Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹76.9 CrAccepted-AOC | ₹76.9 Cr Quoted ₹77.2 Cr | L-1 | Accepted-AOC As per AOC |
| 2 | L-2₹78.9 CrRejected-Finance | ₹78.9 Cr | L-2 | Rejected-Finance Other than L-1 Bidder |
| 3 | L-3₹86.2 CrRejected-Finance | ₹86.2 Cr | L-3 | Rejected-Finance Other than L-1 Bidder |
| 4 | L-4₹86.6 CrRejected-Finance F 18 ANSAL COMPLEX OPP JWALA HARI MARKET PASCHIM VIHAR NEW DELHI 110063 | NEW DELHI | WEST DELHI | DELHI | 110063 | ₹86.6 Cr | L-4 | Rejected-Finance Other than L-1 Bidder |
| 5 | L-5₹89.2 CrRejected-Finance | ₹89.2 Cr | L-5 | Rejected-Finance Other than L-1 Bidder |
Tender Value
Refer Docs
EMD Value
₹15 L
Closing Date
19 Jul 2021, 6:00 pmClosed
HQ CE SILIGURI ZONE
HQ CE SILIGURI ZONE, PO SALUGARA, DIST JALPAIGURI, PIN 734008 WEST BENGAL
PROVN OF TECH AND OTM ACCN (PH-III) FOR BH AT TEZPUR UNDER GE (S) TEZPUR
2021_MES_420149_1
98706/TEZ(S)/SZ/E8
Open Tender
Civil Works
1274 days
TEZPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,000
GE (S) TEZPUR
₹15 L
Yes
HQ CE SILIGURI ZONE
29 Sept 2021
8 Feb 2021
22 Jul 2021
8 Feb 2021
19 Jul 2021
10 Jul 2021
8 Feb 2021 - 25 Feb 2021
9 Mar 2021
Amount
BUILDING AND STRUCTURE (Sch 'A' PART-I)
Lump sum price worked out by the Contractor for “BUILDING AND STRUCTURE” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 37,74,75,000.00 inserted by the MES in Schedule ‘A’ Part-I.
EXCAVATION & EARTHWORK FOR SITE CLEARANCE AND AREA DEVELOPMENT, OTHER SCHEDULES (EXCEPT SCH 'A' PART-I) (Sch 'A' PART-II)
Lump sum price worked out by the Contractor for “EXCAVATION & EARTHWORK FOR SITE CLEARANCE AND AREA DEVELOPMENT, OTHER SCHEDULES (EXCEPT SCH 'A' PART-I)” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 20,14,340.87 inserted by the MES in Schedule ‘A’ Part-II.
INTERNAL WATER SUPPLY (Sch 'A' PART-III)
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY (Sch 'A' PART-III)” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,82,543.00 inserted by the MES in Schedule ‘A’ Part-III.
INTERNAL WATER SUPPLY (Sch 'A' Part-III (A) (MISC))
S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 20 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed.
S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 25 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed.
S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 40 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed.
S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 50 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed.
NOTE FOR SERIAL ITEM No. 4.01 TO 4.04 : CPVC pipes from service tanks to toilets at outside surface of building shall be fixed on surface of wall and inside the building shall be concealed.
S&F of shower rose cast copper alloy chromium plated 125 mm size with swivel joint for fixing to 15 mm bore GI pipe or union including GI pipe 15 mm, 300 mm long with each shower complete all as specified and as directed.
S&F of CP brass wall mixer hot and cold water screwed down for iron pipe of size 15 mm dia with 115 mm long bend pipe for connecting to overhead shower with bush and piston diverter fitting with aereter complete all as specified and as directed.
S&F of brass non return valve screwed down for iron / CPVC pipe of size 15 mm dia medium weight complete all as specified and as directed. Note :- 1. Pillar cocks for wash hand basins shall be part of Lumpsum of building. 2. As per drawing No. ADG/2016/EM/012 Sheet No. 49/54 to 51/40 the GI pipe 80 mm as outlet to service tank has been shown as horizontal on terrace and vertical on wall and further branches of CPVC 50 mm has been shown for each floor. However, for effective distribution of water supply to each floor the GI pipe 80 mm shall be provided horizontal on terrace only and further CPVC pipe of 50 mm shall be provided vertically on wall from GI pipe 80 mm on terrace separate for each floor. Gate valves 40 mm to be provided on CPVC pipe 50 mm to be provided on terrace for controlling water supply of each floor.
S&F of Gun Metal Gate Valve of size 80 mm dia with iron wheel head, screwed both ends for iron pipes or for unions fixed complete all as specified and as directed.
S&F brass CP basin mixture 15 mm bore for mixing hot and cold water screwed down complete all as specified and as directed.
Sub total
INTERNAL ELECTRIFICATION (Sch 'A' PART-IV)
Lump sum price worked out by the Contractor for “(INTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 26,47,904.20 inserted by the MES in Schedule ‘A’ Part-IV.
INTERNAL ELECTRIFICATION (Sch 'A' PART-IV(A) (MISC))
(a) One light / fan point controlled by one , one way switch.
(b) One bell point controlled by one bell push.
(c) One socket outlet point 6 A on independent board.
(d) One socket outlet point 6 A on same board.
M&L for concealed point wiring with 4.0 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including stove enameled steel conduit of adequate size with all fittings and accessories including one run of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor of size 4.0 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one 16 Amp socket outlet on independent board complete all as specified and as directed. NOTE : Modular metal flush box and cover plate will be measured and paid separately.
BLANK
M&L for concealed flame proof point wiring with 2.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories including PTFE (Teaflon) type sealing proof joint complete including FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 2.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one light points controlled by one, one way flame proof switch complete all as specified and as directed.
S&F of switch flame proof rotary type with termination box in LM6, 16 Amp, Single Pole, 250 V complete all as specified and as directed.
M&L for concealed Sub main wiring with four run of 16.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 16 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
M&L for concealed Sub main wiring with four run of 10.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 10 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
M&L for concealed Sub main wiring with four run of 6.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB and for AC complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
M&L for concealed Sub main wiring with four run of 4.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 4.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
M&L for concealed Sub main wiring with two run of 6.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including one run of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB and for AC complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
M&L for concealed Sub main wiring with two run of 4.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including one run of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 4.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. NOTE : Connections of cables with MCBs or bus bars shall be done through appropriate size brass / copper thimbles.
S&F of MCB, DB, TPN, 4-ways (8 + 12 WAYS), DOUBLE DOOR, Horizontal type, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed.
S&F of MCB, DB, TPN, 8-ways (8 + 24 WAYS), DOUBLE DOOR, Horizontal type, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed.
S&F of MCB, DB, SPN, 8-ways, DOUBLE DOOR, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed.
S&F of RCBO 4 pole, 30 mA 63 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed.
S&F of RCBO 4 pole, 30 mA 32 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed.
S&F of RCBO 4 pole, 30 mA 20 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed.
S&F of RCBO 4 pole, 30 mA 16 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed.
S&F MCB, SPN rupturing capacity 10 kA, ‘C’ curve, 06-32 Amp, ISI marked complete all as specified and as directed.
S&F of MCB, rupturing capacity 10 kA, ‘C’ curve, Single Pole, 6 to 32 Amp, ISI marked, complete all as specified and as directed.
Supply, installation, testing and commissioning of Heavy Duty exhaust fan 300 mm sweep, 1400 RPM, Air Delivery not less than 1900 CMH, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint (if any) complete all as specified and as directed.
Supply, installation, testing and commissioning of Heavy Duty exhaust fan 380 mm sweep, 1400 RPM, Air Delivery not less than 4000 CMH, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint (if any) complete all as specified and as directed.
Supply, installation, testing and commissioning of exhaust fan with automatic back shutter louvers 300/305 mm sweep, FLAME PROOF type and 1440 RPM or more, Air Delivery not less than 1120 CFM, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint (if any) complete all as specified and as directed.
S&F, IP >=20, Class-I, LED light fitting 1 x 20 W (4 FT), CRI >=80, CCT - 6500 K, wall / surface mounted, integrated type, constructed of epoxy powder coated white extruded aluminium channel housing with integrated high efficiency electronic driver & surge suppressor of 2 KV or more, system lumens - 2200 Im, Electronic driver with lower THD (<15%) power factor >= 0.90, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 20 W (4 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F, IP >=20, Class-I, LED light fitting 1 x 40 W (4 FT), CRI >=80, CT>=5700 K, wall / surface mounted, integrated type, constructed of epoxy powder coated white extruded aluminium channel housing with integrated high efficiency electronic driver & surge suppressor of 2 KV or more,system lumens - 4100 Im, Electronic driver with lower THD (<10%) power factor >= 0.95, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 40 W (4 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F, IP >=20, Class-I, LED light fitting 1 x 10 W (2 FT), CRI >=80, CCT-6500 K, wall / surface mounted, integrated type, constructed of epoxy powder coated white extruded aluminium channel housing with integrated high efficiency electronic driver & surge suppressor of 2 KV or more,system lumens - 1050 Im, Electronic driver with lower THD (<10%) power factor >= 0.90, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 100 W (2 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F energy saving & environment friendly long life 25 W, CT >= 5700 K, LED building security light made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less tha IK-07 complete with integrated type, with high efficiency electronic driver, surge suppressor of 5 KV or more and high brightness LEDs, system lumens - 2550 Im, Electronic driver with lower THD (<10%), power factor >= 0.95 operating range – 140 to 270 V, 50 Hz complete including bracket made out of 40 mm dia light grade GI pipe duly fixed with MS clamps, nuts, bolts etc. including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F, IP 65, Class-I, energy saving, environment friendly, surface mounted, 10 W or next higher rating decorative Oval Bulk-Head edge-lit LED luminaire comprising of high brightness LEDs as light source with CRI >=80, CT>=6000 K integrated type with system lumens - 1000 Im, Electronic driver with lower THD (<10%) Power Factor >= 0.95, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F, IP 65, Class-I, energy saving, environment friendly, surface mounted, 10 W or next higher rating decorative Oval, FLAME PROOF Bulk-Head edge-lit LED luminaire comprising of high brightness LEDs as light source with CRI >=80, CT>=6000 K integrated type with luminaire efficacy >95 lumens/Watt, Power Factor >= 0.90, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F of Bed side Lamp fitting with suitable metal shed and lamp holder and LED lamp 10 W complete all as specified and as directed.
S&F, IP >= 20, Class-I, ceiling mounted, LED square shape slim ceiling light fitting 36 W or next higher rating CRI >=80, CCT - 6500 K, approx. dimensions 600 x 600 mm, integrated type with high efficiency electronic driver, surge suppressor of 2 KV or more and high brightness LEDs, system lumens - 4350 Im, Electronic driver with lower THD (<20%), Power Factor >= 0.95, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F Single pole and neutral Sheet Metal Enclosure (industrial socket) with a two pin and earth plug socket for AC complete with one single pole MCB 16 to 20 Amp, 240 V complete all as specified and as directed.
Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 V grade of size 35 Sqmm 3.5 core (Main LT Panel to each Floor panel for four lifts).
S&F of energy efficient (BLDC), AC 230 Volts, single phase, 26 Watt ceiling fan 1200 mm sweep BEE 5 star rated and suspended from fan hook including electrically connecting with three core PVC insulated of 0.75 Sqmm copper conductor cable from ceiling rose to ceiling fan including writing of MES Number 2.0 cm height with synthetic enamel paint complete all as specified and as directed.
Sub total
EXTERNAL WATER SUPPLY (Sch 'A' Part-V)
Lump sum price worked out by the Contractor for “(EXTERNAL WATER SUPPLY)” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 4,57,777.60 inserted by the MES in Schedule ‘A’ Part-V.
EXTERNAL WATER SUPPLY (Sch 'A' Part-V(A) (MISC))
Supply, jointing, testing and laying in trenches DI pipes with spigot and socket ends suitable for push on rubber joint centrifugally cast class K-7 for drinking water supply, inner side cement mortar lining and outer side black bitumen coating and any length of size 150 mm bore pipe and including push on rubber (EPDM) ring with ISI marked complete all as specified and as directed.
Supply, jointing, testing and laying in trenches DI pipes with spigot and socket ends suitable for push on rubber joint centrifugally cast class K-7 for drinking water supply, inner side cement mortar lining and outer side black bitumen coating and any length of size 100 mm bore pipe and including push on rubber ((EPDM)) ring with ISI marked complete all as specified and as directed.
M&L for DI specials / fittings confirming to IS:9523/2000 of size upto 150 mm bore suitable for DI pipes class K-12, PN-16, with inside cement mortar lining and black bitumen external coating such as bends (any type radius & angle) tapers, tee pieces, single branches, Y-junctions, double junctions, connecting pieces, nuts & bolts, gaskets, flanges including push on rubber joints etc complete all as specified and as directed.
Construction of brick masonry chamber with sub class ‘B’ brick in CM (1:6) with PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) for foundation of internal dimension of 100cm x 100cm x 100cm including 15 mm thick plastering in CM (1:4) inside the chamber and on the external portion exposed above ground level, including 3 mm thick MS cover welded around with MS flat iron of size 40x6 mm including MS angle iron frame of size 40x40x6mm with locking arrangement including painting with two coats of synthetic enamel paint over a coat of red oxide primer including necessary earth work in soft / loose soil well ramming of soil around the constructed chamber complete all as specified and as directed.
Construction of brick masonry chamber with sub class ‘B’ brick in CM (1:6) with PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) for foundation of internal dimension of 600mm x 600mm x 600mm including 15 mm thick plastering in CM (1:4) inside the chamber and on the external portion exposed above ground level, including 3 mm thick MS cover welded around with MS flat iron of size 40x6 mm including MS angle iron frame of size 40x40x6mm with locking arrangement including painting with two coats of synthetic enamel paint over a coat of red oxide primer including necessary earth work in soft / loose soil well ramming of soil around the constructed chamber complete all as specified and as directed.
S&F foot valve 100 mm bore, conforming to IS-4038 with 3mm thick rubber gasket with necessary bolts, nuts, washers, etc of suitable size complete all as specified and as directed.
Supply, installation, testing and commissioning centrifugal pump set 1200 LPM discharge capacity working at 35 mtrs head (Head range 30 to 40 mtr and discharge range as per manufacturer design), 2900 RPM, suitable for drinking water and coupled with 3 phase, 50 c/s, 415 V electric motor of suitable capacity including suction pipe, suitable capacity star delta starter with over load, dry run and single phase protection etc (Starter to be mounted on proposed water supply panel board considered separately) and PCC foundation with MS base frame as per manufacturer design including connecting up with suction and delivery main and suitable size of copper conductor etc, cable from starter to motor complete all as specified and as per manufacturer’s specification.
Supply, installation, testing and commissioning of disinfection chemical (Chlorine) dosing pump of suitable discharge consisting 100 Ltrs FRP tank with agitator complete all as specified and as directed.
BLANK
S&F of Aviation light yellow painted die cast aluminium alloy housing red coloured poly carbonate dome and accessories completed all as specified and as directed.
OUTGOING (a) MCCB 4 pole, 63 Amps, 50 Hz, 415 V, thermal magnetic release, Ics = 100% Icu, with rupturing cap 16 KA – 02 Nos. (b) MCB SPN 32 Amps, 10 KA, ‘C’ Series – 03 Nos. (c) Automatic Star Delta Starter for 25 HP motor – 02 Nos. (d) Single Phase / Over Load / Dry run preventors – 02 Sets.
Sub total
EXTERNAL ELECTRIFICATION (Sch 'A' PART-VI)
Lump sum price worked out by the Contractor for “(EXTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-VI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 19,78,971.60 inserted by the MES in Schedule ‘A’ Part-VI.
EXTERNAL ELECTRIFICATION (Sch 'A' PART-VI(A) (MISC))
Supply, installation, testing and commissioning of indoor type VCB panel board 11 KV 630 A, 3-Phase, 50 Hz AC supply system made of sheet metal duly painted (powder coated) totally enclosed free standing, floor mounted type with track mounted VCB horizontal / vertical isolation and horizontal draw out type, cubical should have not less than IP-43 Class degree of protection, copper bus bar, pre-wired for controller and accessories using copper conductor, suitable for side extension in both directions and provision for cable entry / outgoing system complete and comprising of the following :- INCOMING FEEDER PANEL = 01 No. OUTGOING TRANSFORMER FEEDER PANEL = 04 Nos. (A) Each Incoming Feeder should comprise of :- HT Vacuum Circuit Breaker Switchgear, Indoor type, dust and vermin proof, motorized as well as manually charged fully interlocked, horizontal draw out type, floor mounted, normal / highest working voltage – 11/12 KV, normal current – 630 A, 3-Phase, 50 HZ AC supply, Breaking capacity – 13.1 KA, Making capacity – 33 KA (p), insulation level KV(rms) / KV(p) -25/75, closing voltage – 110 V DC complete as per IS : 3427 & IS : 118 with all standards accessories and metering equipment and comprising the following :- (i) HT CT 100/50/5-5 (Dual Core), Class 5 P 10 for protection and Class 1.0 for metering, 15 VA burden, short time rating – 13.1 KA for 1 sec, having IS : 2705 marking, suitable for 12 KV – 03 Nos. Item Continued as 10.02
Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 630 KVA step down, BEE 5 Star rated (Energy Efficiency Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling hollow fins, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :- (a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete. (b) 01 No. cable end box on LT side consisting of 04 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Explosion vent with double diaphragm and sight glass. (e) Thermometer Pocket. (f) Two earthing terminal on tank body to facilitate fixing of 32 x 6 mm GI strip etc. Item Continued as 10.06
Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 200 KVA step down, BEE 5 Star rated (Energy Efficiency Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling hollow fins, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :- (a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete. (b) 01 No. cable end box on LT side consisting of 04 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Explosion vent with double diaphragm and sight glass. (e) Thermometer Pocket. Item Continued as 10.08
Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 100 KVA step down, BEE 5 Star rated (Energy Efficiency Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling hollow fins, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :- (a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete. (b) 01 No. cable end box on LT side consisting of 04 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Explosion vent with double diaphragm and sight glass. (e) Thermometer Pocket. (f) Two earthing terminal on tank body to facilitate fixing of 32 x 6 mm GI strip etc. Item Continued as 10.10
Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made, CPRI type tested of 250 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current rating of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :- (a) 600 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators. (b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 36 KA of rating 400 A -01 No. as incoming. Item continued as 10.12
Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made, CPRI type tested of 80 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current ranking of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :- (a) 200 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators. (b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 160 A -01 No. as incoming. (c) A set of heavy duty, capacitor heavy duty, type MDXL or any suitable type, 440 V with output capacity 80 KVAR, capacitor bank in 5 steps (1 x 5 KVAR + 2 x 12.5 KVAR + 2 x 25 KVAR) to accommodate all possible set of automatic operation to maintain 0.99 power factor. Item continued as 10.15
Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made CPRI type tested of 40 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current rating of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :- (a) 200 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators. (b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 80 A -01 No. as incoming Item continued as 10.18
S&F of energy saving and environment friendly long life 45 W or next higher available rating, CT>=5700 K, LED street light made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less than IK-07 complete with integrated type, with high efficiency electronic driver, built-in- surge suppressor / SPD of 10 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens/Watt, power factor >=0.90, operating range – 140 to 270 V, 50 Hz complete including suitable fixing arrangement made out of 40 mm dia GI Bracket, necessary MS clamps, nuts, bolts etc. complete all as specified and as directed.
S&F of factory fabricated (CPRI type tested) weather proof, dust and vermin proof street light junction box of size 250(L) x 250(B) x 150(D) mm (minimum dimensions) made up of 3.15 mm thick CRCA sheet, powder coated after preparation of surfaces comprising of 04 Nos. aluminium bus-bar of size 20 x 4 mm mounted on suitable size spacer insulators with provn of 01 No. MCB SP 6 Amps, 10 KA breaking capacity, ‘C’ Curve and two openings at the bottom and one opening at the top with cable glands and fixing with the help of suitable sized MS clamps to steel poles including complete all as specified and as directed.
Supply, laying, jointing and testing of XLPE insulated screened PVC bedded galvanized steel strip armoured, heavy duty electric power cable with stranded aluminium conductor 11000 V grade (Earthed), IS:7098 Part-II ISI marked, latest version, of size 3 Core 95 Sqmm laid in trench, ducts etc or fixed to poles with GI pipe and Fl clamps 50 mm x 5 mm, including nuts, bolts and washers complete all as specified and as directed. NOTE :- (a) The cost of clamps, nuts bolts and washers etc shall be included in this item without any extra cost. (b) Necessary earthwork, PCC etc shall be measured and paid separately under relevant items of work.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 400 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 240 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 120 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 95 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 50 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 25 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 16 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 10 Sqmm 2 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade, ISI marked with stranded aluminium conductor of size 6 Sqmm 2 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed.
Supply, erection, commissioning and testing of High Galvanized Mast Light 15 Meter High suitable for 06 Nos. 1 x 160 W LED Flood light and having three point suspension system with steel wire rope of 6 mm did and double drum winch with luminaire mounting arm, 01 No. LED type aviation obstruction light including lamp, lightning arrestor spike, power tools including lamp, lightning arrestor spike, power tools including cutting road / hard standing, excavation for RCC foundation complete with following and all as specified and as directed :- (a) High mast fabricated from steel plates conforming to BSEN-10025/IS:5986, cut and folded to from a polygonal section. Mast shall be in two sections for 16 mtr heights having only longitudinal weld conforming to BS-5135/AWS. The mast is to be provided with a fully penetrated flange which shall be free from any laminations or incursions. The welded connection of the base flange shall be fully developed to the strength of the entire section. The base flange shall be provided with supplementary gussets between bolt holes to ensure elimination of helical stress concentration. For environmental protection of the mast, the entire fabricated mast shall be Hot Dip Galvanized (As per IS:2629) internally and externally having uniform thickness of average 86 microns for bottom / top sections respectively and certificate from the OEM regarding the same to be submitted alongwith the PV and test certificates. (b) An adequate door opening shall be provided at the base of the mast. The opening shall be such that it permits clear access to equipment’s lich winch, cable, wire rope, plug and socket etc. and also facilitates easy removal of the winch for servicing. Item continued as 10.33
The door opening shall be complete with a close fitting vandal resistant allen key locking with provision for external lock. The door opening shall be carefully designed and reinforced with adequate steel section so that the mast section at the base is unaffected, and undue buckling of the cut portion is prevented under heavy wind condition. (c) Mast structure shall sustain as assumed maximum reaction arising from wind speed as per IS-875 (Part-3) 1987 (three seconds) which is measured at a height of 10 mtrs above ground level. (d) The high mast shall be provided with accessories which include a raising and lowering system (R&L), trailing cable, power tool, lighting finial and aviation obstruction warning light. (e) The wire ropes shall be of stainless steel grade AISI 304 with minimum 6 mm diameter and 7/19 construction. Its central cores shall be also SS and have a minimum breaking strength of 2400 Kgs. The power tool shall be integral type suitable for handling the total head load. It shall have a mechanical torque limiter to ensure safety and also a manual handle shall be provided. (f) Earthing 04 Nos. (02 for FP Box and 02 for High mast) complete with Galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below ground level with the top edge of the earth plate not less than 1.5 mtr below ground level and connected to galvanized iron earth lead strip 32 x 6 mm dia by means of bolts, nuts, check nuts and washer of Item continued as 10.34
galvanized iron including PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) precast RCC cover slab including one handle made out of 8 mm dia round bar embedded in precast slab and 20 mm bore medium grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil including Test Point complete all as shown in EP No. 3 of SSR Part-I and testing on completion complete all as specified and as directed. (g) Earthing 01 No. (for Surge protection device) complete with Galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below ground level with the top edge of the earth plate not less than 1.5 mtr below ground level and connected to galvanized iron wire 4 mm dia by means of bolts, nuts, check nuts, and washer of galvanized iron including PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) precast RCC cover slab including one handle made out of 8 mm dia round bar embedded in precast slab and 20 mm bore medium grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 15 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil complete all as shown in EP No. 3 of SSR Part-I and testing on completion complete all as specified and as directed. Item continued as 10.35
(h) The light luminaries shall be 9 Nos. 200 W LED, CT>=5700 K made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less than IK-07 complete with integrated type, with high efficiency electronic driver, surge suppressor 5 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens/Watt, power factor >=0.90, operating range – 140 to 270 V, 50 Hz complete including suitable fixing arrangement made out of 40 mm dia GI Bracket, necessary MS clamps, nuts, bolts etc. complete all as specified and as directed. (j) The aviation obstruction light shall be LED type with IP 65/66 protection and all as per the recommendations of the OEM complete. (k) LT feeder pillar box both side openable with projected globe roof for rain water protection, manufactured by a CPRI approve manufacturer dust and vermin proof, suitable for 440 V, 3-Phase, 4 wire system made out of 3.15 mm thick CRCA sheet of size as per OEM and built upon rigid frame work having front and rear hinged double shutter doors with neoprene rubber gasket, epoxy powder coated including danger plate, earthing strip point and ventilation louvers at rear side, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc. and embedded with 50 x 50 x 6 mm mild steel angle iron frame complete with PCC foundation in Cement Concrete (1:2:4) (using 20 mm graded stone aggregate) and testing after insulation complete all as specified and as directed :- Item continued as 10.36
Supply, installation, testing and commissioning of LT panel board, “indoor pedestal type” of size 1500 mm (height) x 1800 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved panel manufacturer (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-43 and general construction confirming to IS / IEC - 60947-2004, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 2.0 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary arrangements for pedestal mounting viz. PCC platform etc. complete all as specified and directed with and including the following accessories :- (MAIN PANEL FOR 630 KVA TRANSFORMER) BUS BAR AND INTERNAL CONNECTIONS :- The bus bars shall be made up of 04 Nos. tinned copper 1500 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc. Item continued as 10.39
Supply, installation, testing and commissioning of LT panel board, “indoor pedestal type” of size 1500 mm (height) x 1800 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved panel manufacturer (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-43 and general construction confirming to IS-13947, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 2.0 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary arrangements for pedestal mounting viz. PCC platform etc. complete all as specified and directed with and including the following accessories :- (MAIN PANEL FOR 630 KVA TRANSFORMER) BUS BAR AND INTERNAL CONNECTIONS :- The bus bars shall be made up of 04 Nos. tinned copper 1500 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc. Item continued as 10.42
Supply, installation, testing and commissioning of LT panel board, “outdoor type” of size 1400 mm (height) x 1200 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved panel manufacturer (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction confirming to IS / IEC- 60947-2004, four side slanting roof duly projected, cubical covered with separate enclosurers double layer shutter in front and single layer shutter in rear side, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 3.15 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary earthwork, PCC foundations, PCC plinth / platform etc. complete all as specified and directed with and including the following accessories :- (MAIN PANEL FOR 200 KVA TRANSFORMER) BUS BAR AND INTERNAL CONNECTIONS :- The bus bars shall be made up of 04 Nos. tinned copper 500 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc. Item continued as 10.45
Supply, installation, testing and commissioning of LT panel board, “outdoor type” of size 1200 mm (height) x 1200 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved panel manufacturer (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction confirming to IS / IEC- 60947-2004, four side slanting roof duly projected, cubical covered with separate enclosurers double layer shutter in front and single layer shutter in rear side, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 3.15 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary earthwork, PCC foundations, PCC plinth / platform etc. complete all as specified and directed with and including the following accessories :- (MAIN PANEL FOR 100 KVA TRANSFORMER) BUS BAR AND INTERNAL CONNECTIONS :- The bus bars shall be made up of 04 Nos. tinned copper 200 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc. Item continued as 10.48
M&L for cable route indicator using RCC post 1.20 mtr long, top 100 x 100 mm and bottom 200 x 200 mm with height not less than 50 cm above GL with engraved marking “HT CABLE” in bold letters during refilling of the trench complete all as specified and as directed. NOTE : The spacing between two consecutive cable route indicators shall not be more than 50.00 meters and also shall be provided at each and every bend or corner.
NOTE : Contractor has to provide ETAP Software (ETAP 20.6 of latest version) (for 100 bus 1 user) comprising of base module, load flow/voltage drop, short circuit ANSI and IEC Star TM - protective device coordination and sequence of operation, harmonic analysis/frequency scan/ harmonic filters and sizing, cable capacity, sizing and shock protection-IEC 60502 and IEC 60364, Transformer sizing and Tap optimization, year of free upgrade and user support to E4 Section of this office i.e. HQ CE Siliguri Zone within 1 (one) month of acceptance of tender. Cost is deemed to be included.
Sub total
SEWAGE DISPOSAL (Sch 'A' Part-VII)
Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 23,97,214.27 inserted by the MES in Schedule ‘A’ Part-VII.
SEWAGE DISPOSAL (Sch 'A' Part-VII (A) (MISC))
M&L for laying DWCPE (SN8) 180 (OD)/163(ID) mm dia meter pipes any length complete all as specified and as directed.
Sub total
AREA DRAINAGE (Sch 'A' Part-VIII)
Lump sum price worked out by the Contractor for “(AREA DRAINAGE)” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 37,67,621.80 inserted by the MES in Schedule ‘A’ Part-IX.
ROAD, PATH & CULVERT (Sch 'A' PART-IX)
Lump sum price worked out by the Contractor for “(ROAD, PATH & CULVERT)” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 35,26,676.00 inserted by the MES in Schedule ‘A’ Part-IX.
ROAD, PATH & CULVERT (Sch 'A' Part-IX(A) (MISC))
Cleaning and preparing the Road surface and making good for Road marking with material and labour by reflective Thermoplastic white road marking paint confirming to BIS 3262 laid down through Road marking machine in a layer of CRYSTALEX and use of 5 Kg Material per square meter by incorporating the white glass beads for reflectivity in 100 mm width complete all as specified as directed.
S&F delineator made of acrylic material fitted with high intensity reflex reflector in white/yellow colour fitted on CRCA pipe 60 cm long painted with powder coated or stove enamelled white/Black colour provided with wire gauge for safety of reflector (ART NO ARS-1006 of M/S Auto Materoad safty Pvt Ltd or other equivalent as approved by GE) embedded in PCC (1:2:4) type B1 with 20 mm graded stone aggregate (size of Block 30 Cmx30 Cmx 30 Cm) complete all as specified and as directed
S&F Cat eyes (3M USA brand) made of non breakable Polycarbonate with electonically welded prismatic retro reflective light on centre for maximum retroreflection in wet and dry conditions, with dust proof body (i.e. no dust accumulation on lens) and space built for finger grip. Bitumin adhesive B1-69 shall be used for fixing the Cat Eyes complete all as specified and as directed.
S&F SOLAR STUDS of approved make all as specified and as directed.
Sub total
SECURITY WALL, FENCING AND GATE (Sch 'A' Part-X)
Lump sum price worked out by the Contractor for “(SECURITY WALL, FENCING AND GATE)” as listed in Schedule ‘A’ Part-X. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 63,022.78 inserted by the MES in Schedule ‘A’ Part-X.
LIGHTNING PROTECTION (Sch 'A' PART-XI)
Lump sum price worked out by the Contractor for “(LIGHTNING PROTECTION)” as listed in Schedule ‘A’ Part-XI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,99,055.20 inserted by the MES in Schedule ‘A’ Part-XI.
AIR CONDITIONING & REFRIGERATION (Sch 'A' Part-XII)
Supply, installation, testing and commissioning of refrigerator inverter type double door, toughened glass shelves, BEE 5-Star rating frost free defrosting, ISI marked, electric driven, single phase having capacity 170 Ltrs or nearest higher capacity, frost free working with non-CFC refrigerant including electric connection complete all as specified and as directed.
Supply, installation, testing and commissioning of refrigerator inverter type double door, toughened glass shelves, BEE 5-Star rating frost free defrosting, ISI marked, electric driven, single phase having capacity 285 Ltrs or nearest higher capacity, frost free working with non-CFC refrigerant including electric connection complete all as specified and as directed.
Supply, installation, testing and commissioning of Water Cooler storage type, ISI marked, electric driven 230 V, 50 Hz, single phase supply with all internal accessories, stainless steel body and tank, power saving PUF insulation, adjustable cold water thermostat, 10 degree to 25 degree centigrade, auto cut-off facility, over-load protection, stainless steel front panel, extended plastic legs, eco-friendly confirming to relevant IS and pf shall not be less than 0.85 compressor & approx storage capacity of 80 Ltrs and nominal cooling capacity of 40 Ltr, non-CFC / non-HCFC gas including electric connection complete all as specified and as directed.
S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 5.0 KVA with time relay suitable for A/C complete all as specified and as directed.
S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 1.0 KVA with time relay suitable for Water Cooler complete all as specified and as directed.
S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 0.5 KVA with time relay suitable for Refrigerator complete all as specified and as directed.
Sub total
FIRE ALARM SYSTEM (Sch 'A' Part-XIII)
Lump sum price worked out by the Contractor for “(FIRE ALARM SYSTEM)” as listed in Schedule ‘A’ Part-XIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 39,388.00 inserted by the MES in Schedule ‘A’ Part-XIII.
FIRE ALARM SYSTEM (Sch 'A' Part-XIII(A) (MISC))
Supply, installation, testing and commissioning detectors complying with and type certified to EN-45 addressable type microprocessor based programmable intelligent type multi-sensor heat and smoke combination detector Photoelectric / Optical with base with self built intelligence as per IS:11360 complete all as specified and as directed.
Supply, installation, testing and commissioning addressable response indicator having flashing green LED and red LED for indication of fire and continuous monitoring including necessary connection to pin point location of fire complete all as specified and as directed.
S&F addressable type manual call point resettable type compatible with main fire alarm control board microprocessor based as per IS:2189 and necessary blinking facility complete all as specified and as directed.
Supply, installation, testing and commissioning addressable electronic sounder cum strobe with range of 25-30 mtr with output not less than 04 Watts including necessary connection complete all as specified and as directed.
Supply, installation, testing and commissioning Fire Alarm Sounders / Sirens Electronic type horizontal single Stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 mtr with sound output variation of +5 DB range complete all as specified and as directed.
Supplying, installation, testing and commissioning Fire Alarm main control panel complying with BSEN 54 UPTP 200 detectors and modules (per each loop) microprocessor based addressable intelligent type and compatible with detectors for communication to detectors and response indicators together with mimic diagram made on Auto Cad and pasted on acrylic sheet with data logging facility and 2 x 16 character LCD, confirming to IS:2189 of capacity from 99 detectors and 99 modules upto 200 detector and modules per zone / loop complete with PA based evacuation system and suitable for 415 V 3 phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have an auto dialing facility and potential NO & NC contacts and 80 Watts PA amplifier The panel should have capacity of not less than 8 zones / loops complete all as specified and as directed.
Supplying, installation, testing and commissioning Fire Alarm main control panel complying with BSEN 54 UPTP 200 detectors and modules (per each loop) microprocessor based addressable intelligent type and compatible with detectors for communication to detectors and response indicators together with mimic diagram made on Auto Cad and pasted on acrylic sheet with data logging facility and 2 x 16 character LCD, confirming to IS:2189 of capacity from 99 detectors and 99 modules upto 200 detector and modules pre zone / loop complete with PA based evacuation system and suitable for 415 V 3 phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have an auto dialing facility and potential NO & NC contacts and 80 Watts PA amplifier. The panel should have capacity of not less than 4 zones / loops complete all as specified and as directed.
NOTE FOR SERIAL ITEM No. 20.06 & 20.07 :- Amplifier of this fire alarm control panel shall be linked with public addressable system with microphone and speakers etc. to be provided by user, auto dialing facility of this control panel shall be linked with pre decided telephone – 02 Nos. Telephone and wiring of telephone will be measured and paid separately.
Supply, installation, testing and commissioning Fire Alarm Fire repeater panel made of 1.2 mm thick MS Sheet with 2 x 16 character single phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have capacity of 8-16 zones complete all as specified and as directed.
Supply, laying, jointing and testing PVC insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 V grade with stranded copper conductor of size 1.5 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc. with all fittings and connecting accessories complete all as specified and as directed. (From control room to security office).
Supply and drawing of the 2 x 1.5 Sqmm size single core PVC insulated, unsheathed, FRLSH cable, 1100 V grade, ISI marked, with multi stranded copper conductor in the existing concealed steel conduit complete all as specified and as directed.
Supply and drawing of the 4 x 1.5 Sqmm size single core PVC insulated, unsheathed, FRLSH cable, 1100 V grade, ISI marked, with multi stranded copper conductor in the existing concealed steel conduit complete all as specified and as directed.
M&L for stove enameled steel conduit and including conduit accessories of 25 mm dia medium grade concealed in wall / ceiling/ floor complete all as specified and as directed.
M&L for stove enameled steel conduit and including conduit accessories of 20 mm dia medium grade concealed in wall / ceiling/ floor complete all as specified and as directed. NOTE :- The followings shall be submitted for approval :- (a) FDA System architectural layout of fire detection and Alarm System. (b) Schemetic Diagram for panel to panel of Fire Alarm System. (c ) Riser Diagram of Fire Alarm/Telephone System with cabling details.
Sub total
FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT (Sch 'A' Part-XIV)
Lump sum price worked out by the Contractor for “(FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT)” as listed in Schedule ‘A’ Part-XIV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,64,487.59 inserted by the MES in Schedule ‘A’ Part-XIV.
FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT (Sch 'A' Part-XIV)(A) (MISC))
S&F of Valves, Sluice, flanged of Class PN 1.6, 150 mm (6”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.
S&F of Valves, Sluice, flanged of Class PN 1.6, 100 mm (4”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.
S&F of Valves, Sluice, flanged of Class PN 1.6, 80 mm (3”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.
S&F of 80 mm bore hand operated butterfly valve of pressure not less than 15 Kg/Sqcm all as conforming to relevant IS including jointing and testing complete all as specified and as directed.
S&F of Valve, reflux, with by-pass arrangement, 150 mm (6") dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.
S&F of Valve, reflux, with by-pass arrangement, 100 mm (4") dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.
S&F of fire hydrant landing valve type-A (single head outlet) of 63 mm dia conforming to IS 5290 including jointing and testing complete all as specified and as directed.
S&F of 63 mm dia RRL Hose type 'A' 15 meter long hose conforming to IS-636 complete with male and female coupling conforming to IS-903 including jointing and testing complete all as specified and as directed.
S&F of hose box made of 18 gauge MS Sheet 800 mm x 600 mm x 250 mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white inside yard for keeping 2 Nos. hose pipe of length 15 meter each, non percolating type conforming to IS 636 complete with branch pipe, nozzle 12.5 mm dia, coupling etc. complete all as specified and as directed.
S&F of hose reel drum and hose reel of 20 mm dia and 36 meter length conforming to IS-884 including jointing and testing complete all as specified and as directed.
S&F of Gun metal fire brigade inlet connection (suction collecting head) consisting of four Nos. 63 mm dia instantaneous type male coupling with built-in check valves and 150 mm dia sluice valve (one No. 150 mm dia NRV) and 150 mm dia flanges outlet complete with all accessories all as conforming to relevant IS including testing complete all as specified and as directed.
S&F of 63 mm dia instantaneous inlet gun branch pipe with 15 mm bore nozzle short conforming to IS-903 including jointing and testing complete all as specified and as directed.
S&F of ICV / Alarm gong (Intermittent hudraulic alarm with alarm gong and water motor alarm) 100 mm all as confirming to relevant IS including testing complete all as specified and as directed.
S&F of fire hydrant stand post 80 mm dia GI / MS flanged type, 1.5 Mtr height with provn of single outlet conforming to IS-908 including jointing and testing complete all as specified and as directed.
S&F of Sprinkler glass bulb type (Standard response) as per IS : 15106 / TAC guidelines 68 degree temperature rating pendent type including testing complete all as specified and as directed.
S&F of Air cushioning tank (Air vessel) 250mm dia x 1000 mm high with dished top, made of minimum 6 mm thick MS pipe / plate complete with 20 mm dia brass air valve (ball type), 20 mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories all as confirming to relevant IS including testing complete all as specified and as directed.
S&F of Automatic Air Release Valve 50 mm dia suitable for domestic water with 50 mm gun metal stop valve all as confirming to relevant IS including testing complete all as specified and as directed.
Supply and laying of pipes ERW steel, 'Heavy Class' including specials, nominal dia 200 mm as per IS 3589 (1981) with minimum thickness 6.0 mm all as confirming to relevant IS including testing complete all as specified and as directed.
Supply and laying of pipes ERW steel, 'Heavy Class' including specials, nominal dia 150 mm as per IS 3589 (1981) with minimum thickness 6.0 mm all as confirming to relevant IS including testing complete all as specified and as directed.
S&F of MS ERW pipe 100 mm NB heavy duty including specials duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer all as confirming to relevant IS including testing complete all as specified and as directed.
S&F of MS ERW pipe 80 mm NB heavy duty including specials duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer all as confirming to relevant IS including testing complete all as specified and as directed.
M&L for construction of brick masonry valve pit of internal dimensions 1000 mm x 1000 mm x 1000 mm complete and fabrication of 3.15 mm thck MS sheet cover and angle iron frame made out of 50 mm x 50 mm x 6 mm MS angle iron and one side provided with hinge with locking arrangement and duly painted with two coats of black bituminous paint over a coat of red oxide primer including necessary earth work and PCC work complete all as specified and as directed.
M&L for cutting of CI / MS / DI pipes in position for insertion of new tee, branches, valves etc. for bore of pipe upto and including 150 mm complete all as specified and as directed.
M&L for Cement Concrete in foundation, filling mass concrete, type-C2, (1:3:6) (using 20 mm graded stone aggregate) for foundation of hose reel box, pipe line thrust block support etc. and finishing the surface even and smooth without using extra cement including necessary formwork complete all as specified and as directed.
S&F of Fire extinguisher, ISI marked, Dry Chemical Powder (ABC) type all as confirming to IS : 15683 of capacity 5 Kg with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.
S&F of Fire extinguisher, ISI marked, Water CO2 / Stored Pressure type all as confirming to IS : 15683 of capacity 9 Ltrs with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.
S&F of Fire extinguisher, ISI marked, CO2 type all as confirming to IS : 15683 of capacity 4.5 Kg with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.
Supply and installation of 06 Nos. fire buckets made out of 24 gauge galvanized steel sheet and of capacity 13 Ltrs., painted white inside, red outside and black on bottom and inscribed with letters "FIRE" in black & bold with and including MS stand duly painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and provision of Shovel - 01 No., Fire hook - 01 No., Fire beater - 01 No. and manually operated MS bell etc. complete all as specified and as directed.
Sub total
CENTRAL AC PLANT (Sch 'A' Part-XV)
Design, Supply, Installation, testing and commissioning of Microprocessor controlled water cooled VFD screw chiller type air conditioning plant of full load capacity not less than 360 TR (2 x 180TR) and with additional 1 x 180 TR as standby to meet 50% of full load capacity of head load suitable for complete operation with refrigerant R-134 a or any non-CFC / non-HCFC based refrigerant with all equipment’s and accessories complete for Hospital Building of 155 BH (Ph-III) at Tezpur, to meet the inside design condition of temp 21 + 2oC and relative humidity 50 + 5% and as per OEM all as conforming to relevant IS complete all as specified and as directed. NOTE :- (i) The tenderer should visit the building / site condition and work out heat load based on the Building Plan, structural specifications, outside / inside parameters and design parameters as given in the tender and ascertain the plant capacity given in the schedule and technical parameters given under relevant schedules / items and PS. (ii) In case of any change considered necessary in the technical parameters given under relevant schedules / items and PS and plant capacity given in the schedule to provide the design parameters, the tenderer should furnish the same within 15 days prior to receipt of tender, duly justified with their heat load calculations. Item continued as 23.02
(iii) Within 4 (Four) Months of acceptance of Tenders complete design along with standard detail and equipment schedules drawings, related calculation basis based on AMCA, AHRI, ASHRAE, NABH, CIIBSE, ISO, NFPA, UL, ECBC, IGBC and NBC shall be submitted by the contractor through Engr-in-Charge to this HQ for scrutiny. Contractor shall provide all necessary assistance/support at all levels for scrutiny. Duly scrutinized scheme shall be got vetted by the contractor from IIT/NIT for any rectification /improvement of the scheme. (iv) The proposed HVAC System owing to efficient Engineering Mode of operation control. (v) Mechanical equipment will be designed for a15-20 years life. Switch Board, equipments and component will be rated for operation in ambient temperature of 45 deg C and upto 95 % relative humidity. (vi) Heat gain/loss Calculation to be done for Summer/ Monsoon and Winters. (vii) Minimum efficiency of HVAC system to be as per ECBC and ASHRAE Standards. (viii) Fresh Air shall be provided based on ASHRAE 170- 2017 (ix) Chiller Plant Manager shall be installed for Energy Conservation and efficient operation of Air Conditioning System. (x) All AHU should be with VFD. (xi) Positive pressure difference in ICU/Wards with outside air in adjoining areas to be maintained as per ASHRAE, NABH,NBC. (xii) All Lift well shall be provided with pressurization system as per as per Fire norms and as per NBC 2016. Item continued as 23.03
(A) Three water cooled VFD Screw chilling units complete and each comprising of following :- (i) AHRI Certified Water cooled Water chilling machine with Semi-hermetic screw compressor with VFD meeting international standards like ECBC (Minimum COP: 5.4, Minimum: IPLV:6.17, test standard ARI 550/590-1998) and ASHRAE 90.1 2010 Standards - path B ( for equipment class water cooled, electrically operated, positive displacement, Minimum COP: 0.718 KW/Ton, Minimum: IPLV:0.54 IPLV, test standard ARI 550/590-1998). Unit need to be mounted on steel frame as per specifications. Motor shall be of high efficiency suitable for 415 +/- 10 % volts, 50 +/- 3Hz, 3 phase AC supply. Refrigerant shall be environmentally friendly R134A refrigerant. Chiller should be capable of unloading from 100 to 25% capacity at constant condenser water temp. Chiller shall come with complete first charge of refrigerant and oil. (Either factory charged /site charged). Chiller Actual condition data must comply followings:- Actual Capacity: 180 TR Total Input Power: 114 kW Refrigerant: R-134a Evaporator Leaving Temperature:6.67 °C Entering Temperature:12.22 °C Delta T:5.55 °C Item continued as 23.04
Flow Rate:27.28 L/s Max Operating Pressure:150 psig (Water Side) Fouling Factor0.017600 M². K/kW Condenser Leaving Temperature:34.61 °C Entering Temperature:29.44 °C Delta T:5.17 °C Flow Rate:34.56 L/s Max Operating Pressure:150 psig (Water Side) Fouling Factor:0.044000 M². K/kW Total Heat Rejection:746.9 kW Electrical Data Volts/Phase/Hertz:415/3/50.0 Full Load Current:186.94 A Starting Current:10.00 A Voltage Range:360 to 440 V (ii) One set of shell and tube type water cooled condenser with shell and integrally finned copper tubing, complete with safety valves, drain valve, water inlet and outlet valves, hot gas inlet and liquid outlet isolating valves thermometer and pressure gauges at inlet and outlet and purge valves all as specified and as directed. (iii) Blank Item continued as 23.05
(iv) One set of MS stand of suitable size and shape fabricated out of channel and angle iron of suitable size painted with two coats of black synthetic enamel paint over one coat of red oxide primer for mounting compressor, motor, condenser, chiller and control panels etc of above specification. (v) One set of anti-vibration mounting pads and suitable foundation as per manufacturer’s instruction including necessary foundation, bolts & nuts etc. (vi) Refrigerant piping complete with all require fittings and accessories such as thermo-setting expansion valve, refrigerant drier with isolating valves, pilot operated solenoid valves etc. with necessary bracket and support to inter connect compressor, chiller, condenser and expansion valves including insulation of suction lines and chiller lines with fire resisting insulating material of adequate thickness all as per manufacturer’s specifications. (vii) Microprocessor based controls comprising of following features :- (a) Automatic capacity control reducing energy system. (b) Microprocessor controlled pump down system. (c) Microprocessor based sequence of starting / stopping of equipment with fixed time delays. (d) Alarm history giving cause of tripping. (e) Data scanner system including operations instructions. (f) Oil pressure failure cut out LP / HP cut out. (g) Liquid line indicator. (viii) Fail safe features will be equipped with following :- (a) Under Voltage protection. Item continued as 23.06
(b) Single phasing protection. (c) Over load protection. (d) Phase imbalance protection. (e) Anti-freeze protection. (f) Power loss trip and shut down. (g) Phase reversal protection. (h) Over voltage / surge protection. (ix) One set of water flow switch in condenser and chiller water line at inlet and outlet. (x) First charge of refrigerant gas R-134 a or any non-CFC /non-HCFC based refrigerant and compressor oil as per manufacturer’s recommendation. (B) Chilled water cooling arrangement comprising of the following :- (i) Supply and fixing of MS Class ‘C’, heavy duty ERW chilled water piping of one lot of adequate size including fittings and fixtures duly welded, laid in ground or air, inside / outside the building alongwith necessary clamps, nuts, bolts etc adequately supported on rigid primary and secondary supports complete with balancing valves at chiller inlet and outlet for circulation of chilled water from chiller to AHU – 15 Nos. with necessary connection to chilled water expansion tank including with water pressure gauge / thermo meter in chiller inlet and outlet. AHU inlet and outlet complete with insulation of fire retardant quality expanded polystyrene moulded pipe section 50 mm thickness and density not less than 20 Kg/Cum covered with a layer of 120 gm/Sqm Item continued as 23.07
polythene sheet (as vapour barrier) duly reinforced with 26 gauge chicken wire mesh with buffing all joint and tied down with GI lacing wire and finally finished rigid with 26 gauge aluminium foil cladding, if laid inside the building, and with cement mortar of 1:3 of 12 mm thick, if laid in ground or air outside the building complete with all accessories comprising control valves like butterfly valves, balancing valves, Y-strainers, non-return valves, pressure gauges, thermometers, water flow switches, suitable EPDM bellows etc including excavation, refilling making good the excavated surface wherever the pipes are required to be laid in ground all as per technical requirement / design. (ii) Three Nos. primary centrifugal chilled water pump set with bronze impeller of suitable type-C (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation including base frame as per manufacturer instruction and with anti-vibration rubber pads with suitable soft starter with overload protection, protection against phase reversal and single phase preventer and 03 Nos. dial type (150 mm) water pressure gauge and thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer check valve on delivery line etc all as specified and as directed. (iii) Three Nos. secondary centrifugal chilled water pump set with bronze impeller of suitable type-C (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation Item continued as 23.08
including base frame as per manufacturer instruction and with anti-vibration rubber pads with suitable starter with overload protection, protection against phase reversal and single phasing and 03 Nos. dial type (150 mm) water pressure gauge and thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer check valve on delivery line etc all as specified and directed and including variable frequency drive. (iv) Chilled water expansion tank of adequate capacity made out of minimum 04 mm thick MS plate construction including insulation with 13 mm thick cross link polyethylene of self adhesive with aluminium foil protection. The tank shall be complete with necessary connection for piping vent and made up connection with necessary float valve, drain valve, incoming / outgoing line valves and drain connection with control valve and necessary inter-connection complete all as specified. (C) Condenser Water Cooling arrangement comprising of following :- (i) Three Nos. centrifugal type Condenser cooling water pump set of suitable type / capacity with bronze impeller each of 50% capacity (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation base frame as per manufacturer instruction and with anti-vibration rubber pads with suitable starter with overload protection, protection against phase reversal and single phasing and 03 Nos. dial type (150 mm) water pressure gauge, thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer, check valve on delivery line etc all as specified and directed. Item continued as 23.09
(ii) Two Nos. induced draft FRP cooling tower of suitable type / capacity of heat rejection capacity minimum 20% higher than total tonnage of AC plant (i.e. 360 TR x 1.2) for a water flow as recommended by OEM, made out with FRP type body and water basin, PVC filling with integral louvers and drift eliminator, filled with spray nozzles of having self-rotating type sprinklers, statically and dynamically balanced counter flow type fan direct driven with TEFC squirrel cage induction motor with suitable starter, suction screen, made up quick fill arrangement, overflow and drain connection switch necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, cement concrete foundation, steel supporting structure, anti-vibration mountings etc complete all as specified and as directed and with necessary PCC hard standing around the area of width not less than 750 mm from the platform of the cooling tower. (iii) One lot of condenser water pipe line and fitting made out of MS ‘C’ grade from makeup water tank to cooling tower, from cooling tower to Condenser and return to cooling tower through condenser cooling water pumps with all controls and fittings complete with materials alongwith necessary clamps, vibration isolators and fittings such as tees, bends, necessary butterfly valves, check valves, Y-type strainer, non-return valves, suitable EPDM bellows and pressure gauges with needle valves, thermometeretc adequately supported on rigid supports etc all as specified and required. (iv) Two Nos. PVC makeup water tank of 2 x 5000 Ltrs capacity, ISI marked, Triple layered, duly interconnected and erected on RCC staging of suitable height and size with suitable RCC slab with necessary Item continued as 23.10
foundation and PCC hard standing on surrounding area to a width of not less than 500 mm from the platform of makeup water tank including inlet and outlet, overflow connection and float valve assembly with necessary inter connection alongwith suitable control valves. (D) Required number of Air Handling Unit with VFD :- 15 Nos. each having 8500 cfm capacity indoor type with necessary provision of air mixing chambers for fresh air draw through type having technical specification all as specified and as directed of sectionalized construction, factory made, floor mounted double skin type made of 25 mm thick modular AHU panels with GI casing of thickness 24 Gauge pre-coated outside layers and 24 Gauge inside layer injected with CFC free polyurethane foam (PUF) of 38 Kg/Cum density insulation complete with blower section, chilled water cooling coil section IP-55 Class F insulation motor and drive set, filter section with muffler and access door to attend the motor / fan and all accessories with lighting provision and all accessories with suitable starter and controls etc and each AHU comprising of following :- (i) 6 row cooling coil made of aluminium finned copper tube with coil section, pre filters section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, fine filters of MERV 14, 99.9%, flanged type of suitable size as per design and 3 x 6 KW heater with ultrasonic humidifier and humidistat including control cable from humidistat to humidifier back to humidistat. External Static pressure 65 mm for which fan motor and fan blower to be considered. Return air plenum with RA and FA Volume control damper.” Item continued as 23.11
(i) 6/8 row Cooling coil of copper tube with aluminium fins with automatic controlled anti-freeze thermostat suitable for chilled water. (ii) Blower section complete with blower having forward curved centrifugal fan for weather maker suitable for static pressure all as specified and as directed, with minimum 2 bends GSS eliminators with suitable capacity TEFC squirrel cage induction motor (IP 55 and class F insulation) for operation on 3 phase 415 V 50 Hz AC supply with mounting frame work. (iii) Inbuilt pan humidifier – 01 Set. (iv) 50 mm thick washable type pre-filters with filter element made out of synthetic non-woven media supported by HDPE mesh on both side including stitching in diamond pattern complete including frame and suitable for efficiency 90% down to 10 micron EU-3 type-C complete with mounting frame work. (v) Secondary dry type cleanable and easily maintainable air filter supported by GI wire and folder to form accordion plate having an efficiency of 99% down to 5 micron EU-5 TYPE complete with mounting frame works. (vi) Drain connection, stainless steel (SS-304) drain pan and with necessary GI pipe for drain out the condensate to the open drain of the building. (vii) Acoustic insulation of AHU all as per manufacturer’s design and type to maintain 50 decibel and all as specified. Item continued as 23.12
(viii) Chilled water lines with suitable butterfly valve, Y strainer, pressure gauge, temperature gauge, on the supply line and with suitable butterfly valve, balancing valve, 3-way modulating control valve, pressure gauge, temperature gauge etc on the return chilled water line complete all as specified and as shown in the schematic diagram and as required. (E) Strip Heaters :- Strip Heaters for winter heating and monsoon reheating with strip heaters, controlled by humidistat, heating thermostat – 18 KW for each AHU x 15 AHUs. (F) Air Distribution System :- Air Distribution System including supply air duct made out of galvanized steel sheet, ducting from AHU to condition room, of commercial grade VIII as per IS-655 with latest insulating material resin bonded glass wool rigid board 48 Kg/Cum density covered with glass cloth and perforated aluminium sheets as per specification including suitable MS supporting arrangements including primary and secondary support from RCC roof / ceilings / walls / traverse for ducts inside the conditioned space and from wall / traverse / floor / ground for ducts outside non-conditioned space including necessary foundation for support etc complete with adjustable dampers, vanes etc complete as per specification and as per ducting layout marked tentatively on site plan to provide the required quantity of supply air in the condition room and to achieve the designed parameters with desirable velocity and noise level with uniform distribution of air and comprising of following accessories :- Item continued as 23.13
(i) New Mechanical Fire dampers of model CFD-FL approved 90 Minutes Fire Rating as per UL-555-1995 by CBRI in existing main supply air duct layout drawing including control wiring. The dampers shall be made of heavy gauge galvanized steel having multi blade construction. The blades shall be fitted with chrome plated shaft and self-lubricated phosphorous bronze bushes. The dampers shall also be provided with jam seal (compression type) on sides to prevent spread of smoke and fire. The blades of the dampers are held in the ‘open’ position by a high tensile spring and a fusible link. The fusible link should be UL stamped and operates at 74oC, causing the damper to close immediately on break fire to prevent the spread of fire through the ducts. Control wing from fire damper to AHU control panel to switch off AHU motors, heaters and humidifier when the fire damper is closed in the event of fire. (ii) Powder coated extruded aluminium section fresh air grill of suitable size in AHU room with GI volume control dampers, bird screen etc complete as required and as specified. (iii) Supply air diffuser duct mounted double louvered and double deflection type of powder coated aluminium with volume control dampers of required sizes and numbers. (iv) Return air grill duct mounted single louvered double deflection type of powder coated aluminiumof required sizes and numbers fitted on ducts all as shown in the drawing. (v) Acoustic lining to the main supply air duct from AHU upto a minimum length of 6 mtrs with 25 mm thick of Resin bonded glass wool of density 32 Kg/Cum overlapped with RO tissue, sealing all joints and finally covered with 0.5 mm perforated aluminium sheet. Item continued as 23.14
(vi) Humidistat cumdigital type thermometer – 01 No. with 99% efficiency and quick response time in each AHU room, Total AHU Room – 15 Nos. NOTE : (i) Return air will come back from Air conditioned room to AHU room from above false ceiling provided in passage. (ii) Ducting should be designed as per SMACNA and ASHRAE 63.1 and 170. VAV control to be installed in ducts to control air flow in individual rooms. (iii) Each AHU should have separate Control Panel. A microprocessor based control panel to show all technical parameter of 15 AHUs and checking in Control Centre of AC Plant. The outdoor design conditions shall be considered as per actual. The indoor design conditions for centrally air-condition spaces shall be:- Dry Bulb Temperature - 21deg C + 2 deg C Max Relative humidity - 50 + 5%. Lighting and Equipment Load shall be as per NABH guide line, NBC, occupancy. In Building Envelope under deck Insulation on Top Floor with 50 mm thick PUF Slab or equivalent insulation. Noise level - Noise level shall be as under :- (i) Departments - 25-35 dB (ii) Ward - 25-35 dB (iii) Administration - 25-35 dB (v) General area - 35-45 dB (vi) Plant Rooms - 70-75 dB Item continued as 23.15
(vii) Automatic Star Delta starter with power contactors of suitable capacity for starting / stopping AHU motor with over load relay, single phase preventer with trip button and toggle switch. (This starter is considered in respective item of AHU and to be fixed in this LT panel.) (viii) Power contactors to make on/ off of strip heaters in steps controlled by heating humidistat and heating thermostat. Strip heaters shall have over load protection. (ix) DOL starter for humidifier controlled by humidistat. (x) One No. electronic digital thermometer with necessary sensors and switching arrangement for each AHU room (total 15 nos.) to display temperature of return air. (xi) Power cabling of adequate size and sufficient core from LT panel board to electric motors and other electrical equipment (03 Nos. Scroll Chilling Unit, 03 Nos. Condenser Pump, 06 Nos. Chilled water pumps, 02 No. Cooling Tower motor, AHU control panel to AHU Motor, strip heaters, humidifier – 15 Sets and other allied electrical equipment if any with multistranded copper conductor XLPE insulated, armoured cable laid neatly and in straight line in trenches / on wall / in cable trays with necessary saddles and clamps including copper lugs of suitable size and cable glands, etc complete all as specified and as per IE rules and electrical codes. (xii) Power cabling of adequate size and sufficient core from main LT panel to AHU control panel – 15 Nos. with multi stranded aluminium conductor XLPE insulated armoured cable laid neatly in trenches / on wall in cable tray including Aluminium lugs and cable gland etc complete all as specified and as per IE rules and electrical code. Item continued as 23.20
(xiii) Control wiring with PVC insulated copper conductor of suitable size with No. of cores as required cable on wall / cable tray etc and armoured PVC insulated, sheathed stranded copper conductor cable of suitable size with No. of cores as required when laid in trenches underground. (xiv) Earthing :- (a) M&L for earthing complete with Galvanized steel earth plate 600x600x6.0 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to GI strip of size 32x6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel including excavation and earth work supplying and laying charcoal dust, common salt, PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in chamber and MS angel iron frame 40x40x3 mm and RCC cover 40 mm thick (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No. 3 of SSR Part-I of 2009 and connected to earth test point including testing complete all as specified and as directed. (02 Nos. of main LT panel, 04 Nos. for AC plant equipment, 02 Nos. each for AHU control panel of one wing x 5 wing i.e. A, B, C, D, E). (b) Earthing busbar made out of 32 x 6 mm GI strip mounted on insulators suitable for 02 Nos. incoming and No. of outgoings as required for AC plant equipment -02 Sets. (c) Two earthing connection to LT panel with GI strip 32 x 6 mm. (d) Two earthing connection from earth bus bar with GI strip 32x6 mm to scroll chillers. Item continued as 23.21
(e) Two earthing connection from earth bus bar with GI strip 25 x 4 mm for motor of capacity 10 HP and above two earthing connection from earth bus bar with GI wire 4 mm dia for motor of capacity less than 10 HP. (f) Two earthing connection with GI strip 25x4 mm to each AHU control panel & AHU shall be connected (H) Miscellaneous Items :- (i) One Display board of size not less than 1 x 1 m showing schematic diagram and flow chart of the AC plant drawn on Acrylic white sheet with coloured paints duly marking the details duly fabricated with suitable aluminium frame. (ii) Supply and fixing glow sign board of Central AC plant size 3000x600x300 mm, weather proof made of MS angle 50 x 50 x 6 mm with white acrylic sheet 2 mm thick and writing “Central AC Plant 155 BH Ph-III, GE (S) Tezpur” with arial black font with suitable size not exceeding 150 mm and minimum size 100 mm and provision of 5 Nos. of LED tube light 1 x 20 Watt and other accessories and grouting on floor / roof with suitable primary and secondary supports. (iii) S&F of fire point comprising of water (Stored pressure) fire extinguisher (IS:6234) 9 Ltr capacity -02 Nos. dry chemical powder (ABC) extinguisher (IS:2171) 5 Kg capacity – 02 Nos, light weight squeeze grip type CO2 extinguisher (IS:2878) 3 Kg capacity – 02 Nos. (iv) Rubber matting of size 1x2m, 19 mm thick for LT panel – 02 Nos. (v) Painting with two coats of synthetic enameled paint over one coat of red oxide primer of all mild steel pipe / structure as per the standard colour of the central AC plant. Item continued as 23.22
(J) Minor Civil Work :- Any other minor masonry work required for erection and smooth functioning of AC plant such as :- (i) Foundation for pumping sets, motor, chiller unit, chilled water pipe, air handling unit, cooling tower make up water tank, expansion tank etc as per manufacturer design complete. (ii) Excavation for chilled water pipe line work, cable etc. (iii) Making good damaged civil work in fixing Ducts laying pipelines collars etc. (iv) All other civil work required for testing and commissioning of the plant. (v) All mild steel work fabricated in rolled steel sections, MS Plates, flats round bolts and nuts etc for supporting/ jointing / fastening condenser water pipes, chilled water pipes, make up and drains water pipes etc. (vi) Painting with two coats of synthetic enameled paint over one coat of red oxide primer of all mild steel pipe / structure as per the standard colour coding of the central AC Plant. (vii) Stenciling on pipe line showing arrow / indicator for flow of water / refrigerant / chilled water / hot water with distinguished colour and stenciling of name of major components for identification and full proof operation of switch gears / indicators.
Sub total
DG SET (Sch 'A' Part-XVI)
Lump sum price worked out by the Contractor for “(DG SET)” as listed in Schedule ‘A’ Part-XVI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 30,183.00 inserted by the MES in Schedule ‘A’ Part-XVI.
DG SET (Sch 'A' Part-XVI(A) (MISC))
Supply, installation, testing and commissioning of silent built-in within an acoustic enclosure diesel engine driven generating set water cooled including AMF panel for standby power supply 415 Volts, 03-Phase, 4-Wire, 50 Cycles/Sec, 500 KVA (400.00 KW) or next higher standard size available at 0.8 power factor complete with alternator directly coupled to diesel engine, mounted on common base frame and complete with self-starter, fuel tank capacity not less than 8 hours fuel requirement and battery as recommended by OEM, battery leads, sound proof canopy etc. with features for automatic shutdown in the event of a circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. and microprocessor based gen-set controller with the following under-mentioned features and all as specified and as directed. (a) Alphanumeric LDC display with LED backlight. (b) Operator interface. (c) Suitable to provide a record of most recent fault conditions and fault history. (d) Complete alternator data, viz. voltage, Ph-Ph, Ph-neutral, KVA, Frequency etc. (e) Complete engine data viz. starting battery voltage, engine temperature, engine running hours, engine oil pressure etc. (f) Control including provision of service adjustment and calibration of DG control functions. Item Continued as 25.02
GENSET SPECIFICATIONS :- Prime Mover Rating : 500 KVA / 400.00 KW Current Rating : 695.65 A No. of Phases : 03 Power Factor : 0.8 (Lag) ENGINE SPECIFICATIONS :- Output Prime : 448 KWm Aspiration : Turbocharged-aftercooled. No. of Cylinders : 06, In line. RPM : 1500 Governor : Mechanical ALTERNATOR SPECIFICATIONS :- Voltage : 415 RPM / Frequency : 1500/50 Hz Enclosure : IP 23 Voltage Regulation (Max) : +/- 1%. Insulation Class : H Class Conformance Standards :- IS 4722, BS 5000, IS 1460, ISO 8528, BS 5514, ISO 3046. Make and Size of Battery : As recommended by OEM. Item Continued as 25.03
Supply, installation, testing and commissioning of silent built-in within an acoustic enclosure diesel engine driven generating set water cooled including AMF panel for standby power supply 415 Volts, 03-Phase, 4-Wire, 50 Cycles/Sec, 600 KVA (480.00 KW) or next higher standard size available at 0.8 power factor complete with alternator directly coupled to diesel engine, mounted on common base frame and complete with self-starter, fuel tank capacity not less than 8 hours fuel requirement and battery as recommended by OEM, battery leads, sound proof canopy etc. with features for automatic shutdown in the event of a circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. and microprocessor based gen-set controller with the following under-mentioned features and all as specified and as directed. (a) Alphanumeric LDC display with LED backlight. (b) Operator interface. (c) Suitable to provide a record of most recent fault conditions and fault history. (d) Complete alternator data, viz. voltage, Ph-Ph, Ph-neutral, KVA, Frequency etc. (e) Complete engine data viz. starting battery voltage, engine temperature, engine running hours, engine oil pressure etc. (f) Control including provision of service adjustment and calibration of DG control functions. GENSET SPECIFICATIONS :- Prime Mover Rating : 600 KVA / 480.00 KW Current Rating : 834.78 A Item Continued as 25.06
No. of Phases : 03 Power Factor : 0.8 (Lag) ENGINE SPECIFICATIONS :- Output Prime : 530 KWm Aspiration : Turbocharged-aftercooled. No. of Cylinders : 12, "Vee". RPM : 1500 Governor : Mechanical ALTERNATOR SPECIFICATIONS :- Voltage : 415 RPM / Frequency : 1500/50 Hz Enclosure : IP 23 Voltage Regulation (Max) : +/- 1%. Insulation Class : H Class Conformance Standards :- IS 4722, BS 5000, IS 1460, ISO 8528, BS 5514, ISO 3046. Make and Size of Battery : As recommended by OEM. Exhaust Pipe : MS Exhaust pipe with bends/flanges and all accessories to be supplied and erected as per OEM recommendation. The Exhaust Pipe shall be insulated with low resin bounded wool of min 75 mm thickness min 144 Kg/m density. Item Continued as 25.07
Sub total
HOSPITAL SIGNAGE (Sch 'A' Part-XVII)
Lump sum price worked out by the Contractor for “(HOSPITAL SIGNAGE)” as listed in Schedule ‘A’ Part-XVII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 30,805.50 inserted by the MES in Schedule ‘A’ Part-XVII.
HOSPITAL SIGNAGE (Sch 'A' Part-XVII(A) (MISC))
S&F of single sided 3 Watts red LED signage (EXIT) with built-in battery backup for 2 hours complete all as specified and as directed. MAKE : Bajaj product code 220209 or equivalent in Philips / Wipro.
S&F of double sided 3 Watts green LED signage (EXIT) with built-in battery backup for 2 hours complete all as specified and as directed. MAKE : Bajaj product code 220210 or equivalent in Philips / Wipro.
S&F of double sided 3 Watts green LED signage (STAIR) with built-in battery backup for 2 hours complete all as specified and as directed. MAKE : Bajaj product code 111501 or equivalent in Philips / Wipro.
S&F of double sided 3 Watts green LED signage (TOILET) with built-in battery backup for 2 hours complete all as specified and as directed. MAKE : Bajaj product code 111505 or equivalent in Philips / Wipro.
S&F of double sided 3 Watts green LED signage (LIFT) with built-in battery backup for 2 hours complete all as specified and as directed. MAKE : Bajaj product code 111503 or equivalent in Philips / Wipro.
M&L for concealed point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi-stranded copper conductor single core cable drawn through and including stove enameled steel conduit of adequate size with all fittings and accessories including sunk mild steel terminal boxes for mounting modular switches, sockets, regulators etc complete including FRLSH PVC insulated & unsheathed single core multi-stranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one socket outlet point 6 A on independent board complete all as specified and as directed.
S&F to wall single sided sign board made out of 3 mm thick acrylic sheet fixed on aluminium angle, iron structure of suitable size duly paste the matter with self adhesive vinyl coloured sticker as per requirement with proper fixing arrangement complete all as specified and as directed.
S&F to wall single sided glow sign board made out of 3 mm thick acrylic sheet with vinyl film letters including necessary LED light 8-10 Watts with driver, pre-wired , PGI Sheet housing etc complete all as specified and as directed.
Sub total
LIFT (Sch 'A' Part-XVIII)
Lump sum price worked out by the Contractor for “(LIFT)” as listed in Schedule ‘A’ Part-XVIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 26,320.00 inserted by the MES in Schedule ‘A’ Part-XVIII.
LIFT (Sch 'A' Part-XVIII(A) (MISC))
(a) Type of lift : Stretcher cum Passenger (15 Passengers) (b) Load capacity : 1020 Kg (c) Speed : 0.50 mtr/sec with single speed mortar (d) Power supply : 415 V, 3 phase, 4 wire AC, 50 Hz. (e) Type of drive : AC variable voltage and variable frequency. (f) Type of machine : Gearless (g) Car size : 1000x2400 mm or nearest suitable size as per OEM (maximum net inside car area - 2.47 Sqm, minimum net inside car area 2.35 sqm) as per IS:14665 (Part-3/Sec 1&2):2000, Well size: 1800x 3000 mm (h) Car door : Automatic centre opening with V3F door drive sliding type, stainless steel, hairline finish (N-304) for car and landing doors at all floors. (j) Car enclosure : Standard manufacturing with MS frame & stainless steel hairline finish (N-304) in standard thickness with LED light fitting on ceiling of appropriate type / size / Wattage and concealed axial flow fan with stainless steel grill and also 02 Nos. vertical down light LED lamp and covered with stainless steel wire mesh all as per OEM. (k) Terminal buffers : Special spring buffers. (l) Door opening (Inside) : 800 x 2000 mm (m) Counter weight shall be of cast iron as recommended by OEM (n) Car and counter weight guide : Guide rails of ‘T’ Section Mild Steel as per OEM design. Item continued as 29.03
(o) Clear Hoist Size : As per OEM. (Bidder shall inspect the same at site before quoting). (p) Flooring : Aluminium chequerred plate 5 mm thick complete. (q) Signals :- (i) Combined luminous hall buttons with VFD hall position indicators at all floors. (ii) Vacuum filled Display (VFD) for car position indicator of stainless steel. (iii) One No. Car operating panel with Luminous buttons in car. (iv) Car direction indicator in car and landing. (v) Battery operated alarm bell and emergency light (rechargeable) alongwith suitable maintenance free battery. (vi) Overload warning feature in car cabin. (vii) Fireman’s switch 01 No. per lift to be installed at Ground floor near landing door. (viii) All signal fixture and car operating panel on stainless steel face plate. (ix) Full height standard infra red door sensor with 154 criss cross beams. Item continued as 29.04
(w) Hoist-Way Construction : RCC wall construction as existing at site, total height from Ground level to slab of machine room – As per OEM. (Bidder shall inspect the same at site before quoting. (x) ACVVVF drive shall be of make OTIS / Johnson / Kone / Schindler / Thyssenkrupp. (y) Control System shall be closed loop type. (z) Door shall have ACVVVF controlled door operator. (za) Faceplate shape shall be Rectangular and stainless steel in Hairline Finish. (B) (zb) Civil Work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine etc and one coat of white wash in the lift shaft after completion of lift installation.
(a) Type of lift : Service cum Passenger (10 Passengers) (b) Load capacity : 680 Kg, Well size 1900x 2100 mm. (c) Speed : 1.00 mtr/sec with single speed mortar (d) Power supply : 415 V, 3 phase, 4 wire AC, 50 Hz. (e) Type of drive : AC variable voltage and variable frequency. (f) Type of machine : Gearless or nearest suitable size as per OEM (g) Car size : 1300x1350 mm Maximum net inside car area - 1.76 Sqm and minimum 1.61 sqm as per IS:14665 (Part-3/Sec 1&2):2000 (h) Car door : Automatic centre opening with V3F door drive sliding type, stainless steel, hairline finish (N-304) for car and landing doors at all floors. (j) Car enclosure : Standard manufacturing with MS frame & stainless steel hairline finish (N-304) in standard thickness with LED light fitting on ceiling of appropriate type / size / Wattage and concealed axial flow fan with stainless grill and also 02 Nos. vertical down light LED lamp and covered with stainless steel wire mesh all as per OEM. (k) Terminal buffers : Special spring buffers. (l) Door opening (Inside) : 800 x 2000 mm (m) Counter weight shall be of cast iron as recommended by OEM (n) Car and counter weight guide : Guide rails of ‘T’ Section Mild Steel as per OEM design. Item continued as 29.08
(o) Clear Hoist Size : As per OEM. (Bidder shall inspect the same at site before quoting). (p) Flooring : Aluminium chequerred plate 5 mm thick complete. (q) Signals :- (i) Combined luminous hall buttons with VFD hall position indicators at all floors. (ii) Vacuum filled Display (VFD) for car position indicator of stainless steel. (iii) One No. Car operating panel with Luminous buttons in car. (iv) Car direction indicator in car and landing. (v) Battery operated alarm bell and emergency light (rechargeable) alongwith suitable maintenance free battery. (vi) Overload warning feature in car cabin. (vii) Fireman’s switch 01 No. per lift to be installed at Ground floor near landing door. (viii) All signal fixture and car operating panel on stainless steel face plate. (ix) Full height standard infra red door sensor with 154 criss cross beams. Item continued as 29.09
(w) Hoist-Way Construction : RCC wall construction as existing at site, total height from Ground level to slab of machine room – As per OEM. Bidder shall inspect the same at site before quoting. (x) ACVVVF drive shall be of make OTIS / Johnson / Kone / Schindler / Thyssenkrupp. (y) Control System shall be closed loop type. (z) Door shall have ACVVVF controlled door operator. (za) Faceplate shape shall be Rectangular and stainless steel in Hairline Finish. (B) (zb) Civil Work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine etc and one coat of white wash in the lift shaft after completion of lift installation.
(a) Type of lift : Stretcher cum Passenger (15 Passengers) (b) Load capacity : 1020 Kg (c) Speed : 0.50 mtr/sec with single speed mortar (d) Power supply : 415 V, 3 phase, 4 wire AC, 50 Hz. (e) Type of drive : AC variable voltage and variable frequency. (f) Type of machine : Gearless (g) Car size : 1000x2400 mm or nearest suitable size as per OEM (maximum net inside car area - 2.47 Sqm, minimum net inside car area 2.35 sqm) as per IS:14665 (Part-3/Sec 1&2):2000, Well size: 1800x 3000 mm (h) Car door : Automatic centre opening with V3F door drive sliding type, stainless steel, hairline finish (N-304) for car and landing doors at all floors. (j) Car enclosure : Standard manufacturing with MS frame & stainless steel hairline finish (N-304) in standard thickness with LED light fitting on ceiling of appropriate type / size / Wattage and concealed axial flow fan with stainless steel grill and also 02 Nos. vertical down light LED lamp and covered with stainless steel wire mesh all as per OEM. (k) Terminal buffers : Special spring buffers. (l) Door opening (Inside) : 800 x 2000 mm (m) Counter weight shall be of cast iron as recommended by OEM (n) Car and counter weight guide : Guide rails of ‘T’ Section Mild Steel as per OEM design. Item continued as 29.13
(o) Clear Hoist Size : As per OEM. (Bidder shall inspect the same at site before quoting). (p) Flooring : Aluminium chequerred plate 5 mm thick complete. (q) Signals :- (i) Combined luminous hall buttons with VFD hall position indicators at all floors. (ii) Vacuum filled Display (VFD) for car position indicator of stainless steel. (iii) One No. Car operating panel with Luminous buttons in car. (iv) Car direction indicator in car and landing. (v) Battery operated alarm bell and emergency light (rechargeable) alongwith suitable maintenance free battery. (vi) Overload warning feature in car cabin. (vii) Fireman’s switch 01 No. per lift to be installed at Ground floor near landing door. (viii) All signal fixture and car operating panel on stainless steel face plate. (ix) Full height standard infra red door sensor with 154 criss cross beams. Item continued as 29.14
(w) Hoist-Way Construction : RCC wall construction as existing at site, total height from Ground level to slab of machine room – As per OEM. (Bidder shall inspect the same at site before quoting. (x) ACVVVF drive shall be of make OTIS / Johnson / Kone / Schindler / Thyssenkrupp. (y) Control System shall be closed loop type. (z) Door shall have ACVVVF controlled door operator. (za) Faceplate shape shall be Rectangular and stainless steel in Hairline Finish. (B) (zb) Civil Work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine etc and one coat of white wash in the lift shaft after completion of lift installation.
Sub total
GEYSER (Sch 'A' Part-XIX)
Supply, installation, testing and commissioning of water heater storage type electric geyser (vertical type) 25 Ltr capacity with BEE 5-Star rating (minimum) and metallic body procelain enamel glass lined inner tank including fixing arrangement with providing including suitable capacity flexible cable 3-core with 3-pin plug of 16 A capacity maximum 2 mtr length, PVC connection pipe of suitable length for Hot and Cold water, fixing on wall with and including all necessary fitting material i.e. mild steel bolts (Bolts to be grouted), nuts, washers, etc complete all as specified and as directed.
Sub total
MORTUARY CABINET & WALK-IN COOLER (Sch 'A' Part-XX)
Lump sum price worked out by the Contractor for “(MORTUARY CABINET & WALK-IN COOLER)” as listed in Schedule ‘A’ Part-XX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 36,271.60 inserted by the MES in Schedule ‘A’ Part-XX.
MORTUARY CABINET & WALK-IN COOLER (Sch 'A' Part-XX (A) (MISC)
Supply, installation, testing and commissioning Mortuary cabinet suitable for single phase, 230 V, 50 Hz, with 0.55 mm thick exterior and interior finish pre-painted GI Sheet, 0.5 mm thick front finish in stainless steel, including vapour proof incandescent lamp, electric temperature indicator cum controller, 3-phase carriage assembly, one piece stainless steel tray, inbuilt power panel, etc. suitable for unitary type refrigeration system and temperature range 4-6oC of capacity 02 body complete all as specified and as directed.
Supoly, installation, testing and commissioning of Walk-in Cold room of two chambers, freezer room of size 8'x8'x8' consisting of wall and ceiling panel made out of PGI sheet filled with 120 mm PUF insulation and Ante Room of size 5'x5'x8' consisting of wall and ceiling panel made out of PGI sheet filled with 60 mm PUF insulation, for Blood Bank and other low temperature application, anti skid GI flooring on 60 mm PUF, door of suitable dimension, hydraulic door closer, digital temperature indicator, Air cooled low temperature split unit of 2 HP rating with Reciprocating / Scroll Compressors working on R-134 a refrigerants to maintain temperature of 4 +2 degree Centigrade at an ambient temperature of 30 degree Centigrade complete all as specified and as directed.
Sub total
TELEPHONE / INTERCOM / MUSIC CABLE) (Sch 'A' Part-XXI)
Lump sum price worked out by the Contractor for “(TELEPHONE / INTERCOM / MUSIC CABLE))” as listed in Schedule ‘A’ Part-XXI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,22,192.00 inserted by the MES in Schedule ‘A’ Part-XXI.
TELEPHONE / INTERCOM / MUSIC CABLE) (Sch 'A' Part-XXI(A) (MISC)
S&F of Telephone jack RJ-11 with shuttes complete all as specified and as directed.
M&L for PVC insulated telephone cable for indoor application confirming to TEC specification GIWIR 06/02 of following size of 0.5 Sqmm ATC unarmoured complete all as specified and as directed :- Item Continued as 34.03 to 34.06
(a) 1 Pair
(b) 5 Pair
(c ) 10 Pair
(d) 20 Pair
S&F of junction DB (upto 20 pair) of telephones complete all as specified and as directed.
M&L for two single core PVC insulated copper conductor of size 1.5 Sqmm multistranded 1100 V grade drawn through steel conduit or duct for musical audio system complete all as specified and as directed. NOTE : Conduit & conduit accessories shall be measured and paid separately.
M&L for two single core PVC insulated copper conductor of size 2.5 Sqmm multistranded 1100 V grade drawn through steel conduit or duct for musical audio system complete all as specified and as directed. NOTE : Conduit & conduit accessories shall be measured and paid separately.
M&L for CA TV co-axial cable 75 Ohms double old / foam type aluminium foil and tinned copper drawn through steel conduit or duct for musical audio system complete all as specified and as directed. NOTE : Conduit & conduit accessories wall shall be measured and paid separately.
S&F of Distribution booster set for video system for 5/6 TV complete all as specified and as directed.
S&F of Co-axial socket for TV cable connection complete all as specified and as directed.
Sub total
NURSE CALL SYSTEM (Sch 'A' Part-XXII)
Supply, installation and commissioning of wireless nurse call system for 20 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed.
Supply, installation and commissioning of wireless nurse call system for 10 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed.
Supply, installation and commissioning of wireless nurse call system for 5 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed.
S&F of Wall Remote Call Switch for wireless nurse call system consisting of call and cancel button complete all as specified and as directed. NOTE : One nurse call system is for one ward / Dept.
Sub total
HAND DRYER (Sch 'A' Part-XXIII)
Supply and installation of automatic Soap Dispenser, ABS body with infrared sensor, operational with battery complete all as specified and as directed. Make : Ascon / Thoshi / Ultramind.
Sub total
PEDESTAL FAN (Sch 'A' Part-XXIV)
S&F of pedestal fan of 450 mm sweep AC, single phase, 230 V with all necessary fittings and accessories including provision of 3-core PVC insulated PVC sheated 3-Core multistranded copper conductor with 5 Amp plug top complete all as specified and as directed. Make : Havells Sprint - 18 HS or equivalent model in Usha / Bajaj.
Sub total
SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT (Sch 'A' Part-XXV)
Lump sum price worked out by the Contractor for “(SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT)” as listed in Schedule ‘A’ Part-XXV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 9,195.00 inserted by the MES in Schedule ‘A’ Part-XXV.
SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT (Sch 'A' Part-XXV) (MISC)
Supply only LED rechargeable portable emergency light with torch suitable for working on 230 V 50 Hz with battery, backup time 4-6 Hrs, auto on facility complete all as specified and as directed. Make : Philips model Ojas or equivalent in Havells / Bajaj.
Supply, install, testing and commissioning of Ceiling mounted double dome shadowless LED Operation theatre Light with illumination level 160000 lux and 110000 lux at 1 metre distance for larger dome and for smaller dome respectively fully counter balanced and fixed on suspension rod, capable of having axial rotation of 360 degree and in-built emergency backup system for 30 minutes. Make : Steris India Pvt Ltd” / Hospitech Industries or equivalent including fixing arrangement complete all as specified and as directed.
Supply, install, testing and commissioning of mobile double dome shadowless LED Operation theatre Light with illumination level 160000 lux and 110000 lux at 1 metre distance for larger dome and for smaller dome respectively fully counter balanced and fixed on suspension rod, capable of having axial rotation of 360 degree and in-built emergency back up system for 30 minutes. Make : Steris India Pvt Ltd” / Hospitech Industries or equivalent including fixing arrangement complete all as specified and as directed.
M&L for Skirting light white LED 3 x 1 Watt module including flush metal modular type box of 3 modules concealed in wall / roof / floor etc complete all as specified and as directed.
M&L for concealed sub-main wiring alongwith earth wire of size (2x1.50) Sqmm + (1x1.50) Sqmm earth wire, ISI marked, FRLS, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enameled steel conduit with all fittings and accessories ISI marked including cutting chases for conduits & sinking’s for modular boxes and making good to walls, floors etc complete all as specified and as directed. NOTE : Two runs of PVC wire, one run of earth wire and one run of steel conduit will be measured as one length.
M&L for concealed sub-main wiring alongwith earth wire of size (2x2.50) Sqmm + (1x2.50) Sqmm earth wire, ISI marked, FRLS, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enameled steel conduit with all fittings and accessories ISI marked including cutting chases for conduits & sinking’s for modular boxes and making good to walls, floors etc complete all as specified and as directed. NOTE : Two runs of PVC wire, one run of earth wire and one run of steel conduit will be measured as one length.
S&F MCB DB single pole & neutral 8 way, IP-43, IK-09, double door with 200 Amps rated common bus bar and neutral link complete including blanking plate all as specified and as directed.
S&F MCB DB triple pole and neutral 4 ways (8+12 ways), IP-43, IK-09, double door with 200 Amps rated common bus bar and neutral link complete including blanking plate all as specified and as directed.
M&L for RCBO double pole 2 modules, 240 V, 300mA, 32 Amps, earth leakage overhead and short circuit protection complete all as specified and as directed.
S&F of MCB, SP, 10 KA, 230 V, “C” Curve, 06-25 A, ISI marked complete all as specified and as directed.
S&F of MCB, TPN, 10 KA, 230 V, “C” Curve, 06-25 A, ISI marked complete all as specified and as directed.
Sub total
CONDUIT PIPE (Sch 'A' Part-XXVI)
Lump sum price worked out by the Contractor for “(CONDUIT PIPE)” as listed in Schedule ‘A’ Part-XXVI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,76,000.00 inserted by the MES in Schedule ‘A’ Part-XXVI.
UPS (Sch 'A' Part-XXVII)
Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 0.5 KVA with sealed lead acid battery 12 Volts 42 AH - 01 No. complete all as specified as directed. Make of UPS : Microtek / Luminous / Su kam. Make of Battery : Exide Power safe / Amaron / Luminous.
Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 1 KVA with sealed lead acid battery 12 Volts 9 AH - 06 Nos. complete all as specified as directed. Make of UPS : Microtek / Luminous / Su kam. Make of Battery : Exide Power safe / Amaron / Luminous.
Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 2 KVA with sealed lead acid battery 12 Volts 18 AH - 06 Nos. complete all as specified as directed. Make of UPS : Microtek / Luminous / Su kam. Make of Battery : Exide Power safe / Amaron / Luminous.
Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 3 KVA with sealed lead acid battery 12 Volts 26 AH - 06 Nos. complete all as specified as directed. Make of UPS : Microtek / Luminous / Su kam. Make of Battery : Exide Power safe / Amaron / Luminous.
Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 5 KVA with sealed lead acid battery 12 Volts 42 AH - 06 Nos. complete all as specified as directed. Make of UPS : Microtek / Luminous / Su kam. Make of Battery : Exide Power safe / Amaron / Luminous.
Supply, installation and testing on line UPS for 30 min back up three phase AC input 300 to 450 V and output 415 + 1% of capacity 3 KVA 3-phase 4-wire system with sealed lead acid battery 12 Volts with suitable AH capacity and No. of batteries as per OEM for 30 min backup complete all as specified as directed.
Supply, installation and testing on line UPS for 30 min back up three phase AC input 300 to 450 V and output 415 + 1% of capacity 5 KVA 3-phase 4-wire system with sealed lead acid battery 12 Volts with suitable AH capacity and No. of batteries as per OEM for 30 min backup complete all as specified as directed.
Sub total
DEMOLITION & DISMANTLING (Sch 'A' Part-XXVIII)
Lump sum price worked out by the Contractor for “(DEMOLITION & DISMANTLING)” as listed in Schedule ‘A’ Part-XXVIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 12,06,244.12 inserted by the MES in Schedule ‘A’ Part-XXVIII.
MANNING & OPERATION OF HVAC AND LIFT (Sch 'A' Part-XXIX)
COMPREHENSIVE MAINTENANCE OF LIFT (FOR 03 YEARS)
basis including Sunday and hoildays for the following lifts :- (a) 08 Passengers elevator of 544 Kg cap with travelling speed of 1.0 Mtr per second (Approx) to serve upto 3rd floor (G+3) including automatic rescue device (ARD) -03 Nos. (b) 15 Passengers (hospital stretchers) elevator of 1020 KG cap with travelling speed 00.5 Mtr per second (Appox) to serve upto 3rd floor (G+3) including automatic rescue device (ARD)-01 No. Note:- (i) The rates quoted above shall be inclusive of materials and labour for unserviceable items including rewinding of burnt motors and replacement of unserviceable Main rope & OSG Rope complete all as directed. (ii) Normally maintenance should be carried out in day time but in case of emergency / breakdown it should be attended at odd hours/night times without any extra cost & rate as quoted above shall be deemed to be inclusive of the same. (iii) All consumables maintenance materials such as oil, lubricants, grease, gland packing thimbles etc will be deemed to be included in the above schedule. (iv) This schedule shall be operational only after expiry of defect liability period from date of completion of contract. (v) The contractor will use only genuine / original new parts as approved by original equipment manufracturer (OEM). (vi) The older materials will be property of the contractor and a proper record to this effect shall be maintained. (vii) All the precautions against loss/damage shall be taken by the contractor. In case of any accident during operation of lift due to maintenance failure, the contractor is solely liaible to pay compensation as applicable.
Outsourcing for operation of Lifts of 155 BH on round the clock basis (one Lift operator in each shift, 03 Nos Shifts a day for each lift 04 Nos lifts) in reliable, safe & efficient operation conditions through qualified and experienced operators for the Lifts as mentioned Serial Item No. 43.03 here-in-above.
COMPREHENSIVE MAINTENANCE OF AC PLANT (FOR 03 YEARS)
Comprehensive maintenance including preventive and periodical maintenance of HVAC system reliable safe efficient operating condition through original equipmenl manufacturer (OEM) by regularly examine, lubricating and adjusting the equipment and carrying out planned maintanance in a systematic and controlled manner using technicians and expertise and replacement of all unserviceable components for Air conditioning Systems comprising of 2 x 180 TR (01 x Working, 01 x Standby) air cooled chilling manners with two redical rotary screw compressors two necessary refrigerator circuits direct expansion chiner air cooled compressor flow switches thermostat vibration isolators intregated refrigerant copper piping accessories automatic controls and safety controls starter for the compressor fans and compressors etc, complete as required at 155 BH for the following HVAC equipments for smooth functioning of HVAC system in three shifts per day each shift 8 Hrs including cost of materilas & qualified above to attend the daily complaints on urgent / immediate basis including Sunday and holidays for a period of 12 months after expiry of defect liability period after one year from successful completion of second seasonal test and taking over the installation of HVAC system. (a) Chilled water circulation pump (Primary pump) (1 x Working + 1 x Standby) - 03 Nos (b) Chilled water circulation pump (secondary pump ) (4W +4S )- 08 Nos (c) Electrical Hot water generators with all controls 400 KW -01 Set (d) Hot water ciculation Pump- 02 Nos. (e) Air circulation system with Fan Coil unit- (i) 1 TR- 08 Nos, (ii) 1.5 TR-56 Nos. (iii) 2 TR- 51 Nos, (iv) 2.5 TR- 7 Nos, (v) 3 TR-2 Nos Item Continued as 43.07
(f) Air-handling unit (AHU) of different sizes (g) Chilled - Hot water piping (h) Air distribution system , Grills, diffusers , electrical panels, different type measuring instruments, different type of valves and cables. Note:- (i) The rates quoted above shall be inclusive of material and labour for unserviceable items all as directed. (ii) The rates quoted shall be inclusive of T&P required for carrying repairs & stationery for maintaning of records all as described and specified. (iii) Normally maintanance carried out will be in day time but in case of emergency / breakdown it should be attended at odd hours/ night time without any extra cost & rate as quoted above. (iv) In case of break down the additional manpower if required will be arranged by the contractor & the rate shall be deemed to be inclusive of the same. (v) The contractor shall carryout daily routine checking of the complete system and rectify the minor/major defect noticed immediately. One separate register to be maintained as complaint register received from department / users and taking signature from users after rectifying the defects, if any. If complaint are not attended within six hours the penalties will be imposed and deducted from payments of the contractor. (vi) All consumables maintainance materials such as oil, lubricants, grease, gland packing thimbles etc will be deemed to be included in the above schedule. Item Continued as 43.08
(vii) The contractor will use only genuine / original new parts as approved by original equipment s manufracuturer. (viii) The old UNSV materilas will be property of the contractor and a proper record to this effect shall be maintained. (ix) All the precutions aganist loss/damage shall be taken by the contractor. In case of accident during operation / maintanance failure the contractor is solely liable to pay compensation as applicable . Note :- The contractor shall have AMC with the original equipment manufacturer of the HVAC system during the entire period covered above.
Outsourcing for operation of AC plant of 155 BH on round the clock basis (one operator in each shift of 08 hours) in reliable. safe & efficient operation conditions through qualified and experienced AC Plant Mechanic operators mentioned Serial Item No. 43.06 here-in-above.
Sub total
PRIME COST SUM
Provide prime cost sum of Rs. 16,00,000.00 for Design, Supply, Installation, testing and commissioning of Iron Removal Plant complete with oxidation chamber, face piping, fitting, valves, catalytic and filter media, made up of MS Shell of 8 mm thickness, under bed plate fitted with PVC strainer, pressure gauges, cocks, manhole, hand hole, air vent system, coagulant feeders, chlorinators, air compressor back washing facility including pressure filter of capacity 10000 Gallon/Hour, including RCC foundation and of capacity 10000 Gallon/Hour to get potable water conforming to IS with all interlocking pipes, valves and other accessories, necessary supports, clamps etc all complete. The media shall be of pebbles, crushed gravel, quartz filtering sand etc. as per requirement to achieve the desired quality of water. The proportion of different media shall be as per standard practice and as per IS requirement complete all as specified and as directed. NOTE : The Treatment Plant shall be capable of removal of all organic / inorganic materials / salts / iron etc from the water and make the water potable as per requirement of IS 10500-1991-Drinking water specifications. Contractor shall submit the design of filtration plant for approval of Accepting Officer before procurement. Necessary Chemical analysis report shall be provided by GE after commissioning of bore well. Any other accessories required for proper functioning of the plant also deemed to be included in the rate quoted for the item. *Add / Deduct ________ % (_______________ percentage) Rs. ___________________ * Above / Below SSR-2010 including all over head profit.
AKM CONSTRUCTION AND ENGINEERING LLP
MANGLA AMIT BUILDERS PVT LTD
City Promoter and Buildwell Pvt. Ltd.
KEC International Ltd
Rds Project ltd.
M P KHAITAN
PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED
Som Projects Pvt Ltd
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid