Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.0 LAdmitted-Finance KARUKAPPILLY THATTATHUKUDIYIL BUILDING KOLENCHERY 682311 | KOLENCHERY | ERNAKULAM | KERALA | 682311 | ₹32.0 L | L1 | Admitted-Finance |
| 2 | L2₹48.7 LAdmitted-Finance | ₹48.7 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical XI 105 C1 SECOND FLOOR PADAMUGAL CIVIL LINE ROAD KAKKANAD P O COCHIN 682030 | COCHIN | ERNAKULAM | KERALA | 682030 | - | - | Rejected-Technical Rejected |
| Sl No | Description | Qty | Unit | LAMOS TECHNOLOGY SOLUTIONS PVT LTD L2 | Power Care Electrical L1 |
|---|---|---|---|---|---|
| 1.00Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 1.01 | Group C | 6 | Point | 1,197 ₹7,182 | 1,350 ₹8,100 |
| 2.00Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | |||||
| 2.01 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire | 110 | Metre | 244 ₹26,840 | 190 ₹20,900 |
| 2.02 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 30 | Metre | 443 ₹13,290 | 250 ₹7,500 |
| 2.03 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire | 10 | Metre | 1,241 ₹12,410 | 800 ₹8,000 |
| 3.00Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | |||||
| 3.01 | 3 x 4 sq. mm | 5 | Metre | 579 ₹2,895 | 250 ₹1,250 |
| 4.00Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | |||||
| 4.01 | 5/6 A switch | 10 | Each | 179 ₹1,790 | 120 ₹1,200 |
Tender Value
₹37.3 L
EMD Value
₹74,600
Closing Date
11 Feb 2026, 6:00 pmClosed
Director
NIT Calicut, NIT Calicut Campus PO, Kerala, 673601
SITC of Lighting system for Creative Zone and Admin Block Area
2026_NITC_895816_1
Engg/EMU/TA-04/004/Creative Zone Lighting/25-26
Open Tender
Electrical Works
60 days
NIT Calicut, NIT Calicut Campus PO, 673601
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹74,600
Yes
25 Feb 2026
28 Jan 2026
13 Feb 2026
28 Jan 2026
11 Feb 2026
28 Jan 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 4 sq. mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
4 Module (125mmX75mm)
6 Module (200mmX75mm)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way , Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MOB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MOB TPDB is normally used where 3 phase outlets are required.)
4 way (4 + 12), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MOB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Supplying and fixing single pole blanking plate in the existing MOB DB complete etc. as required.
Supplying and fixing 40A , Three pole, 415 V, C curve Miniature circuit breaker (MCB) in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 40A , Four pole, 415 V, C curve Miniature circuit breaker (MCB) in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Earthing with G.I. earth pipe 2.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
Supply of excel earthing compound or its equivalent etc.
Providing and fixing 25 mm X 5 mm copper strip(tinned with lead) on surface or in recess for connections etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Supply and laying of 3 inch 80 NB GI pipe (medium class B) on ground with all accessories like socket, bend, couplers with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., and making good the damages of road with concrete mixture of 1 : 2 : 4 including watering & ramming etc. as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 25 sq. mm (28mm)
Supplying and making end termination with brass compression gland and copper lugs for 3C × 2.5 sq.mm PVC insulated & PVC sheathed copper conductor cable, 1.1 kV grade as required
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
63 mm dia (00-63 mm & ID-51 mm nominal)
Charges for concreting with 30 x 30 x 90 cm up to ground level and 20 cm above ground level using 8 mm steel reinforcement as per drawing with cement concrete of 1:2:4, after excavation and plastering the sides including a neat cement flushing coat, painting with cement paint etc, as required.
Charges for concreting with 20 x 20 x 70 cm up to ground level and 10 cm above ground level using 8 mm steel reinforcement as per drawing with cement concrete of 1:2:4, after excavation and plastering the sides including a neat cement flushing coat, painting with cement paint etc, as required.
Charges for concreting with 20 x 10 x 30 cm up to ground level and 30 cm above ground level using 8 mm steel reinforcement as per drawing with cement concrete of 1:2:4, after excavation and plastering the sides including a neat cement flushing coat, painting with cement paint etc, as required.
Charges for concreting with 20 x 10 x 30 cm up to ground level and 10 cm above ground level using 8 mm steel reinforcement as per drawing with cement concrete of 1:2:4, after excavation and plastering the sides including a neat cement flushing coat, painting with cement paint etc, as required.
Supply and laying of one number of 8 SWG good quality bare copper wire for loop earthing along with existing XLPE insulated aluminium cable as required.
Supplying of one number 4Cx 25 sq mm Aluminium condutor XLPE insulated PVC sheathed power cable of 1.1 kV grade etc. as required.
Supplying of one number 3Cx 2.5 sq mm copper condutor armoured PVC sheathed power cable of 1.1 kV grade etc. as required.
Supplying and laying of 3 core × 2.5 sq.mm ISI marked PVC sheathed flat submersible cable with bare bunched copper conductor, suitable for working voltage up to and including 1.1 kV, including supply and wrapping with waterproof insulating tape, laying, testing and commissioning complete as required.
Supplying and fixing of weather proof outdoor junction box for outdoor installation of size 130mm x 180mm x 77mm with knockouts for cable entry including dinbar, suitable connectors for connecting Cu/ Al cable to copper cable of suitable size, provision for fixing two number of double pole MCB, weather proof gourmets,glands,clamps,screws of required length fastners connections for surface/ recess fixing on existing concerte base etc. as required(clip type)Hensel IP 69 DK 1010G made or Equivalent.
SITC of 24 Hour Digital Time switch (crono)for operating automatic ON-OFF function 110 - 240 VAC 1 C/O Base/DIN 25 ON/OFF Each,L&T 67DDT0 or equivalent.
SITC of 3 pole power contactor,Type MNX40,240V coil voltage
supplying, installation, testing and commissioning of LED Post Top Luminaire including proper supporting provision /arrangement to fix luminaire to the GI post if necessary,power consumption not exceeding 40 Watt, suitable for mounting on existing pole/post, complete with all accessories and internal wiring, as required at site. The luminaire shall be post-top type with die-cast aluminium housing (grey finish) and frosted white polycarbonate/PMMA diffuser, fitted with high efficiency LEDs having CRI > 80, CCT 3000 K / 4000 K / 5700 K, and minimum luminous efficacy of 80 lumens per watt at 5700 K, complete with inbuilt electronic LED driver. The luminaire shall be compatible with the existing pole and installed without causing any damage to the pole or mounting arrangement. Approved Make: Jaquar – OGL-GRY-PTRING01FD40WWTO / Philips / Equivalent approved make.(Annexure-I)
Design, supply, installation, testing and commissioning of 3 -4 m high decorative pole, made of hot-dip galvanised steel tube Ø76 mm × 3.2 mm thick (Class ‘A’), black PU painted, with gold colour painted decorative cast aluminium rings, complete with welded base plate Ø140 mm × 5 mm thick (Class ‘B’) having 4 mounting holes, including 4 Nos. foundation bolts 16 mm dia × 450 mm long with 200 mm PCD, manufactured from special steel, complete with SS nuts, washers, anchor plate and common template. Pole shall be suitable for 3.0 m height and provided with integral connector block for loop-in / loop-out flushed in bottom portion of pole, including supply and termination of 3C × 2.5 sq.mm flexible copper cable and 6–32 A SP C-curve MCB, complete with all wiring, connections, accessories, testing and commissioning, etc., as required. Approved make: Bajaj BJPL-01-300 ECO / Kesslec 3 m ECO-70/90 spigot or equivalent. (Annexure-II)
Supply, fixing, conveyance, installation, testing and commissioning of 25W LED Spike Light with COB LED light source,gray pure polyester powder-coated pressure die-cast aluminium housing for efficient thermal management, sturdiness and excellent corrosion resistance. The housing shall have IP66 protection, suitable for reliable outdoor applications, complete with driver, spike mounting arrangement, wiring, accessories, labour etc as required.Make havells(LYCUSSPS25WLED730PSYBOTG) jaquar or equivalent
Supply, conveyance, installation, testing and commissioning of 9W LED Mushroom bollard light light, Black color (Dimensions 145x87x43 mm) with IP65 directly on wall including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required. Philips /Jaquar make 9W model No. OBL-GRY-LBLDMSH009XW or Techno commercial equivalent.
SITC of LED Flood Light with a minimum system lumen of 4700 Lumen and system wattage not exceeding 35W with a nominal efficiency 130 lumen/watt .The Luminaire should be having Minimum 75000 Burning hours(L70B50) with CRI ≥70, SDCM< 5 and co-related color temperature (CCT) of 5700K. The housing should be of Single piece non-corrosive ADC12Grade high-pressure die-cast aluminum and should have corrosion resistant coating to pass Natural salt spray test of 500 Hrs with IP66 Protection. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs , should have an auto shutdown at 325V and have an auto recovery feature , Under Voltage protection with Input Voltage Stress of 100V for 48 Hrs, PF > 0.95 and THD<10 %.The Luminaire should have a 10 KV SPD duly bolted in the Luminaire,SPD should be able to sustain a minimum 15 hits of 10KV rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2 .The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire,PF>0.95 and THD<10% . Luminaire and driver shall be separately BIS approved of same make equivalent to Philips BVP120 LED047 CW NB FG A1 PSU GR/ kesslec /Osram. LM80,LM79 ,Type Test certificate and Bis certificate need to be submitted.
Supply, installation, testing, and commissioning of a 15W Disc LED Bollard luminaire with a rated input wattage of 15 W ± 10%, operating at 220–240 V AC, 50 Hz, with a luminous flux of 750 lm and luminaire efficacy of 50 lm/W as per BIS standards. The luminaire shall have a correlated color temperature (CCT) of 3000 K ± tolerance per ANSI, color rendering index (CRI) greater than 80 Ra, and an asymmetric beam angle. It shall be constructed from die-cast aluminium housing with matt grey powder coating, fitted with an opal white polycarbonate diffuser and polycarbonate reflector. The LED driver efficiency shall be ≥85%, with a rated LED lifespan exceeding 50,000 hours at L70. Protection features include overvoltage withstand up to 360 VAC for 2 hours, 2.5 KV surge protection, IP65 ingress protection, IK07 impact rating, and short circuit, open circuit, and reverse polarity protections.make Jaquar Model No. OBL-GRY-LBLD20X015XW/philips/equivalent
Supply, installation, testing, and commissioning of a 45 W single arm bracket post LED luminaire operating at a voltage range of 140 V to 270 V, rated voltage 240 V, power factor > 0.9,THD< 10%, and driver efficiency > 85%, high-power SMD LEDs with luminous efficacy > 90 lm/W at 5700 K correlated color temperature,CCT 3000K and a CRI> 70 Ra. The fixture include a acrylic diffuser with dimensions approximately dimension 510 mm X 560 mm and housing made of powder-coated spun and die-cast aluminium with IP65 ingress protection, 5 kV surge protection, and IK07 impact resistance.light mounting suspended type with a 3/4" BSP socket or pin-type pipe outlet.make Jaquar(mini sentinel -OGL_BL-SLMSNLSUCD45WWT3)/philips/equivalent (Annexure-III)
Supply and installation of a single arm decorative bracket on the existing pole, including all required mounting hardware, clamps, bolts, brackets, and accessories to ensure proper alignment and secure fixing. The work shall include drilling, fabrication adjustments (if required), surface finishing, and making good any damages to the existing pole to complete the installation as directed.Make Jaquar (OPO-BLK-POLBKTS04SA7501M)/philips/equivalent. (Annexure-IV)
Fabrication, design, supply, installation, testing, and commissioning (SITC) of a dust-, weather-, and vermin-proof outdoor panel with hinged door, conforming to IS and IE rules, made of 14-gauge galvanised sheet with powder-coated finish, with provision to house 1 no. 3-phase 4-way vertical distribution board (DB) and 1 no. Sintex box containing 1× 4P contactor and 1× 2P timer. The work includes all cable glands, connectors, internal wiring, earthing studs, mounting brackets, fasteners, sealing gaskets, cable entry provisions, and all associated civil work for mounting, foundations, and supports. (Site visit is recommended)
Supply and installation of suitable-size Sintex box(IP-rated) with provision to accommodate 4-way contactor and 2-way timer, including mounting inside the existing outdoor panel box, complete with interconnection,din rail for fixing the contactor and timer, and cable entry provision etc. as required
Design, providing, supplying, installation, testing and commissioning of LED Wall Washer luminaires (36 Nos.), each of 18 Watt, operating on DC 24 Volt, with CCT 3000 K, fitted with high-performance optics of 10°, 20°, 40°, 60° and 10° × 20°, having minimum luminous efficacy of 80 lumens per watt, CRI greater than 80 and SDCM less than 5 for uniform colour consistency, complete with 1000 mm long luminaires, IP66 ingress protection and IK06 impact resistance, suitable for outdoor architectural lighting, capable of operation from –10°C to +50°C, with On-Off control. The item shall include supply, installation, testing and commissioning of 4 numbers compatible 200 Watt constant-voltage power supplies with input AC 100–200 V and output DC 24 V, IP67 protected, installed in 4 numbers outdoor-rated driver boxes with provisions for cable entry and exit, complete with 50 metres of flexible copper cable 3C × 2.5 sq.mm, 50 metres of flexible copper cable 2C × 2.5 sq.mm for power and control wiring, 30 metres of 25 mm PVC conduit for routing and mechanical protection of cables, and 20 numbers IP-rated straight and T-type connectors in 3-pin / 5-pin configuration for secure interconnection of luminaires and drivers, including fixing arrangements, cable termination, testing and commissioning, complete in all respects as required.Make jaquar: Jaquar(Wall washer FLG-GRY-LORD0182062619OV,Wall washer -drive(AFD-WHT-FLPSMWXLG200)/philips/equivalent(site visit recommeded)
Labelling of DB/Main Panel/hensel Box with adhesive plastic coated printed labels (3 to 6 letters, maximum 25sq.cm. size) necessory arrangement for fixing on exixting DB/switch board etc. as required.
Electrical Schematic drawing in Autocad and pdf format along with physical copy of the same for Electrical inspectorate approval (along with seal,signature and license details of B class contractor) and complete assistance in obtaining the necessary approval from the Electrical inspectorate, ensuring that all compliance requirements and procedures are properly followed etc as required.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of up to 35 sq.mm size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.