Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAdmitted-Finance | ₹1.8 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.9 Cr+₹3.8 L (2.08%)Admitted-Finance 245 2 RAJPUR ROAD OPPOSITE HOTEL MADHUBAN DEHRADUN | ₹1.9 Cr+₹3.8 L (2.08%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Modern Electric Company L2 | SAINKO SYSTEMS L1 |
|---|---|---|---|---|---|
| 1.00 | 11KV SINGLE PANEL HT VCB (INDOOR) - ONE INCOMER CUM OUTGOING IN IP-4X ENCLOSURE, Design, Manufacture and Supply of 1 Panel, 11 kV HT VCB Switch Board with Following Accessories :,Incoming 630A, 11kV, 350MVA for 3 Sec., TP, Horizontally isolated, horizontally drawout type, motorised spring charged, closing mechanism, motor voltage 230V AC, shunt tripping & Closing coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum Circuit Breaker(VCB) With Mechanical & Electrical OFF/ON Indicators & Provided with Following - 1 No.,CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 110_/5/5A ratio - 3 Nos.IDMT relay with 3 elements for over current (50-200%) and 1 element for earth fault protection(10-40%). - 1 Set,Anti Pumping Relay - 1 Set,Master Trip Relay - 1 Set,Trip circuit supervision relay - 1 Set,Potential Transformers, 3 Phase, 3 Limb, Drawout Type, Resin Cast 11000/(Root 3)/110/(Root 3) Ratio Class 1 Accuracy, 100 VA Burden, with HV fuse on primary side and MCB / MPCB on secondary side. - 1 Set,6 Windows Annunciator with Hooter - 1 Set,1 Window for over current trip - 1 Set,1 Window for earth fault trip - 1 Set,1 Window for master trip relay - 1 Set,1 Window for Emergency Stop Push Button - 1 Set,2 Windows Spare - 1 Set,Digital Ammeter with inbuilt selector switch - 1 Set,Digital Voltmeter with inbuilt selector switch - 1 Set A set of breaker ON/OFF/Trip/DC control supply healthy/Trip circuit healthy/ Spring Charged VCB in test / VCB in service & R,Y,B phase indication lamps. - 1 Set,Emergency stop push button - 1 Set,Limit switches with 4 NO/ 4 NC breaker auxiliary contacts - 1 Set,Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. - 1 Set,All control wiring with protection & test terminal block as required. - 1 Set,Strip heater with thermostat for moisture absorption. - 1 Set,Suitable for connection to 3C x 240 sq.mm. Cross linked polythelene(XLPE) 11kV cables or as called for. - 1 Set,Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set,HT Danger Plate - 1 Set,Incoming as described above. 1 Sets,Powerpack as Required to Be Included (220V/24V DC), 7AH Battery for Each Breaker Module.SINGLE PANEL 11KV HT VCB PANEL AS DESCRIBED ABOVE | 1 | SET | 5,37,000 ₹5,37,000 | 5,35,000 ₹5,35,000 Lowest |
| 2.00 | 11KV TRANSFORMER (11 KV /0.433 KV) (500 KVA),Supply Installtion, Testing and commissioning of outdoor OIL cooled Outdoor Type Transformer 11 KV / 433 Volt Rating 3 phase, Double Wound with copper Winding. (as per IS : 1180 (part 1) : 2014 Level 1 (AMENDMENT 4)/ Equivalent IEC Standard , OLTC in Steps (+10% to -15% @ 1.5%), Insulation Class : Class A , Temperature Rise : 40 Deg.c in Oil , 45 deg.c by Resistance, 50 deg.c by Ambient , Dyn 11 Vector Group and other Standard Accessories as Required Including Followings : PLEASE NOTE THE TRASNFOREMR SHALL BE IN COMPLINACE WITH NEW REGUALTION IS 1180 or Equivalent IEC Standard FOR LOSSES AND EFFICIENCY and ammended upto date,Civil work shall be paid extra as per actual.Cable Termination box with disconnecting facility for 11 KV 3C-240 sq mm XLPE cable at 11 KV side ,ON Load Tap Changer on HV side +10% to -15% @ 1.5%.,Standard Fittings , Accessories /Spares :-Rating and Terminal Marking Plate - 1,Earthing Terminals - 2,Lifting Lugs - 2,Drain Valve with Blanking Plate - 1,Filter Valve with Blanking Plate - 1,Conservator - 1,Conservator Oil Filling Hole With Cap - 1,Oil Level Indicator with Min. Marking - 1,Dehydrating Breather - 1,Conservator Drain Plug - 1,Air Release Device - 1,Pressure Relief Valve - 1,Thermometer Pocket - 1,Rollers Bi directional - 4,Radiators Detachable - 4,HV Cable Box with disconnecting chamber - 1,LT Cable Box - 1,Seperate Neutral Terminal - 1,ON Load Tap Changer - 1,OTI with alarm and trip contacts,Buchholz relay with alarm & trip contact,Current Transformer,Radiator Valve,Marshalling Box,WTI with alarm & trip contact,WTI Pocket,MOG with LOLA Contacts,Buchholz relay with shut off valve,Jacking Pads,Drain Valve with Blanking Plate (OLTC),Filter Valve with Blanking Plate (OLTC),OLTC Surge Relay,RTCC Indoor,AVR,500 KVA (11/433V) AS DESCRIBE ABOVE | 1 | SET | 24,85,000 ₹24,85,000 | 24,70,000 ₹24,70,000 Lowest |
| 3.00 | DIESEL GENERATOR SET - 200 KVA DG SET :-Supply, intastallation, Testing & Commissioning of 200 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 200 KVA DG Set as per standards of Engine manufacture and as per latest CPCB Noms follow,provision of conrol cable from engine to control panel to engine. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge. | 1 | SET | 36,50,000 ₹36,50,000 | 36,45,000 ₹36,45,000 Lowest |
| 4.00Diesel Engine (CPCB-4 NORMS COMPLANT or as per latest) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 160 KW Having Following Arrangement :-Flywheel With Starter Ring for Generating Set,Air Filter , Lube Oil Cooler Assembly with Accessories,Exhaust Air Manifold,Exhaust Bellow,Fuel Fiter,Diesel engine pre heating arrangement,Lube Oil Filter,Exhaust Gas Turbo Charger with After Coller,Day Tank For fuel with Markings,ECP Panel mounted on a Separate Frame,Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump,12V Electrical Starting System with Starter Motor and Battery Charging Alternator,Engine Mounting Supports,ALTERNATOR Rated at 200 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification,Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).Excitation: Self Excited - Self Regulated.Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.Vibration: Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.Enclosure: Screen protected drip proof enclosure with IP – 23 degree of protection.Cooling: Air Cooled type with radial fan mounted on Rotor.Winding and Insulation: Insulation class H as defined in IEC – 60034-1 | |||||
| 5.00ACCESSORIES :-MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.2 Nos 12 Volts DC Battery of SUITABLE Capacity with Leads.1 Set of AVM Pads Fitted in Base Frame. | |||||
| 6.00 | Supply, intastallation, Testing & Commissioning of 125 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 125 KVA DG Set as per standards of Engine manufacture, provision of conrol cable from engine to control panel to engine as per latest CPCB Noms follow. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge. | 1 | SET | 24,25,000 ₹24,25,000 | 24,15,000 ₹24,15,000 Lowest |
| 7.00Diesel Engine (CPCB-4 NORMS COMPLANT or as per latest) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 100 KW Having Following Arrangement :-Flywheel With Starter Ring for Generating Set,Air Filter , Lube Oil Cooler Assembly with Accessories.Exhaust Air Manifold,Exhaust Bellow,Fuel Fiter,Diesel engine pre heating arrangement,Lube Oil Filter,Exhaust Gas Turbo Charger with After Coller,Day Tank For fuel with Markings,ECP Panel mounted on a Separate Frame.Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump,12V Electrical Starting System with Starter Motor and Battery Charging Alternator,Engine Mounting Supports,ALTERNATOR Rated at 125 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification,Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).Excitation: Self Excited - Self Regulated.Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.Vibration : Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.Enclosure : Screen protected drip proof enclosure with IP – 23 degree of protection.Cooling: Air Cooled type with radial fan mounted on Rotor.Winding and Insulation: Insulation class H as defined in IEC – 60034-1. | |||||
| 8.00ACCESSORIES :-MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.2 Nos 12 Volts DC Battery of SUITABLE Capacity with Leads.1 Set of AVM Pads Fitted in Base Frame. | |||||
| 9.00DG ACCESSORIES:- | |||||
| 10.00 | Supplying,installation,testing & commissioning of 'B' Class MS Pipe exhaust piping / chimney up to top level made out of suitable dia M.S piping complete with bends, duly painted with primer and insulated with 50 mm thick layer of LRB rock wool having 100 kg / m density, white wool. Finishing of the insulation shall be with chicken wire mesh and 26 kg.Aluminium sheet cladding all around exhaust pipe provided with self tapping screws complete as required. . 150 mm Dia Pipe - 4.85 mm Thickness | 30 | MTR | 1,010 ₹30,300 | 1,000 ₹30,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹3.7 L
Closing Date
19 Apr 2025, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
External Electrification works of Non Residential and Residential Buildings for District Jail at Champawat
2025_BRID3_82491_2
755/BRIDCUL/980/1/25 Dated 04.04.2025
Open Tender
Electrical Works
Item Rate
540 days
Champawat
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹3.7 L
BRIDCUL Dehradun
22 Apr 2025
7 Apr 2025
19 Apr 2025
7 Apr 2025
19 Apr 2025
11 Apr 2025
10 Apr 2025
Amount
11KV TRANSFORMER (11 KV /0.433 KV) (500 KVA),Supply Installtion, Testing and commissioning of outdoor OIL cooled Outdoor Type Transformer 11 KV / 433 Volt Rating 3 phase, Double Wound with copper Winding. (as per IS : 1180 (part 1) : 2014 Level 1 (AMENDMENT 4)/ Equivalent IEC Standard , OLTC in Steps (+10% to -15% @ 1.5%), Insulation Class : Class A , Temperature Rise : 40 Deg.c in Oil , 45 deg.c by Resistance, 50 deg.c by Ambient , Dyn 11 Vector Group and other Standard Accessories as Required Including Followings : PLEASE NOTE THE TRASNFOREMR SHALL BE IN COMPLINACE WITH NEW REGUALTION IS 1180 or Equivalent IEC Standard FOR LOSSES AND EFFICIENCY and ammended upto date,Civil work shall be paid extra as per actual.Cable Termination box with disconnecting facility for 11 KV 3C-240 sq mm XLPE cable at 11 KV side ,ON Load Tap Changer on HV side +10% to -15% @ 1.5%.,Standard Fittings , Accessories /Spares :-Rating and Terminal Marking Plate - 1,Earthing Terminals - 2,Lifting Lugs - 2,Drain Valve with Blanking Plate - 1,Filter Valve with Blanking Plate - 1,Conservator - 1,Conservator Oil Filling Hole With Cap - 1,Oil Level Indicator with Min. Marking - 1,Dehydrating Breather - 1,Conservator Drain Plug - 1,Air Release Device - 1,Pressure Relief Valve - 1,Thermometer Pocket - 1,Rollers Bi directional - 4,Radiators Detachable - 4,HV Cable Box with disconnecting chamber - 1,LT Cable Box - 1,Seperate Neutral Terminal - 1,ON Load Tap Changer - 1,OTI with alarm and trip contacts,Buchholz relay with alarm & trip contact,Current Transformer,Radiator Valve,Marshalling Box,WTI with alarm & trip contact,WTI Pocket,MOG with LOLA Contacts,Buchholz relay with shut off valve,Jacking Pads,Drain Valve with Blanking Plate (OLTC),Filter Valve with Blanking Plate (OLTC),OLTC Surge Relay,RTCC Indoor,AVR,500 KVA (11/433V) AS DESCRIBE ABOVE
DIESEL GENERATOR SET - 200 KVA DG SET :-Supply, intastallation, Testing & Commissioning of 200 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 200 KVA DG Set as per standards of Engine manufacture and as per latest CPCB Noms follow,provision of conrol cable from engine to control panel to engine. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge.
Diesel Engine (CPCB-4 NORMS COMPLANT or as per latest) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 160 KW Having Following Arrangement :-Flywheel With Starter Ring for Generating Set,Air Filter , Lube Oil Cooler Assembly with Accessories,Exhaust Air Manifold,Exhaust Bellow,Fuel Fiter,Diesel engine pre heating arrangement,Lube Oil Filter,Exhaust Gas Turbo Charger with After Coller,Day Tank For fuel with Markings,ECP Panel mounted on a Separate Frame,Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump,12V Electrical Starting System with Starter Motor and Battery Charging Alternator,Engine Mounting Supports,ALTERNATOR Rated at 200 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification,Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).Excitation: Self Excited - Self Regulated.Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.Vibration: Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.Enclosure: Screen protected drip proof enclosure with IP – 23 degree of protection.Cooling: Air Cooled type with radial fan mounted on Rotor.Winding and Insulation: Insulation class H as defined in IEC – 60034-1
ACCESSORIES :-MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.2 Nos 12 Volts DC Battery of SUITABLE Capacity with Leads.1 Set of AVM Pads Fitted in Base Frame.
Supply, intastallation, Testing & Commissioning of 125 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 125 KVA DG Set as per standards of Engine manufacture, provision of conrol cable from engine to control panel to engine as per latest CPCB Noms follow. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge.
Diesel Engine (CPCB-4 NORMS COMPLANT or as per latest) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 100 KW Having Following Arrangement :-Flywheel With Starter Ring for Generating Set,Air Filter , Lube Oil Cooler Assembly with Accessories.Exhaust Air Manifold,Exhaust Bellow,Fuel Fiter,Diesel engine pre heating arrangement,Lube Oil Filter,Exhaust Gas Turbo Charger with After Coller,Day Tank For fuel with Markings,ECP Panel mounted on a Separate Frame.Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump,12V Electrical Starting System with Starter Motor and Battery Charging Alternator,Engine Mounting Supports,ALTERNATOR Rated at 125 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification,Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).Excitation: Self Excited - Self Regulated.Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.Vibration : Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.Enclosure : Screen protected drip proof enclosure with IP – 23 degree of protection.Cooling: Air Cooled type with radial fan mounted on Rotor.Winding and Insulation: Insulation class H as defined in IEC – 60034-1.
ACCESSORIES :-MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.2 Nos 12 Volts DC Battery of SUITABLE Capacity with Leads.1 Set of AVM Pads Fitted in Base Frame.
DG ACCESSORIES:-
Supplying,installation,testing & commissioning of 'B' Class MS Pipe exhaust piping / chimney up to top level made out of suitable dia M.S piping complete with bends, duly painted with primer and insulated with 50 mm thick layer of LRB rock wool having 100 kg / m density, white wool. Finishing of the insulation shall be with chicken wire mesh and 26 kg.Aluminium sheet cladding all around exhaust pipe provided with self tapping screws complete as required. . 150 mm Dia Pipe - 4.85 mm Thickness
Supplying,installation,testing & commissioning of 'B' Class MS Pipe exhaust piping / chimney up to top level made out of suitable dia M.S piping complete with bends, duly painted with primer and insulated with 50 mm thick layer of LRB rock wool having 100 kg / m density, white wool. Finishing of the insulation shall be with chicken wire mesh and 26 kg.Aluminium sheet cladding all around exhaust pipe provided with self tapping screws complete as required. 250 mm Dia Pipe - 4.85 mm Thickness
Supply & Fixing of 75mm Thick Compressed Mineral Wool Insulation for DG Exhaust Pipe With 24 Gauge Aluminium Sheet Cladding etc as Required for The Under Mentioned Dia Pipe .150 mm Dia Pipe (Insulation)
Supply & Fixing of 75mm Thick Compressed Mineral Wool Insulation for DG Exhaust Pipe With 24 Gauge Aluminium Sheet Cladding etc as Required for The Under Mentioned Dia Pipe.250 mm Dia Pipe (Insulation)
Supply of SS Bellow.
MAIN LT PANEL.Suppy , installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 2mm CRCA sheet steel fabricated cubical type Main L.T. Panel (totally type test assembled-TTA) floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, As per IEC 61439 after proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641. NOTE:- MCCB's Wherever Specified shall have Rotary Handle.
(Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers).
Degree of protection IP-42
The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCB's.
Colour: Siemens Gray Powder Coated or as per approved shade.
INCOMER 1 FROM 500 KVA OUTDOOR TRANSFORMER
1 Nos. 800 amps Four Pole ACB of Fault Breaking Capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated Position Indicator and Frame Earthing Contact ,Confiming to IS 13947-2 1993 as Amended upto Date Complete with Following Accessories.
1 set of 3 CT's of ratio 800/5A, Class 1.0 accuracy 15 VA burden for APFCR.
Independent manual spring closing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set .
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required.
Shunt trip coil 220 Volt AC.
INCOMER 2 FROM DG SET (200 KVA) - 1 Nos
1 Nos 400 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-2 1993 as amended upto date complete With Following Accessories.
1 set of 3 CT's of ratio 400/5A, Class 1.0
Independent manual spring closing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set .
Protection releases with LSIG and Over voltage ,under voltage,Reverse power protection Relay & Metering & Accessories for each D G set incomers
3 Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required .
Shunt trip coil 220 Volt AC.
1 nos battery charger with DC voltmeter and ammeter suitable for the DG sets (200 KVA)
INCOMER 3 FROM DG SET (125 KVA) - 1 Nos
1 Nos 250 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu) fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-2 1993 as amended upto date complete With Following Accessories .
1 set of 3 CT's of ratio 250/5A, Class 1.0
Independent manual spring closing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set .
Protection releases with LSIG and Over voltage ,under voltage,Reverse power protection Relay & Metering & Accessories for each D G set incomers
3 Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required .
Shunt trip coil 220 Volt AC.
1 nos battery charger with DC voltmeter and ammeter suitable for the DG sets (125 KVA)
INTERLOCKING
Interlocking logic electrical Interlocking between incomers and bus coupler and it should have auto start and auto trip facility for Automatic Operation of The Breakers WITH MANUAL OVER RID FACILITY
BUS COUPLER
One Number 800A 50KA 4 pole ACB as Bus Coupler with ON/OFF Indication.
BUS BAR
1000 A TPN Aluminium bus bar with heat Shrink Sleeve
OUTGOINGs
ALL THE MCCB'S SHALL BE EQUIPPED/ PROVIDED WITH ALL ACCESSORIES & IN BUILT PROTECTION RELEASES
1 Nos. 500 AMPS TP MCCB (Capacitor Panel)
1 No. 400A 50KA 4P MCCB (SPARE)
1 No. 200A 50KA 4P MCCB (SPARE)
1 No. 160A 50KA 4P MCCB (SPARE)
2 No. 125A 50KA 4P MCCB (SPARE)
1 No. 100A 50KA 4P MCCB (SPARE)
Other items such as
1 set of control wiring
1 Set of designation plates
NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as per the current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge, 3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode.
Complete Panel as Above and complete
AUTOMATIC POWER FACTOR CORRECTION PANEL (CAPACITOR PANEL) - 175 KVAR-Supplying, Installation, Testing and Commissioning of cubicle type capacitior panel suitable for 415 & 3 phase 50 HZ A.C. supply System fabricated in compartmentalised design from CRCA Sheet Steel of 2 mm thick for frame work and cover, 3 mm thick for gland plates i/c powder coating in approve shade having 500 AMP capacity TPN Aluminium bus bar DMC/SMC bus bar supprot entire pannel should have common Al. earth bar for size 50 mm x 5 mm i/c Providing & fixing following switch gear mounting there on fans,grills for propor ventillation complete with gaskets & inner connection i/c connection with existing CTS in the main CT Panel complete as reqd. The panel board shall be of dust and verm proof with degree of protection IP 42) .a) 500 Amps TP MCCB with Microprocessor Based release and E/F proctection with time dely (Ics=100% Icu) - 1 No.(b) 500A, 4 strip Tinned Aluminium busbar -1 Set,(c) Micro processor based automatic Power factor control relay i/c power factor metre in 8 steps,(d) Multi functional meters with suitable CTS and protection MCBS 1 set.(e) 3 Nos. Phase indieating right (lamp) with MCBs protection.
OUTGOINGS -
complete panel as above and complete
FEEDER PILLAR 1-Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. INCOMER : 125 AMP FP MCCB , BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 1 No 63 AMP 4P MCB,3 No 100 AMP 4P MCCB,1 No 100 AMP 4P MCCB (Spare),1 No 63 AMP 4P MCB (Spare),complete panel as above and complete
FEEDER PILLAR 2-Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. INCOMER : 125 AMP FP MCCB, BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 3 No 40 AMP DP MCB,2 No 100 AMP 4P MCCB,1 No 100 AMP 4P MCCB (Spare).2 No 63 AMP 4P MCB (Spare),complete panel as above and complete
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 240 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 185 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 150 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 120 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.,3.5 C X 95 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.,3.5 C X 70 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 50 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 35 Sq.mm Al. XLPE arm.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 25 Sq.mm Al. XLPE arm.
LT CABLE LAYING
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Upto 35 sq. mm
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Above 35 sq. mm and upto 95 sq. mm
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Above 95 sq. mm and upto 185 sq. mm
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Above 185 sq. mm and upto 400 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 25 sq. mm (28mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 35 sq. mm (32mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 50 sq. mm (35mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. 3½ X 70 sq. mm (38mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. 3½ X 95 sq. mm (45mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 120 sq. mm (45mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 150 sq. mm (50mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 185 sq. mm (57mm)
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.3½ X 240 sq. mm (62mm)
Supply & Testing of following 11 KV( UE) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required.3 C x 240 Sq. mm 11 KV (UE)
H V CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
H.T Termination
Supply and making Indoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required.3 C x 240 Sq.mm
Supply and making Outdoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required.3 C x 240 Sq.mm
Supply and Making Straight Through Cable Jointing With Cast Resin Compund, Including Ferrule & Other Jointing Materials for Following Size of 3 core, XLPE Aluminium conductor cable of 11KV grade as required.3 C x 240 Sq.mm
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single Red colour on front side as required.
SITC of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board with supply of all material labour T & P etc for proper completion of work. (Approx front area = 1.20 sq M)
SITC of First aid box as approved by Indian red cross conforming to IS : 2217.
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked
SITC of ABC FIRE EXTINGUISHER 4 KG capacity complete in all respect ISI : 15683 marked
SITC of Fire Bucket stand made of M S angle suitable for and with 4 Nos Fire Buckets of 9.5 Ltrs capacity
SITC of of rubber gloves of 11 KV grade as per IS : 4770.
SITC of cable route marker
SITC of ANTI SKID RUBBER MAT 1 mtr x 2 mtr. 3mm thick ISI - 15652 marked
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.. (BODY EARTHING)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.. (NEUTRAL EARTHING)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Providing and fixing of lightning conductor finial, made of 25mm dia 300mm long, G.I tube, having single prong at top with 85mm dia 6mm thick G.I base plate including holes etc. complete as required.
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for horizontal run)
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for vertical run)
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
RCC Hume pipes
Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete .250 mm dia
Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete .300 mm dia
Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete .100 mm dia
Manholes
Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 200 mm dia (OD-200 mm & ID-175 mm nominal)
CABLE TRAYS
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement).150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement).300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement).450 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement) .600 mm width X 50 mm depth X 2.0 mm thickness
POLE ERECTION
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 4.5 metre and upto 6.5 metre
Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape , Hole Seeling to be done complete as required.. 32 mm dia
EXTERNAL LIGHTING SYSTEM
Supply , Installation, Testing & Commissioning of 50 W LED with complete with pot optic reflector connection with 3 x 2.5sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required.
Supply, Installation, Testing and Commissioning of 200x160x70 Polycarbonate thermoplastics enclosure - junction box with I.P - 66 Protection.
Supplying of ADP Octagonal Pole Single Arm 6 m ADP, Material of Octagonal pole : Grade ISH430LA as perIS:5986:2017 latest, Base plate material : Grade: E250, Quality:BR(as per IS:2062:2011 latest).
Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing laid in ground including cost of digging upto required depth, 150 mm sand all around the cable, brick protection and back filling, clamped to wall with suitable clamps including saddles fixing bolts, Connection Testing and commissioning as Required..2x6 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering. Upto 35 sq. mm
Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing trenches/pipes, cable trays, ducts, clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning as Required. 2x6 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 core 2.5 sq.mm (for Poles)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
Modern Electric Company (BID ID -375253)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .