE cableas per DGVCL technical
Supply & fixing of heat shrinkable straight
22 9925000022 through joint type for upto 22kV 3C x 185 mm2 No.
size XLPE cable as per DGVCL technical
Labour charge for excavation of 2100mm long x
1200mm wide x 1200 mm deep joint pits for
installation of 11kV / 22kV Straight through
joints as per instruction of engineer-in-charge &
covering the cable with 150 mm dia (Outer),
thickness 25 mm, 1.0 meter long RCC half
round muffs & refilling same as per instruction
Providing and fixing of insulating bus bar, made
from 11KV/22KV XLPE cable after removal of
semi conducting layer and applying of PVC heat
shrinkable anti-tracking core insulating tubing
(1.1KV), on both end terminal using Aluminium
long barrel heavy duty up to 240 sq mm lugs,
24 9925000024 Aluminium bus connector. Taping with PG- clamp No.
for bus conductor as per drawing and as per
instruction of EIC. The Alluminium lugs and PG
clamp shall be covered with 11KV/22KV HT
insulating tapes.(11KV/22KV XLPE cable will be
in scope of DGVCL while all other materials will
be in bidder's scope)
Testing of cable at various points and
commissioning the feeder as per instruction of
engineer-in-charge.Test result shall be submitted
by contractor with bill.
Preparation and submission of 6 (six) copies, of
complete layout drawings with GIS mapping as
26 9925000026 per actual cable routing showing road crossing, Set
HDPE pipe sleeving, jointing locations, markers
Providing and fixing of Sign Board at junction
point Made out of 2 mm aluminium sheet size
750x300 mm (2.5 x 1ft) rectangle, as per design,
pre treated with phosphate process and acid
etching coated with one coat of epoxy primer and
two coats of best quality paints, refloctrorised
with Hi-Intensity retro – reflective sheeting as per
the latest and frame fabricated from suitable size
iron angle. The Sign Board is to be fixed on the
base prepared from channel and bracing angles
which is grouted by means of cement concreting
of 1:2:4 for size of 300 mm dia x 800 mm height
(500 mm to be grouted in ground). The details to
be displayed on sign board will be given by In-
charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger
Board) on Distribution Transformer Centers
Made out of 2mm aluminium sheet size
300x300mm (1x1ft) as per design, pre treated
with phosphate process and acid etching coated
with one coat of epoxy primer and two coats of
28 9925000028 best quality paints, refloctrorised with Hi-Intensity No.
retro-reflective sheeting as per the latest and
frame fabricated from suitable size iron angle.
The Sign Board (Danger Board is to be fixed at
the location as per instruction of In-charge
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size
mm (L) x 75 mm (W) from 3 mm aluminium sheet
along with 1.0 mm dia aluminium binding wire for
fixing of aluminium tag near end termination joint
29 9925000029 at DP structure for identifyng the cable. The No.
details of feeder i.e. 11 / 22 KV with feeder name
shound be punched on the tag by letter punch of
size 16 mm as per instruction of In-charge
Supply & fixing of heat shrink type end
terminations (outdoor) for 11kV 3C x 240 mm2
size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end
terminations (outdoor) for 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat shrink type end
terminations (indoor) for 11kV 3C x 240 mm2
size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end
terminations (indoor) for 22 kV 3C x 240 mm2
size XLPE cable as per DGVCL technical
Supply & fixing of heat shrinkable straight
through joint for 11kV 3C x 240 mm2 size
XLPE cableas per DGVCL technical
Supply & fixing of heat shrinkable straight
through joint type for 22kV 3C x 240 mm2 size
XLPE cable as per DGVCL technical
Installation, Testing and commissioning of
KV,630 A SCADA Compatible, RRL type- 3 Way
36 9925000038 RMU including Two numbers of earthings as per No.
Drawing (material is in bidder's scope) and as per
DGVCL Technical specification.
Installation, Testing and commissioning of
KV,630 A SCADA Compatible, RRLL type-
37 9925000039 Way RMU including Two numbers of earthings No.
as per Drawing (material is in bidder's scope) and
as per DGVCL Technical specification.
Installation, Testing and commissioning of
22KV,630 A SCADA Compatible, RRL type-3
38 9925000040 Way, RMU including Two numbers of earthings No.
as per Drawing (material is in bidder's scope) and
as per DGVCL Technical specification.
Installation, Testing and commissioning of
22KV,630 A SCADA Compatible, RRLL type-4
39 9925000041 Way, RMU including Two numbers of earthings No.
as per Drawing (material is in bidder's scope) and
as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type-
Way (i.e Two numbers of Isolator & One number
of Breaker) Ring Main Unit as per DGVCL's
technical specification mentioned in drawing no:
Drg. 11kv-01. All required material will be
supplied by contractor.
Construction of plinth for 11KV, RRLL type-
Way (i.e Two numbers of Isolator & Two number
of Breaker)Ring Main Unit as per DGVCL's
technical specification mentioned in drawing
no:Drg. 11kv-02.All required material will be
supplied by contractor.
Construction of plinth for 22KV, RRL type-
Way (i.e Two numbers of Isolator & One number
of Breaker) Ring Main Unit as per DGVCL's
technical specification mentioned in drawing no:
Drg. 22kv-01. All required material will be
supplied by contractor.
Construction of plinth for 22KV, RRLL type-
Way (i.e Two numbers of Isolator & Two number
of Breaker)Ring Main Unit as per DGVCL's
technical specification mentioned in drawing
no:Drg. 22kv-02.All required material will be
supplied by contractor.
Modifications e.g.Providing and fixing of Terminal
protectors i.e. Re-use able boot (HT Side
11/22KV, LT Side 1.1KV) including 11/22 KV
insulating taps and L.T.(1.1 KV) insulating taps
,Busbar, Tapping from Bus Bar (11/22 KV XLPE
cable) through P.G. Clamp for H.T. Jumper to
D.O. Fuse to bushings of Transformer Center,
providing & Fixing of jumper and providing &
fixing of Heat Shrinkable Anti Tracking Core
Insulating Tubing (Insulation Level 11/22 KV) in
H.T. jumper , Clamping arrangement of cable
44 9925000046 support frame on both side of existing Over Head No.
type Distribution Transformer to utilize in Under
Ground cable network as per drawing & as per
instruction of Engineer incharge. All live parts
i.e. PG-Clamp, connections of D.O.fuses, HT
bushings etc . shall be covered with fixinng of
11/22 KV HT insulating tapes. ( 11/22 KV XLPE
cable will be in scope of DGVCL while all other
materials will be in bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE /PILC
45 9925000047 Per Cable Per Mtr
Cable in redaymade trench or in open space
Labour charges for Lying of O/H XLPE cable pole
Supply of 150 mm dia (Inner), thickness 25 mm,
1.0 meter long RCC half round pipe
In Words :-- Thirty Lakh Rupees Only
% Above / Below of Estimate Amount
Stamp & Sign of Contractor
Executive Engineer (O&M)
DGVCL,Rander Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. ug cable olpad SI-DISS.pdf
2. OlpadSub Division Bid Document.pdf
3. Olpad Sub Division Detail Tech Specification.pdf
4. Schedule -b for OLPAD SDN UG CABLE.pdf
5.Letter to All DISCOMs for Ratified Common UG Tender Conditions.pdf
6.Reference Bid Drawing.pdf
7.UG CABLE TENDER IMP POINTS.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .